Series One/Series Three Data Communications User's Manual: Chapter 6 Serial Interface Protocol, pages 114 to 121

Pages 114 to 121 of 134, from Series One/Series Three Data Communications User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the GE Fanuc IC630MDL357A, Fanuc IC630MDL357A and GE IC630MDL357A

Page 114

GEK-90477

Serial

Interface

Protocol

6-9

PC%-844060

SEND

EOT

I

I

SEND ACK

READ

EOT

I

SEND LOT TO END SESSION

1

9EE CONDITION 5, TABLE 6.2 +QGNCE 2SEE CONDITION 7, TABLE 6.2 2SEE CONDITION 8; TABLE 6.2 4 Figure

6.7

READ DATA

I

/

BLOCKS,

MASTER

OR SLAVE

Page 115

GEK-90477

Write

Serial

Interface

Data Blocks,

Master

6-10

Protocol or Slave (See Figure

6.6)

Write data block. e Is there a time-out on the data block response? (Condition 6, Table 6.2) If YES, is data block response ACK or NAK? If NO, is data block response ACK or NAK? If not ACK or NAK, send EOT to other device and exit. If ACK or NAK, is it a NAK? If YES, has data block been retried 3 times? If NO, return to “Write Data Block”. *If NO, is it last data block? If NO, set up next data block and return to “Write Data Block”. If YES, send EOT to end session. Is this device a Master? If YES, exit N Sequence. If NO, read EOT. Is there a time-out on EOT or is character not an EOT? (Condition 8, Table 6.2) If there is a time-out or the character is not EOT, send EOT and exit N Response. If EOT is OK, session is complete. Exit N response.

Read Data Blocks,

Master or Slave (See Figure

6.7)

Read data block. Is there a time-out on the first character of the data block? (Condition 5, Table 6.2) If YES, send an EOT and exit. If NO, is there a time-out on the entire data block? (Condition 7, Table 6.2) If YES, send an EOT and exit. If NO, is the data block OK? If NO, has the data block been retried 3 times? If YES, send EOT and exit. If NO, send NAK and return to “Read Data Block”. If YES, send ACK. “Is it the last data block? If NO, return to “Read Data Block”. If YES, read EOT. Is there a time-out on the EOT or is the character not an EOT? If there is a time-out or the character is not EOT, send EOT and exit. If EOT is OK, is this device a master? If NO, the session is complete, exit N Response. If YES, send EOT to end session, exit N Sequence. l

*

For Series One and Series One Junior communications, only one partial data block can be sent per request based on the time outs in Table 6.2. Therefore, it is always the last. The flow chart and accompanying explanation describe the full functionality of CCM2 protocol.

Page 116

GEK-90477

Serial

MASTER-SLAVE

Interface

6-l 1

Protocol

MESSAGE TRANSFERS

As explained before, when the master wishes to initiate a data transfer, it issues a The receiving device responds by sending a three-character enquiry sequence. three-character acknowledge or negative acknowledge sequence. This establishes a link which permits the transfer of a message. Message transfers consist of a 17-byte header, sent by the master, followed by a block of data.

HEADER

BLOCK

A header block header specifies is sent before the text data block to describe transfer of data. The the direction of the data transfer, the amount and location of the data to be transferred, and the destination of the transfer. The header is composed of 17 bytes; the header format is shown in Figure 6.8. _

. S 0 H

1

D0J ID

DATA FLOW DIR

2

3

4

DCU MEM TYPE

ADD

ECU MEM ADD

COMP DATA

MSB

LSB

BLKS

LAST BLK

09

10

12

DCU MEM

5

67 A

NO

11

NO BYTES

13

.

(OlH) DCU (target) ID Number (not encoded the same as the target address) BYTES 4 + 5 Data flow direction, DCU memory type BYTES 6 + 7 Most significant byte of address of requested data BYTES 8 + 9 Least significant byte of address of requested data BYTES 10 + 11 Number of complete data blocks to follow the header Series One and Series One Junior data communications, byte is always zero). BYTES 12 + 13 Number of bytes in incomplete last block. BYTES 14 + 15 Source ID Number BYTE 16 ETB (17H) BYTE 17 LRC (Exclusive “OR” of Bytes 2-15) BYTE BYTES

1 SOH 2 + 3

Figure The information in bytes 2-15 hexadecimal values are 30H-39H than one byte, the most signif icant

6.8

SERIAL

HEADER are ASCII coded (O-9) and 41 H-46H byte is transmitted

(In this

FORMAT hexadecimal. (A-F). For first.

Valid ASCII fields requiring coded more

Page 117

GEK-90477

Serial

Interface

Protocol

6-12

DCU or DCM ID Number The DCU or DCM ID (target ID) is the identification number of the DCU or DCM and it is set with DIP switches= This number can range from 1 to 90. (In ASCII coded HEX: 01 to 5A). This is not encoded the same as the Target-__Address in the enquiry sequence. See the section, Normal Enquiry Sequence, in this chapter.

Data Flow Direction and Memory

Bytes 4 and 5 inform type involved.

Type the DCU or DCM of the direction of the transfer and the memory

Byte 4 - Direction

1

CONTEKTS OF BYTE 4 DEC HEX ASCII 30 38

48 56

Byte 5 - Memory

DATA FLOW DIRECTION 4

0 8

Read from DCU or DCM Write to DCU or DCM

Type

CONTENTS OF BYTE 5 DEC HEX ASCII

*

49

31

1

50

32

3

54 55 57

36 37 39

6 7 9

TARGET ME?IORY TYPE

(Memory Type 1) Data Registers* and CPU Timer/Counter Memory (Memory Type 3) CPU Discrete I/O Status values (External and Internal Input/Output values, shift registers, and Timer/Counter complete* bits) (Memory Type 6) CPU Scratch Pad Memory (Memory Type 7) CPU User Logic Memory (Memory Type 9) DCU or DCM Diagnostic Status Words

Timer/Counter complete references Plus and Series Three CPUs only.

Target Memory and Data Registers in Series

One

One/Junior/Plus or can be accessed

Address

The target meiory address specifies the address Series Three CPU where the transfer is to begin.

within the Series

Page 118

GEK-90477

Serial Interface

Protocol

6-l 3

Memory Type 1 The target memory address specifies the Timer/Counter accumulator or Data Register (Series One Plus and Series Three PCs only) where the data transfer is to begin. The mapping of reference numbers to numbers used for the target memory address is shown in Tables 5.1 (Series One), 5.2 (Series One Junior), 5.3 (Series One Plus), and 5.4 (Series Three). Valid Range

Series One OOOlH-0040H

Series One Plus OOOlH-0080H

Series One Junior OOOlH-0015H

Series Three OOOlH-OOCOH

Memory Type 3 The target memory address specifies the Input or Output point where the data transfer is to begin. The transfer begins with the byte that contains the specified The mapping of discrete I/O reference numbers to numbers used for Input or Output. target memory address is shown in Tables 5.1 (Series One), 5.2 (Series One Junior). 5.3 (Series One Plus), and 5.4 (Series Three). Valid Range

Series One OOOlH-0030H

Series One Plus Series One Junior OOOlH-OOZOH OOOlH-0040H (excluding 0009H-OOOBH)

Memory Type 6 The target memory which the data transfer is to begin. Valid Range address specifies

Series One Series One Junior OOOOH or 0016H OOOOH or 0016H

Series Three OOblH-0080H the CPU Scratch-Pad

Series One Plus OOOOH, OOOZH, OOO4H, or 0016H reference at

Series Three OOOOH or 0016H l

The address can be either OOOOHto access CPU operation mode status or OO16t-i to access PC Type status. Operation mode and PC type each consist of 2 bytes. See the section, Accessing the CPU Scratch Pad.

Memory Type 7 The target memory address specifies the User-Logic memory word at which the data transfer is to begin. Timer and Counter instructions must be written in their entirety (2 words or 4 bytes). To clear User-Logic memory, write FF to each byte to cleared. Valid Range

Series One OOOOH-06BBH

Series One Junior OOOOH-02BBH

Memory Type 9 The target memory address which the data transfer is to begin. The only 5 words (10 bytes) must be read or written. Valid Range

Series One OOOOH

See the section,

Diagnostic

Series One Plus OOOOH-06BBH

Series Three OOOOH-OFFEH specifies the Diagnostic Status Word at valid target memory address is OOOOH. All

Series One Junior OOOOH

Series One Plus OOOOH

Series Three OOOOH

Status Words, in Chapter

5 for the definition of each word.

Page 119

GEK-90477

Serial

Interface

Number of Complete

Protocol

Data Blocks to Follow

6-14

Header

*

This specifies the number of 256-byte data blocks to be transferred following the header. This number can range from 0 to 20H for Series One Plus or Series Three communications, but must be 0 for Series One or Series One Junior communications using the serial time outs in Table 6.2. For more information, see the section on Text Data Blocks. The information below defines the unit length and accessible lengths for each Series This information will help you to One/Junior/Plus and Series Three memory type. determine how many 8-bit bytes are required for a particular transfer.

SERIES ONE/JUNIOR/PLUS SERIES THREE MEMORY TYPE

1:

1: 3. 61 7. l

9. 0

Number

Timer/Counter Accumulator Data Registers (Series One Plus and Three Only) Discrete Scratch Pad I/O Bytes User Logic Word Diagnostic Status Word of Bytes in IncomPlete

UNIT LENGTH

ACCESSIBLE LENGTHS

1 Accum = 16 bits 1 Data Reg = 8 bits 1 Point ==8 1bits bit Byte 1 Word = 16 bits 1 Word = 16 bits

Accumulator(s) Multiples of 2 Reg Multiples 2 of 8 Points Bytes Word(s) 5 Words

Last Block

This specifies the number of bytes in the last data block. data blocks is zero, this number specifies the total number

When the number of complete of bytes to be transferred.

For Series One Plus and Series Three communications, this number of bytes in the last block can vary from 0001 H to OOFFH. For Series One and Series One Junior communciations, this number is restricted because of the limitation of accessing memory through the DCU. For more information, see the section on Text Data Blocks.

Source ID Number The source ID number is the identification CPU, this ranges from 1 to 5AH.

number of the source device.

For a Series Six

Page 120

GEK-90477

Serial interface

6-l 5

Protocol

Text Data Block The maximum data block size is 256 (OOFFH) bytes for Series One Plus and Series Three CPUs but is less than this for Series One/Junior CPUs using the time outs in Table 6.2. This does not affect reading or writing to memory types 6 (Scratch Pad) or 9 (Diagnostic Status Words). Reading and writing to memory types 1 (T/C Accumulators), 3 (l/O and Shift Registers), and 7 (User Memory) are restricted as shown in the table below.

TYPE OF COMMUNICATION REQUEST

MAXIMUM AMOUNT OF DATA FOR EACH COMMUNICATION

SERIES ONE PC* 58 Act

Read from Memory Type 3 (I/O and Shift Reg) Write to Memory Type 3 (I/O and Shift Reg)

368

I/O

46 Bytes

24

I/O

3 Bytes

75 Words

150 Bytes

25 Words

50 Bytes

45 Words

90 Bytes

20 Words

ZIO Bytes

* CPU Revision

Communication Not Supported

All 21 Act

42 Bytes

Read from Memory Type 1 (T/C Accumulators) Write to Memory Type 1 (T/C Accumulators)

Read from Memory Type 7 (User Memory) Write to Memory Type 7 (User Memory)

116 Bytes

SERIES ONE JR PC

Communication Not Supported 176 I/O

22 Bytes

No I/O, Communication Times Out

C or later. NOTE

If you are writing a CCM protocol interface for the Series One or Series One Junior, the time outs for conditions 5, 6, and possibly 7 in Table 6.2 must be lengthened to transfer more data per request. The time outs in the Series Six CCM2 and CCM3, however, are fixed and cannot be made lonaer.

The text data block always starts with a Start-Of-Text (STX) character which is followed by the text. The text is followed by an End-Of-Text (ETX) character. This is then followed by the text data checksum. This checksum is used to verify the data’s integrity. The checksum, (LRC) is an exclusive r’OR’f of all the text data bytes. When 16-bit information (registers or user logic) is being transferred in a text data block, the least significant byte is transferred first followed by the most significant byte.

Page 121

GEK-90477

HEADER

Serial

Interface

Protocol

AND TEXT DATA

BLOCK

6-16

RESPONSE

The header and text data blocks are responded to with an acknowledge (ACK) acknowledge (NAK). An ACK means that the header or text was acceptable permission to the sending device to start sending the next data block. A NAK means that the header or text the header or data. The unacceptable or negative and grants was not acceptable and asks for a retransmission header or text is retried three times.

of

MESSAGE TERMINATION After the ACK to the final text data block has been received, the device receiving the ACK sends an End-Of-Transmission (EOT) character to close the serial link. The master always terminates the link with an EOT.

TIMING

CONSIDERATIONS

Serial Link Time-Outs A time-out occurs on a serial link when the DCU or DCM does not receive a response, a header, or data from another device within a fixed amount of time. Time-outs are used on the serial link for error detection, error recovery, and to prevent missing end-of-block sequences. Whenever a serial link time-out occurs, the DCU or DCM will abort the conversation and send an EOT to the other device. After an EOT, a new enquiry sequence must be sent to restore communications. Refer to Table 6.2 for time-outs at any point in the serial protocol.

Turn-Around

Delays

Turn-around delay options of 0 to 10 ms for the DCU or DCM can be selected by DIP switch. A lo-ms turn-around delay should be selected when using modems in the half-duplex mode of operation or when using full-duplex modems in multidrop configurations. This delay allows a computer or Series Six the time needed to signal the modem to turn on and ringing on the line to stop before actual transmission of data. The DCU or DCM will delay 10 ms before header, or the start of a text data block. When the 10 ms turn-around serial time-outs in Table 6.2.

delay is selected, sending the a control time character, is automatically the start of added to the