Page 41

Terminal CPX-P Technical data – Bus node CPX-FB11 Connection and display components

1

2

4

3

Pin allocation for the DeviceNet interface Pin allocation Pin

1 Bus-specific LEDs 2 CPX-P-specific status LEDs 3 Selectable fieldbus connection Micro Style Open Style 4 DIL switch cover

Signal-specific core colour1)

Signal

Designation

– Blue Black – Blank – White – Red n.c. CAN_L 0 V bus n.c. Screened n.c. CAN_H n.c. 24 V DC bus

Not connected Received/transmitted data low 0 V CAN interface Not connected Connection to housing Not connected Received/transmitted data high Not connected 24 V DC supply for CAN interface

Micro Style bus connection (M12), incoming/outgoing Incoming 1 Blank 2 Red

Screened 24 V DC bus

Connection to housing 24 V DC supply for CAN interface

Sub-D plug 1 2 3 4 5 6 7 8 9

Outgoing

3

Black

0 V bus

0 V CAN interface

4

White

CAN_H

Received/transmitted data high

5

Blue

CAN_L

Received/transmitted data low

1 2

Blank Red

Screened 24 V DC bus

Connection to housing 24 V DC supply for CAN interface

3

Black

0 V bus

0 V CAN interface

4

White

CAN_H

Received/transmitted data high

5

Blue

CAN_L

Received/transmitted data low

1

Black

0 V bus

0 V CAN interface

2

Blue

CAN_L

Received/transmitted data low

3

Blank

Screened

Connection to housing

4

White

CAN_H

Received/transmitted data high

5

Red

24 V DC bus

24 V DC supply for CAN interface

1

Black

Screened

Connection to housing

2

Blue

24 V DC

24 V DC supply for CAN interface

3

Blank

0V

0 V CAN interface

4

White

CAN_H

Received/transmitted data high

5

Red

CAN_L

Received/transmitted data low

Open Style bus connection

7/8" bus connection

1)

Typical for DeviceNet cables

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

41

Page 42

Terminal CPX-P Technical data – Bus node CPX-FB11 Ordering data Designation

Part No.

Type

DeviceNet bus node

526172

CPX-FB11

Sub-D plug

532219

FBS-SUB-9-BU-2x5POL-B

Connection block, 9-pin Sub-D socket, 5-pin 7/8" plug

571052

CPX-AB-1-7/8-DN

Micro Style bus connection, 2xM12

525632

FBA-2-M12-5POL

Socket for Micro Style connection, M12

18324

FBSD-GD-9-5POL

Plug for Micro Style connection, M12

175380

FBS-M12-5GS-PG9

Open Style bus connection for 5-pin terminal strip

525634

FBA-1-SL-5POL

Terminal strip for Open Style connection, 5-pin

525635

FBSD-KL-2x5POL

Cover cap for sealing unused M12 connections (10 pieces)

165592

ISK-M12

Inspection cover, transparent, for Sub-D connection

533334

AK-SUB-9/15-B

Inscription label holder for connection block

536593

CPX-ST-1

Inscription labels 6x10 mm, 64 pieces, in frames

18576

IBS-6x10

Bus node

Bus connection

Covers

Inscription label

42

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 43

Terminal CPX-P Technical data – Bus node CPX-FB11 Ordering data Designation

Part No.

Type

German English Spanish French Italian

526421 526422 526423 526424 526425

P.BE-CPX-FB11-DE P.BE-CPX-FB11-EN P.BE-CPX-FB11-ES P.BE-CPX-FB11-FR P.BE-CPX-FB11-IT

Adapter from 5-pin M12 to mini USB socket and controller software

547432

NEFC-M12G5-0.3-U1G5

User documentation User documentation for bus node CPX-FB11

Software

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

43

Page 44

Terminal CPX-P Technical data – Bus node CPX-FB13 Bus node for handling communication between the electrical CPX-P terminal and a higher-order master via PROFIBUS DP. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX-P terminal is displayed as a common message via four CPX-P-specific LEDs. The fieldbus communication status is displayed via the PROFIBUS-specific error LED.

Application Bus connection The bus connection is established via a 9-pin Sub-D socket with a typical PROFIBUS allocation (to EN 50170).

The bus connector plug (with IP65/IP67 protection from Festo or IP20 protection from other manufac­ turers) facilitates the connection of an incoming and an outgoing bus cable.

An active bus terminal can be connec­ ted using the DIL switch integrated in the plug.

The Sub-D interface is designed for controlling network components with a fibre-optic cable connection.

In addition to DPV0, acyclic commu­ nication to the advanced specification DPV1 is supported. DPV1 provides acyclic access to advanced system information and assigns operation parameters while the controller is running via the user program.

An example of this is access to the in­ tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type.

With its address capacity of 64 byte inputs and 64 byte outputs, the CPX-FB13 supports any configura­ tion of I/O modules, including pneumatic interface.

When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX-P control block.

In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX-P bus node is established by interlinking the CPX-P modules and occupies the following address capacity in the CPX-P system: 8 byte outputs 8 byte inputs

The remaining address capacity of the control block or CPX-P system for actuating the peripherals is: 56 byte inputs 56 byte outputs

44

è Internet: www.festo.com/catalogue/...

PROFIBUS DP implementation The CPX-FB13 supports the PROFIBUS DP protocol to EN 50170 Volume 2 for cyclic I/O exchange, parameterisation and diagnostic functions (DPV0).

Points to note in connection with CPX-CEC

Subject to change – 2018/04

Page 45

Terminal CPX-P Technical data – Bus node CPX-FB13 General technical data Type

CPX-FB13

Fieldbus interface Baud rate Addressing range

[Mbps]

Product range Ident. number Communication types Configuration support Max. address capacity

Inputs Outputs

[byte] [byte]

Nominal value Permissible range Power failure buffering

[V DC] [V DC] [ms] [mA]

Operation Storage/transport

[°C] [°C]

LED displays (bus-specific) Device-specific diagnostics Parameterisation Additional functions

Control elements Operating voltage

Current consumption Protection class to EN 60529 Temperature range

Materials RoHS status Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight

[mm] [mm] [g]

Sub-D socket, 9-pin (EN 50170) Galvanically isolated 5 V 0.0096 … 12 1 … 125 Set using DIL switch 4: Valves 0x059E DPV0: Cyclic communication DPV1: Acyclic communication GSD file and bitmaps 64 64 BF: Bus fault Identifier and channel-oriented diagnostics to EN 50170 (PROFIBUS standard) Start-up parameterisation via configuration interface in plain text (GSD) Acyclic parameterisation via DPV1 Storage of the last 40 errors with timestamp (access via DPV1) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table DIL switch 24 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC RoHs-compliant in accordance with EU Directive 50 50 x 107 x 50 115

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

45

Page 46

Terminal CPX-P Technical data – Bus node CPX-FB13 Connection and display components

1

2

4

3

Pin allocation for PROFIBUS DP interface Pin allocation Pin

1 Bus status LEDs/bus fault 2 CPX-P-specific status LEDs 3 Fieldbus connection (9-pin Sub-D socket) 4 DIL switch cover

Signal

Designation

1 2 3 4 5 6 7 8 9 Hous­ ing n.c. n.c. RxD/TxD-P CNTR-P1) DGND VP n.c. RxD/TxD-N n.c. Screened

Not connected Not connected Received/transmitted data P Repeater control signal Data reference potential (M5V) Supply voltage (P5V) Not connected Received/transmitted data N Not connected Connection to housing

1 2 3 4 5 and M12 n.c. RxD/TxD-N n.c. RxD/TxD-P Screened

Not connected Received/transmitted data N Not connected Received/transmitted data P Connection to FE (functional earth)

1 2 3 4 5 and M12

VP RxD/TxD-N DGND RxD/TxD-P Screened

Supply voltage (P5V) Received/transmitted data N Data reference potential (M5V) Received/transmitted data P Connection to FE (functional earth)

Sub-D socket

Bus connection M12 adapter (B-coded) Incoming

Outgoing

1)

46

The repeater control signal CNTR-P is a TTL signal..

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 47

Terminal CPX-P Technical data – Bus node CPX-FB13 Ordering data Designation

Part No.

Type

PROFIBUS bus node

195740

CPX-FB13

Sub-D plug, straight

532216

FBS-SUB-9-GS-DP-B

Sub-D plug, angled

533780

FBS-SUB-9-WS-PB-K

Bus connection, adapter from 9-pin Sub-D plug to 5-pin M12 plug/socket, B-coded

533118

FBA-2-M12-5POL-RK

Connection block, adapter from 9-pin Sub-D plug to 5-pin M12 plug/socket, B-coded

541519

CPX-AB-2-M12-RK-DP

Socket M12x1, 5-pin, straight, for self-assembly of a connecting cable compatible with FBA-2-M12-5POL-RK and CPX-AB-2-M12-RK-DP

1067905

NECU-M-B12G5-C2-PB

Plug M12x1, 5-pin, straight, for self-assembly of a connecting cable compatible with FBA-2-M12-5POL-RK and CPX-AB-2-M12-RK-DP

1066354

NECU-M-S-B12G5-C2-PB

Terminating resistor, M12, B-coded for PROFIBUS

1072128

CACR-S-B12G5-220-PB

Cover cap for sealing unused M12 connections (10 pieces)

165592

ISK-M12

Inspection cover, transparent, for Sub-D connection

533334

AK-SUB-9/15-B

Inscription label holder for connection block

536593

CPX-ST-1

Inscription labels 6x10 mm, 64 pieces, in frames

18576

IBS-6x10

Bus node

Bus connection

Covers

Inscription label

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

47

Page 48

Terminal CPX-P Technical data – Bus node CPX-FB13 Ordering data Designation

Part No.

Type

German English Spanish French Italian

526427 526428 526429 526430 526431

P.BE-CPX-FB13-DE P.BE-CPX-FB13-EN P.BE-CPX-FB13-ES P.BE-CPX-FB13-FR P.BE-CPX-FB13-IT

Adapter from 5-pin M12 to mini USB socket and controller software

547432

NEFC-M12G5-0.3-U1G5

User documentation User documentation for bus node CPX-FB13

Software

48

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 49

Terminal CPX-P Technical data – Bus node CPX-FB33 Bus node for operating the CPX-P valve terminal on PROFINET. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX-P terminal is displayed as a common message via four CPX-P-specific LEDs. The fieldbus communication status is displayed via three bus-specific LEDs.

Application Bus connection The bus connection is established via two M12 sockets, D-coded to IEC61076-2-101 with IP65, 67 protection.

Both connections are equivalent 100BaseTX Ethernet ports with integrated auto MDI functionality

(cross-over and patch cables can be used) that are brought together via an internal switch.

Maximum segment length 100 m Baud rate 100 Mbps process equipment. In addition, nonreal-time critical information such as diagnostic information, configuration information, etc. can be transferred. The Ethernet bandwidth is sufficient to transfer both data types (real-time and non-real-time) in parallel.

The bus node features LEDs for bus status and CPX-P peripheral informa­ tion as well as switch elements, memory stick and a diagnostic inter­ face. The purpose of the memory stick is to guarantee fast replacement of the bus node in the event of an error. PROFINET provides the user with access to all peripherals, diagnostic data and parameter data of the CPX-P valve terminal. The bus node can be used as a remote I/O or remote con­ troller. All information relevant to the CPX-P can be read out and, depending on the function, changed via an operator unit (CPX-MMI).

In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX-P bus node takes place by interlinking the CPX-P modules and takes up the following address capacity in the CPX-P system: 8 byte outputs 8 byte inputs

The remaining address capacity of the control block or CPX-P system for actuating the peripherals is: 56 byte inputs 56 byte outputs

PROFINET implementation The CPX-FB33 supports the PROFINET protocol based on the Ethernet standard and the TCP/IP technology to IEEE802.3. This guarantees a data exchange with a high data transmission rate, for example I/O data from sensors, actuators or robot controllers, PLCs or Points to note in connection with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX-P control block.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

49

Page 50

Terminal CPX-P Technical data – Bus node CPX-FB33 General technical data Type

CPX-FB33

Fieldbus interface Baud rate Protocol Max. address capacity LED displays

[Mbps]

Inputs Outputs (bus-specific)

[byte] [byte]

(product-specific)

Device-specific diagnostics

Configuration support Parameterisation

Additional functions

Control elements Operating voltage Current consumption Protection class to EN 60529 Temperature range

Nominal value Permissible range

[V DC] [V DC] [mA]

Operation Storage/transport Housing

[°C] [°C]

Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight

[mm] [mm] [g]

-H- Note

-H- Note

Please observe the general limits and guidelines for the system when configuring the electrical modules.

Always use screws appropriate to the interlinking block (metal or plastic):

50

è Internet: www.festo.com/catalogue/...

2x M12 socket, D-coded, 4-pin 100 PROFINET RT PROFINET IRT 64 64 M/P = Maintenance/PROFIenergy NF = Network fault TP1 = Network active port 1 TP2 = Network active port 2 M = Modify, parameterisation PL = Load supply PS = Electronic supply, sensor supply SF = System fault Channel and module-oriented diagnostics Undervoltage of modules Diagnostic memory GSDML file System parameters Diagnostic behaviour Signal setup Fail-safe response Forcing of channels Start-up parameterisation in plain text via fieldbus Fast startup (FSU) Channel-oriented diagnostics via fieldbus Acyclic data access via fieldbus System status can be represented using process data Additional diagnostic interface for operator units Acyclic data access via EtherCat DIL switch Optional memory card 24 18 … 30 Typically 120 IP65, IP67 –5 … +50 –20 … +70 Die-cast aluminium 50 50 x 107 x 50 280

Self-tapping screws for plastic interlinking blocks

Screws with metric thread for metal interlinking blocks

Subject to change – 2018/04