Page 81
-V- New Terminal CPX Technical data – HART input/output module Function The HART input/output module allows for connection of up to 4 sensors or actuators. The corresponding communication channel is made available for sensors or actuators that communicate using the HART protocol. With the HART protocol, a conven tional analogy 4 … 20 mA current signal is modulated by a second frequency-modulated signal. Each of the 4 connections of the module can be configured as inputs or outputs.
Area of application Multi I/O module for 24 V DC supply voltage Supports manifold blocks with M12 and terminal connection Module features can be parameterised The module receives the voltage supply for the electronics, outputs and the sensors from the interlinking block Module protection and diagnostics through integrated electronic fuse protection
General technical data Type code Protocol Number of selectable analogue inputs/outputs Sensor type Operating voltage Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Maximum short circuit current Maximum open circuit voltage Minimum available sensor voltage Fuse protection (short circuit) Reverse polarity protection Electrical isolation Channel – channel Channel – internal bus Signal range Data format Maximum load Maximum input resistance Maximum cable length Basic error limit at 25 °C Operating error limit related to the ambient temperature range Repetition accuracy LED indicators Group diagnostics Channel diagnostics Channel status Control elements
2018/04 – Subject to change
CPX-4AE-4AA-H
[V DC] [V DC] [ms] [mA] [mA] [V]
[Ω] [Ω] [m] [%] [%]
HART 4 0 … 20 mA 4 … 20 mA 24 18 … 30 10 Typically 170 22 28.8 20.7 V DC at 20 mA Internal electronic fuse per channel For all electrical connections No Yes 0 … 20 mA 4 … 20 mA 15 bits + prefix Scalable to 15 bits 750 300 500 ±0.1 ±0.3 0.05% at 20ºC 1 4 4 DIL switch
è Internet: www.festo.com/catalogue/...
4 … 20 mA with HART
4 … 20 mA with HART
81
Page 82
-V- New Terminal CPX Technical data – HART input/output module General technical data Wire break per channel Limit value violation per channel Short circuit/overload per channel Parameterisation error Overflow/underflow Limit value violation to NE43 per channel Data format Failsafe per channel Forcing per channel Limit monitoring per channel Idle mode per channel Measured value smoothing Signal range per channel Monitoring of overflow/underflow Monitoring according to NE43, inputs Behaviour after short circuit/overload Monitoring wire break per channel Number of HART repetitions Hysteresis for limit values HART variables (4 pieces) Depending on manifold block
Diagnostics
Parameterisation
Degree of protection to EN 60529 Technical data – Mechanical Type of mounting Product weight Grid dimension Dimensions (incl. interlinking block and manifold block) WxLxH
[g] [mm] [mm]
On interlinking block 77.4 50 50 x 107 x 70
Materials Housing Note on materials
PA reinforced, PC RoHS-compliant
Operating and environmental conditions Ambient temperature Storage temperature Relative humidity Corrosion resistance class CRC1) CE marking (see declaration of conformity)3) 1)
2) 3)
[°C] [°C] [%]
–5 … +50 –20 … +70 95, non-condensing 1 (when installed) To EU EMC Directive2)
Corrosion resistance class CRC 1 to Festo standard FN 940070 Low corrosion stress. For dry indoor applications or transport and storage protection. Also applies to parts behind covers, in the non-visible interior area, and parts which are covered in the application (e.g. drive trunnions). For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com/sp è Certificates. If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary. Additional information www.festo.com/sp è Certificates.
Safety data Shock resistance Vibration resistance
82
Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 83
-V- New Terminal CPX Technical data – HART input/output module Connection and display components CPX-4EA-4AA-H 3
1
2
1 Status LEDs: – Inputs (green) – Outputs (yellow) è Pin allocation for module 2 Error LEDs (red) Allocation to inputs/outputs è Pin allocation for module
Combinations of bus nodes/control blocks with HART input/output module Bus node/control block Part No. Protocol CPX-FB13 CPX-FB33
3 Error LED (red) (module error)
HART input/output module CPX-4EA-4AA-H n n
PROFIBUS PROFINET RT, M12
195740 548755
-H- Note The HART input/output module CPX-4EA-4AA-H can only be connec tion as of software release 33 or 34 (in the case of CPX-FB13). Combinations of manifold blocks with HART input/output module Manifold blocks Part No. CPX-P-AB-4XM12-4POL CPX-P-AB-2XKL-8POL
2018/04 – Subject to change
565706 565704
HART input/output module CPX-4EA-4AA-H n n
è Internet: www.festo.com/catalogue/...
83
Page 84
-V- New Terminal CPX Technical data – HART input/output module Pin allocation Manifold block inputs/outputs
CPX-4AE-4AA-H Inputs
Outputs
CPX-P-AB-4XM12-4POL X1.1: X1.2: X1.3: X1.4:
24 VSEN x 0V Input x 0V
X3.1: X3.2: X3.3: X3.4:
24 VSEN x+2 0V Input x+2 0V
X1.1: X1.2: X1.3: X1.4:
Output I0+ 0V – 0V
X3.1: X3.2: X3.3: X3.4:
Output I2+ 0V – 0V
X2.1: X2.2: X2.3: X2.4:
24 VSEN x+1 0V Input x+1 0V
X4.1: X4.2: X4.3: X4.4:
24 VSEN x+3 0V Input x+3 0V
X2.1: X2.2: X2.3: X2.4:
Output I1+ 0V – 0V
X4.1: X4.2: X4.3: X4.4:
Output I3+ 0V – 0V
X1.1: X1.2: X1.3: X1.4:
24 VSEN x 0V Input x 0V
X2.1: X2.2: X2.3: X2.4:
24 VSEN x+2 0V Input x+2 0V
X1.1: X1.2: X1.3: X1.4:
Output I0+ 0V – 0V
X2.1: X2.2: X2.3: X2.4:
Output I2+ 0V – 0V
X1.5: X1.6: X1.7: X1.8:
24 VSEN x+1 0V Input x+1 0V
X2.5: X2.6: X2.7: X2.8:
24 VSEN x+3 0V Input x+3 0V
X1.5: X1.6: X1.7: X1.8:
Output I1+ 0V – 0V
X2.5: X2.6: X2.7: X2.8:
Output I3+ 0V – 0V
CPX-P-AB-2XKL-8POL
-H- Note In the case of mixed operation of inputs and outputs in one module, the connections are first assigned input signals and then output signals, in ascending order.
84
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 85
-V- New Terminal CPX Accessories – HART input/output module Ordering data Designation
Part No.
Type code
HART input/output module 4 analogue inputs/outputs
8059847
CPX-4AE-4AA-H
4x socket, M12, 4-pin
565706
CPX-P-AB-4XM12-4POL
2x plug, 8-pin
565704
CPX-P-AB-2XKL-8POL
Manifold block Plastic
Connectors 8-pin socket
Plug M12x1, 4-pin, straight, A-coded
Spring-loaded terminal
Connecting cross-section 0.2 … 2.5 mm2
565712
NECU-L3G8-C1
Screw terminal
Connecting cross-section 0.2 … 2.5 mm2
565710
NECU-L3G8-C2
Insulation displacement connector Screw terminal
Connecting cross-section 0.25 … 0.5 mm2
525928
SEA-GS-HAR-4POL
Connecting cross-section 0.14 … 0.5 mm2 Connecting cross-section 0.75 mm2 permissible cable 4 … 6 mm Connecting cross-section 0.75 mm2 permissible cable 6 … 8 mm
192008 18666
SEA-4GS-7-2,5 SEA-GS-7
18778
SEA-GS-9
165592
ISK-M12
565713
CPX-P-KDS-AB-2XKL
Cover Cover cap for sealing unused ports M12x1 (10 pieces)
Coding element Ensures that a coded socket NECU-L3G8 can only be inserted in the matching coded manifold block CPX-P-AB-2XKL (96 pieces of each)
2018/04 – Subject to change
For NECU-L3G8
è Internet: www.festo.com/catalogue/...
85
Page 86
Terminal CPX-P Technical data – Interlinking block with system supply Function Interlinking blocks ensure the electrical supply of all other CPX-P modules. They have contact rails, from which the other CPX-P components on the interlinking modules are supplied with current. Internal division of the power supply makes it possible to switch off specific areas of the sensors and actuators individually.
Applications 24 V DC supply voltage for electronics of the CPX-P terminal 24 V DC supply voltage for inputs 24 V DC supply voltage for valves 24 V DC supply voltage for outputs
General technical data Nominal operating voltage Protection class to EN 60529 Ambient temperature Note on materials Grid dimension Dimensions W x L x H Electrical connection Current supply
[V DC] [°C] [mm] [mm] Sensors and electronics Valves and outputs
Materials Product weight
[A] [A] [g]
Pin allocation Circuitry
24 Depending on connection block –5 … +50 RoHS-compliant 50 50 x 107 x 35 7/8", 5-pin Max. 8 Max. 8 Die-cast aluminium 187
Pin
Allocation
1
0 V valves and outputs
2
0 V electronics and sensors
3
FE
4
24 V DC supply voltage for electronics and sensors
5
24 V DC load voltage supply for valves and outputs
Round plug, 5-pin 7/8"
86
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 87
Terminal CPX-P Technical data – Interlinking block with system supply Ordering data Designation Interlinking block with system supply 7/8" connection, metal interlinking block
5-pin
–
Part No.
Type
550208
CPX-M-GE-EV-S-7/8-5POL
For ATEX environment 8022165
7/8" connection sockets Power supply socket
CPX-M-GE-EV-S-7/8-5POL-VL
5-pin
543107
NECU-G78G5-C2
Angled socket, 5-pin – open cable end, 5-pin
2m
573855
NEBU-G78W5-K-2-N-LE5
Screws for mounting the bus node/connection block on an interlinking block
Bus node/plastic connection 550219 block Bus node/metal connection block 550216
Mounting accessories
2018/04 – Subject to change
CPX-M-M3x22-4x CPX-M-M3x22-S-4x
è Internet: www.festo.com/catalogue/...
87
Page 88
Terminal CPX-P Technical data – Interlinking block Function Interlinking blocks ensure the electrical supply of all other CPX-P modules. They have contact rails, from which the other CPX-P components on the interlinking modules are supplied with current. Internal division of the power supply makes it possible to switch off specific areas of the sensors and actuators individually.
Applications All voltages are fed through to the next module by means of interlinking blocks. The connected electronics module for inputs/outputs or bus node taps off the required voltage.
General technical data Electrical connection Nominal operating voltage Acceptable current load (per contact/contact rail) Protection class to EN 60529 Ambient temperature Note on materials Materials Grid dimension Dimensions W x L x H Product weight
[V DC] [A] [°C]
[mm] [mm] [g]
Pin allocation Circuitry
88
è Internet: www.festo.com/catalogue/...
– 24 16 Depending on connection block –5 … +50 RoHS-compliant Aluminium 50 50 x 107 x 35 169
Pin
Allocation
–
–
–
–
–
–
–
–
Subject to change – 2018/04
Page 89
Terminal CPX-P Technical data – Interlinking block Ordering data Designation
Part No.
Type
Interlinking block without supply Metal interlinking block
550206
CPX-M-GE-EV
550219
CPX-M-M3x22-4x
550216
CPX-M-M3x22-S-4x
Mounting accessories Screws for mounting the bus node/connection block on an interlinking block
2018/04 – Subject to change
Bus node/plastic connection block Bus node/metal connection block
è Internet: www.festo.com/catalogue/...
89
Page 90
Terminal CPX-P Technical data – Interlinking block with additional power supply for outputs Function Interlinking blocks ensure the electrical supply of all other CPX-P modules. They have contact rails, from which the other CPX-P components on the interlinking modules are supplied with current. Internal division of the power supply makes it possible to switch off specific areas of the sensors and actuators individually.
Applications 24 V DC supply voltage for outputs
General technical data Nominal operating voltage Protection class to EN 60529 Ambient temperature Note on materials Grid dimension Dimensions W x L x H Electrical connection Current supply Materials Product weight
[V DC] [°C] [mm] [mm] Outputs
[A] [g]
Pin allocation – Metal interlinking blocks Circuitry
24 Depending on connection block –5 … +50 RoHS-compliant 50 50 x 107 x 35 7/8", 5-pin Max. 8 Die-cast aluminium 187
Pin
Allocation
1
0 V outputs
2 n.c.
3
FE
4 n.c.
5
24 V DC load voltage supply for outputs
Round plug, 5-pin 7/8"
90
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04