The text of a manual · part 6 of 10
Modular electrical terminal CPX-P, pages 51 to 60
Pages 51 to 60 of 99
The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Festo CPX-AB-8-KL
Page 51
Terminal CPX-P Technical data – Bus node CPX-FB33 Connection and display components
2
1 4
3
3
Pin allocation for the fieldbus interface Pin allocation
1 Bus-specific status LEDs 2 CPX-P-specific status LEDs 3 Fieldbus connection (4-pin socket M12, D-coded) 4 Transparent cover for DIL switch and memory card
Pin
Signal
Designation
1
TD+
Transmitted data+
2
RD+
Received data+
3
TD-
Transmitted data-
4
RD-
Received data-
M12 socket, D-coded
Housing
2018/04 – Subject to change
Screened
è Internet: www.festo.com/catalogue/...
51
Page 52
Terminal CPX-P Technical data – Bus node CPX-FB33 Ordering data Designation
Part No.
Type
PROFINET bus node
548755
CPX-FB33
Plug M12x1, 4-pin, D-coded
543109
NECU-M-S-D12G4-C2-ET
Cover cap for sealing unused M12 connections (10 pieces)
165592
ISK-M12
Transparent cover for DIL switch and memory card
548757
CPX-AK-P
Memory card for PROFINET bus node, 2 MB
568647
CPX-SK-2
Screws for attaching an inscription label holder to the bus node (12 pieces)
550222
CPX-M-M2,5X8-12X
Electronics manual, CPX-P bus node, type CPX-FB33
German English Spanish French Italian
548759 548760 548761 548762 548763
P.BE-CPX-PNIO-DE P.BE-CPX-PNIO-EN P.BE-CPX-PNIO-ES P.BE-CPX-PNIO-FR P.BE-CPX-PNIO-IT
Adapter from 5-pin M12 to mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
Bus node
Bus connection
Covers
Function block
Screws
User documentation
Software
52
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 53
Terminal CPX-P Technical data – Input module, digital, NAMUR Function Digital input modules enable the con nection of up to eight NAMUR sensors (or wired mechanical contacts). In addition, the first four channels can alternatively be used as counters or for frequency measurement. M12 and terminal strip connection technology can be used.
Applications Input modules for 24 V DC sensor supply voltage Module features can be parameterised The input module receives the voltage supply for the electronics and the sensors from the interlinking block Module protection and diagnostics through integrated electronic fuse protection in each channel
General technical data Number of inputs Max. cable length Input debounce time Fuse protection (short circuit) Module current consumption (voltage supply for electronics) Nominal operating voltage Permissible voltage fluctuations Power failure buffering Residual ripple Electrical isolation Channel – channel Channel – internal bus Input characteristic curve Switching level LED displays Group diagnostics Channel diagnostics Channel status Diagnostics
Protection class to EN 60529
8 200 3 (0, 10, 20 parameterisable) Internal electronic fuse for each channel Typically 75 24 (reverse polarity protected) ±25 20 0.4 No Yes To EN 60947-5-6 To EN 60947-5-6 1 8 8 Wire break per channel Limit value violation per channel Parameterisation error Overload per channel Data format Input debounce time per channel Input function per channel Replacement value in diagnostic case per channel Upper limit value per channel Signal extension time per channel Gate time per channel Monitoring of limit value per channel Monitoring of short circuit per channel Monitoring of wire break per channel Monitoring of parameters Lower limit value per channel Upper limit value per channel Counter configuration per channel DIL switch Frequency measurement Counter operation Depending on connection block
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
Parameterisation
Control elements Additional functions
[m] [ms] [mA] [V DC] [%] [ms] [Vss]
53
Page 54
Terminal CPX-P Technical data – Input module, digital, NAMUR General technical data Grid dimension Dimensions (incl. interlinking block and connection block) W x L x H Product weight
[mm] [mm] [g]
Explosion protection parameters of the module inputs Type Maximum output power Maximum output voltage Maximum output current Maximum external inductance Maximum external capacitance
[mW] [V] [mA] [mH] [μF]
Certifications and approvals – Maximum values Type ATEX category for gas Explosion ignition protection type for gas ATEX category for dust Explosion ignition protection type for dust Explosion protection certification outside the EU
Explosion-proof temperature Certificate issuing authority
[°C]
50 50 x 107 x 70 100
CPX-P-8DE-N
CPX-P-8DE-N-IS
– – – – –
42 10 16.8 125 3
CPX-P-8DE-N
CPX-P-8DE-N-IS
– – – – – – – – – – – –
II (1) G [Ex ia Ga] IIC II (1) D [Ex ia Da] IIIC EPL Ga (IEC-EX) EPL Da (IEC-EX) EPL Ga (BR) EPL Da (BR) –5 ≤ Ta ≤ +70 ZELM 12 ATEX 0500 X IECEx ZLM 12.0007 X DNV 15.0192 X
-H- Note
-H- Note
-H- Note
-H- Note
The module CPX-P-8DE-N-IS has additional safety measures for pos sible faults such as non-resettable fuses to ensure safe operation as per the ignition protection type. If the module is operated within the permissible parameters, these pro tective measures will be irrelevant.
Only the end plate, the pneumatic interface or another module in in trinsically safe design are permitted directly to the right of modules in intrinsically safe design (CPX-P-8DE-N-IS) within the CPX-P terminal.
The insulating plate CPX-P-AB-IP must be mounted between a module in intrinsically safe design (CPX-P-8DE-N-IS) and another, non-intrinsically safe CPX input or output module.
The above-mentioned certifications for the CPX-P-8DE-N-IS module do not apply if the module is used out side the appropriately configured terminal CPX-P.
Materials Housing
PA reinforced PC RoHS-compliant
Note on materials Operating and environmental conditions Type Ambient temperature Storage temperature Relative air humidity CE marking (see declaration of conformity)1)
1)
54
[°C] [°C] [%]
CPX-P-8DE-N
CPX-P-8DE-N-IS
–5 … +50 –20 … +70 95, non-condensing
–5 … +50 –20 … +70 95, non-condensing To EU Explosion Protection Directive (ATEX)
–
Additional information www.festo.com/sp è Certificates.
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 55
Terminal CPX-P Technical data – Input module, digital, NAMUR Connection and display components 3 4
1
2
1 Status LEDs (green) For allocation to inputs è Pin allocation for module 2 Channel-related error LEDs (red) 3 Error LED (red, module error) 4 Marking for intrinsically safe variant, CPX-P-8DE-N-IS (blue)
Connection block/digital input module combinations Connection blocks Part No. CPX-P-AB-4XM12-4POL CPX-P-AB-2XKL-8POL CPX-P-AB-4XM12-4POL-8DE-N-IS CPX-P-AB-2XKL-8POL-8DE-N-IS
Pin allocation Connection block outputs
565706 565704 565705 565703
CPX-P-8DE-N-IS n n – –
– – n n
CPX-P-8DE-N and CPX-P-8DE-N-IS
CPX-P-AB-4XM12-4POL and CPX-P-AB-4XM12-4POL-8DE-N-IS X1.1: BN+ [0] X1.2: BU– [0] X1.3: BN+ [1] X1.4: BU– [1]
X2.1: X2.2: X2.3: X2.4:
BN+ [2] BU– [2] BN+ [3] BU– [3]
CPX-P-AB-2XKL-8POL and CPX-P-AB-2XKL-8POL-8DE-N-IS X1.1: BN+ [0] X1.2: BU– [0] X1.3: BN+ [1] X1.4: BU– [1] X1.5: X1.6: X1.7: X1.8:
2018/04 – Subject to change
Digital input module CPX-P-8DE-N
BN+ [2] BU– [2] BN+ [3] BU– [3]
X3.1: X3.2: X3.3: X3.4:
BN+ [4] BU– [4] BN+ [5] BU– [5]
X4.1: X4.2: X4.3: X4.4:
BN+ [6] BU– [6] BN+ [7] BU– [7]
X2.1: X2.2: X2.3: X2.4:
BN+ [4] BU– [4] BN+ [5] BU– [5]
X2.5: X2.6: X2.7: X2.8:
BN+ [6] BU– [6] BN+ [7] BU– [7]
è Internet: www.festo.com/catalogue/...
55
Page 56
Terminal CPX-P Technical data – Input module, digital, NAMUR Ordering data Name
Part No.
Type
Input module, digital, to NAMUR 8 digital inputs 8 digital inputs, intrinsically safe design
565933 565934
CPX-P-8DE-N CPX-P-8DE-N-IS
-H- Note An intrinsically safe circuit may only be constructed using components and accessories approved for intrinsically safe operation.
Connection block Plastic
4x socket, M12, 4-pin
For non-intrinsically safe design
565706
CPX-P-AB-4XM12-4POL
For intrinsically safe design
565705
CPX-P-AB-4XM12-4POL-8DE-N-IS
2x plug, 8-pin
For non-intrinsically safe design
565704
CPX-P-AB-2XKL-8POL
For intrinsically safe design
565703
CPX-P-AB-2XKL-8POL-8DE-N-IS
Push-in T-connector
1x plug M12, 4-pin
2x socket M12, 4-pin
562248
NEDU-M12D4-M12T4-IS1)
Socket
8-pin
Spring-loaded terminal Screw terminal
Plug, M12, 4-pin
Spring-loaded terminal Screw terminal
Black Gentian blue Black Gentian blue For cable 4 … 8 mm
565712 565711 565710 565709 575719
NECU-L3G8-C1 NECU-L3G8-C1-IS1) NECU-L3G8-C2 NECU-L3G8-C2-IS1) NECU-M-S-A12G4-IS1)
For cable 2.5 … 2.9 mm For cable 4 … 6 mm For cable 6 … 8 mm For cable 2x3 mm or 2x5 mm
570955 570953 570954 570956
NECU-S-M12G4-P1-Q6-IS1) NECU-S-M12G4-P1-IS1) NECU-S-M12G4-P2-IS1) NECU-S-M12G4-D-IS1)
Plug
Cover Cover cap for sealing unused connections (10 pieces)
For M12 connections
165592
ISK-M12
Ensures that a coded socket NECU-L3G8 can only be inserted in the matching coded connection block CPX-P-AB-2XKL (96 pieces of each)
For NECU-L3G8
565713
CPX-P-KDS-AB-2XKL
Insulating plate for safe separation of intrinsically safe and non-intrinsically safe areas of the CPX terminal
565708
CPX-P-AB-IP
User documentation
575378 575379 575380 575381 575382 575383
P.BE-CPX-P-EA-DE P.BE-CPX-P-EA-EN P.BE-CPX-P-EA-ES P.BE-CPX-P-EA-FR P.BE-CPX-P-EA-IT P.BE-CPX-P-EA-SV
Coding element
Screening plate
User documentation
1)
56
German English Spanish French Italian Swedish
Component preferred for operation in intrinsically safe circuits.
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 57
Terminal CPX-P Technical data – Input module, digital, 8 inputs Function Digital input modules enable the connection of two-wire and three-wire sensors (proximity sensors, inductive or capacitive sensors, etc.). Depending on the connection block selected, the module supports various connection concepts with different numbers of sockets (single or double allocation).
Area of application Input modules for 24 V DC sensor supply voltage PNP or NPN logic Supports connection blocks with M12, M8, Sub-D, HARAX® and terminal connection Module features can be parameterised Input module receives the voltage supply for the electronics and the sensors from the interlinking block Module protection and diagnostics through integrated electronic fuse protection
General technical data Type Number of inputs Max. residual current of inputs per module Fuse protection Intrinsic current consumption at operating voltage Operating voltage Nominal value Permissible range Electrical isolation Channel – channel Channel – internal bus Switching level Signal 0 Signal 1 Input debounce time Input characteristic Switching logic LED displays Group diagnostics Channel diagnostics Channel status Diagnostics Parameterisation
Degree of protection to EN 60529 Temperature range
Operation Storage/transport
Materials Grid dimension Dimensions (incl. interlinking block and connection block) W x L x H Product weight
2018/04 – Subject to change
[A] [mA] [V DC] [V DC]
[V DC] [V DC] [ms]
[°C] [°C] [mm] [mm] [g]
CPX-8DE
CPX-8NDE
8 1 Internal electronic fuse per module Typically 15 24 18 … 30 No No 5 11 3 (0.1, 10, 20 parameterisable) IEC 1131-T2 Positive logic (PNP) 1 – 8 Short circuit/overload per channel Module monitoring Behaviour after short circuit Input debounce time Signal extension time Depending on connection block –5 … +50 –20 … +70 PA reinforced, PC 50 50 x 107 x 50 38
8 0.7
è Internet: www.festo.com/catalogue/...
11 5
Negative logic (NPN) 1 – 8
57
Page 58
Terminal CPX-P Technical data – Input module, digital, 8 inputs Connection and display components CPX-8DE
CPX-8NDE
2
1
2
1 Status LEDs (green) For allocation to outputs è Pin allocation for module 2 Error LED (red, module error)
For allocation to inputs è Pin allocation for module
1
Connection block/digital input module combinations Connection blocks Part No. CPX-AB-8-M8-3POL CPX-AB-4-M12X2-5POL CPX-AB-4-M12X2-5POL-R CPX-AB-8-KL-4POL CPX-AB-1-SUB-BU-25POL CPX-AB-4-HAR-4POL CPX-M-AB-4-M12X2-5POL
195706 195704 541254 195708 525676 525636 549367
Pin allocation Connection block inputs
CPX-8DE and CPX-8NDE
Digital input modules CPX-8DE
CPX-8NDE n n n n n n n n n n n n n n
CPX-AB-8-M8-3POL X1.1: 24 VSEN x X1.3: 0 VSEN x X1.4: Input x
X5.1: 24 VSEN x+4 X5.3: 0 VSEN x+4 X5.4: Input x+4
X2.1: 24 VSEN x+1 X2.3: 0 VSEN x+1 X2.4: Input x+1
X6.1: 24 VSEN x+5 X6.3: 0 VSEN x+5 X6.4: Input x+5
X3.1: 24 VSEN x+2 X3.3: 0 VSEN x+2 X3.4: Input x+2
X7.1: 24 VSEN x+6 X7.3: 0 VSEN x+6 X7.4: Input x+6
X4.1: 24 VSEN x+3 X4.3: 0 VSEN x+3 X4.4: Input x+3
X8.1: 24 VSEN x+7 X8.3: 0 VSEN x+7 X8.4: Input x+7
CPX-AB-4-M12X2-5POL, CPX-AB-4-M12X2-5POL-R1 X1.1: 24 VSEN x X1.2: Input x+1 X1.3: 0 VSEN x X1.4: Input x X1.5: FE X2.1: X2.2: X2.3: X2.4: X2.5: 1)
58
24 VSEN x+2 Input x+3 0 VSENx+2 Input x+2 FE
X3.1: X3.2: X3.3: X3.4: X3.5:
24 VSEN x+4 Input x+5 0 VSEN x+4 Input x+4 FE
X4.1: X4.2: X4.3: X4.4: X4.5:
24 VSEN x+6 Input x+7 0 VSEN x+6 Input x+6 FE
Speedcon quick lock, screening additionally on metal thread
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 59
Terminal CPX-P Technical data – Input module, digital, 8 inputs Pin allocation Connection block inputs
CPX-8DE and CPX-8NDE
CPX-AB-8-KL-4POL X1.0: X1.1: X1.2: X1.3:
24 VSEN x 0 VSEN x Input x FE
X5.0: X5.1: X5.2: X5.3:
24 VSEN x+4 0 VSEN x+4 Input x+4 FE
X2.0: X2.1: X2.2: X2.3:
24 VSEN x+1 0 VSEN x+1 Input x+1 FE
X6.0: X6.1: X6.2: X6.3:
24 VSEN x+5 0 VSEN x+5 Input x+5 FE
X3.0: X3.1: X3.2: X3.3:
24 VSEN x+2 0 VSEN x+2 Input x+2 FE
X7.0: X7.1: X7.2: X7.3:
24 VSEN x+6 0 VSEN x+6 Input x+6 FE
X4.0: X4.1: X4.2: X4.3:
24 VSEN x+3 0 VSEN x+3 Input x+3 FE
X8.0: X8.1: X8.2: X8.3:
24 VSEN x+7 0 VSEN x+7 Input x+7 FE
1: 2: 3: 4: 5: 6: 7: 8: 9: 10: 11: 12: 13:
Input x Input x+1 Input x+2 Input x+3 24 VSEN x+1 0 VSEN x+1 24 VSEN x+3 0 VSEN x+3 24 VSEN x 24 VSEN x+2 0 VSEN x 0 VSEN x+2 FE
14: Input x+4 15: Input x+5 16: Input x+6 17: Input x+7 18: 24 VSEN x+4 19: 24 VSEN x+5 20: 24 VSEN x+6 21: 24 VSEN x+7 22: 0 VSEN x+2 u. 3 23: 0 VSEN x+2 u. 3 24: 0 VSEN x+2 u. 3 25: FE Housing: FE
X1.1: X1.2: X1.3: X1.4:
24 VSEN x Input x+1 0 VSEN x Input x
X3.1: X3.2: X3.3: X3.4:
24 VSEN x+4 Input x+5 0 VSEN x+4 Input x+4
X2.1: X2.2: X2.3: X2.4:
24 VSEN x+2 Input x+3 0 VSEN x+2 Input x+2
X4.1: X4.2: X4.3: X4.4:
24 VSEN x+6 Input x+7 0 VSEN x+6 Input x+6
CPX-AB-1-SUB-BU-25POL
CPX-AB-4-HAR-4POL
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
59
Page 60
Terminal CPX-P Accessories – Input module, digital, 8 inputs Ordering data Description
Part No.
Type
8 digital inputs, positive logic (PNP)
195750
CPX-8DE
8 digital inputs, negative logic (NPN)
543813
CPX-8NDE
Plastic
195706 195704 541254 195708 525676 525636 549367
CPX-AB-8-M8-3POL CPX-AB-4-M12X2-5POL CPX-AB-4-M12X2-5POL-R CPX-AB-8-KL-4POL CPX-AB-1-SUB-BU-25POL CPX-AB-4-HAR-4POL CPX-M-AB-4-M12X2-5POL
Modular system for all types of sensor/actuator distributor
–
NEDY-… è Internet: nedy
1x plug connector M12, 4-pin
2x socket M8, 3-pin
8005311
NEDY-L2R1-V1-M8G3-N-M12G4
2x socket, M12, 5-pin
8005310
NEDY-L2R1-V1-M12G5-N-M12G4
HARAX® plug connector, 4-pin
18696 192009 18666 192008 18778 18779 192010 175487 525928
SEA-GS-M8 SEA-3GS-M8-S SEA-GS-7 SEA-4GS-7-2,5 SEA-GS-9 SEA-GS-11-DUO SEA-5GS-11-DUO SEA-M12-5GS-PG7 SEA-GS-HAR-4POL
Sub-D plug connector, 25-pin
527522
SD-SUB-D-ST25
541346 541347 541348 541349 –
NEBU-M8G3-K-0.5-M8G3 NEBU-M8G3-K-1-M8G3 NEBU-M8G3-K-2.5-M8G3 NEBU-M8G3-K-5-M8G3 NEBU-… è Internet: nebu
Input module, digital
Connection block 8x socket M8, 3-pin 4x socket M12, 5-pin 4x socket, M12 with quick-lock technology, 5-pin Spring-loaded terminal, 32-pin 1x socket, Sub-D, 25-pin 4x socket, quick connector, 4-pin 4x socket M12, 5-pin
Metal Distributor
Plug connector Plug connector
M8, 3-pin
Solderable Screw-in
M12, 4-pin, PG7 M12, PG7, 4-pin for cable diameter 2.5mm M12, 4-pin, PG9 M12, 4 pin for 2 cables M12 for 2 cables, 5-pin M12, 5-pin
Connecting cable Connecting cable M8-M8
Modular system for connecting cables
60
è Internet: www.festo.com/catalogue/...
0.5 m 1.0 m 2.5 m 5.0 m
Subject to change – 2018/04