Manual · GE Fanuc
Series One/Series Three Data Communications User's Manual
Manual134 pagesPDF 14 MB
User's manual for the GE Fanuc Series One and Series Three PC serial links: the Data Communications Unit (DCU) and Module (DCM).
What this file really is
The old site listed this file as a manual for the Fanuc IC630MDL357A, GE IC630MDL357A and GE Fanuc IC630MDL357A. Filed as a user manual for the IC630MDL357A, but it is the Series One/Series Three Data Communications manual, which names the IC630MDL357A only in a Series Three power (units of load) table.
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
GE Fanuc manual GEK-90477A on serial communications between a Series Six PC or host computer and Series One, Series One Junior, Series One Plus or Series Three PCs. It covers installing and operating the Data Communications Unit (DCU) and Data Communications Module (DCM), their LEDs, switches and power, RS-422 and modem cable diagrams, diagnostics, Series Six SCREQ ladder examples, and the serial interface protocol for writing a host driver.
Its parts
- Chapter 1 Introduction
- Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs
- Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC
- Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM
- Chapter 5 Communication Examples using the Series Six PC as a Master Device
- Chapter 6 Serial Interface Protocol
From the manual
Key facts from this manual
Each line names its page in the PDF.
GE Fanuc Series One/Series Three Data Communications User's Manual GEK-90477A (December 1986). It covers the Data Communications Unit (DCU) for the Series One, Series One Junior and Series One Plus PCs and the Data Communications Module (DCM, IC630CCM300) for the Series Three PC, which link these PCs to a Series Six PC, Workmaster or host computer over RS-422. IC630MDL357A, the model it is filed under, appears only in a Series Three power-load table.
- What it covers
- Serial RS-422 interface (DCU or DCM) between a Series One, One Junior, One Plus or Series Three PC and a Series Six PC, Workmaster or host computer p. 14
- Series Three DCM
- Data Communications Module IC630CCM300 p. 30
- Protocol
- CCM2 master-slave; the Series One or Three PC is always the slave p. 14
- Data rate
- 19.2 kBps for direct connections; other DIP-switch selectable rates for modems p. 14
- Distance and drops
- RS-422 up to 4000 feet (1200 meters); up to 8 slaves multidropped p. 15, 16
- Communications port
- 25-pin female D-type; a mating 25-pin male connector is supplied p. 42, 43
- DCM power
- From the Series Three CPU or an external 5 V dc supply at 0.5 A, chosen by a power select switch p. 32, 37
- DCM to CPU cable
- IC630CBL395A, supplied with each DCM p. 32, 39
- RS-422 cable types
- 9184, 9302 and 222PISLCBT (Belden and NEC), for 4000 feet at 19.2 kbps p. 43
- Status LEDs
- DATA (data transfer), DIAG (power-up diagnostics passed), PWR (5 V dc connected) p. 31
- Accessible memory
- Discrete I/O, timer and counter accumulators, data registers, scratchpad, user logic and diagnostic information p. 14
- Diagnostics
- Power-up RAM, PROM checksum and USART tests; loop-back test with DIP switch 5 ON p. 53
- Diagnostic Status Words
- 5 words per port, read as memory type 9 starting at word 1 p. 71
What this manual walks you through
- Choosing a point-to-point or multidrop configuration, direct or by modem p. 15, 16
- Reading the DCM status LEDs p. 31
- Powering the DCM from the CPU or an external supply p. 32, 37
- Checking the rack power budget in units of load p. 37, 38
- Installing the DCM and connecting it to the Series Three CPU p. 39
- Communications port pin assignments p. 42
- Wiring the DCU or DCM directly to a Workmaster p. 53
- Running power-up and loop-back diagnostics p. 53, 54
- Reading the Diagnostic Status Words and error codes p. 71, 72
Good to know
- Ground the DCU or DCM and the connected device to a common point, or the equipment may be damaged. p. 44
- With Series Three power supply IC630PWR300A the DCM needs an external 5 V dc supply. p. 37
- Connect the DCM to the CPU with the Series Three power off. p. 39
- Loop-back diagnostics run only with the unit off line and connected to the CPU. p. 53
Questions this manual answers
How far can a Series Three DCM communicate over RS-422?
Up to 4000 feet (1200 meters) direct; longer distances need modems and an RS-232 to RS-422 adapter unit. p. 15
How many Series One or Series Three PCs can be multidropped?
Up to 8 slaves on RS-422, with at most 4000 feet (1200 meters) between the end devices. p. 16
What power does the Series Three DCM need?
5 V dc at 0.5 A, from the Series Three CPU or from an external supply through the front connector. p. 32
Contents
Chapters and sections
Each line opens the PDF at its page.
- Chapter 1 Introduction14
- Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs18
- Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC30
- Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM42
- Chapter 5 Communication Examples using the Series Six PC as a Master Device56
- Chapter 6 Serial Interface Protocol106
- Index128
The whole text · 14 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 131-13
- Chapter 1 Introduction14-17
- Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs18-29
- Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC30-41
- Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM42-55
- Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 56 to 6556-65
- Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 66 to 7566-75
- Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 76 to 8576-85
- Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 86 to 9586-95
- Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 96 to 10596-105
- Chapter 6 Serial Interface Protocol, pages 106 to 113106-113
- Chapter 6 Serial Interface Protocol, pages 114 to 121114-121
- Chapter 6 Serial Interface Protocol, pages 122 to 127122-127
- Index128-134
The file