Page 1 of Series One/Series Three Data Communications User's Manual

Manual · GE Fanuc

Series One/Series Three Data Communications User's Manual

Manual134 pagesPDF 14 MB

User's manual for the GE Fanuc Series One and Series Three PC serial links: the Data Communications Unit (DCU) and Module (DCM).

What this file really is

The old site listed this file as a manual for the Fanuc IC630MDL357A, GE IC630MDL357A and GE Fanuc IC630MDL357A. Filed as a user manual for the IC630MDL357A, but it is the Series One/Series Three Data Communications manual, which names the IC630MDL357A only in a Series Three power (units of load) table.

Download the PDF14 MB

Filed with · 3 models

Also filed with these models on the old site

Summary

What is in it

GE Fanuc manual GEK-90477A on serial communications between a Series Six PC or host computer and Series One, Series One Junior, Series One Plus or Series Three PCs. It covers installing and operating the Data Communications Unit (DCU) and Data Communications Module (DCM), their LEDs, switches and power, RS-422 and modem cable diagrams, diagnostics, Series Six SCREQ ladder examples, and the serial interface protocol for writing a host driver.

Its parts

  1. Chapter 1 Introduction
  2. Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs
  3. Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC
  4. Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM
  5. Chapter 5 Communication Examples using the Series Six PC as a Master Device
  6. Chapter 6 Serial Interface Protocol

From the manual

Key facts from this manual

Each line names its page in the PDF.

GE Fanuc Series One/Series Three Data Communications User's Manual GEK-90477A (December 1986). It covers the Data Communications Unit (DCU) for the Series One, Series One Junior and Series One Plus PCs and the Data Communications Module (DCM, IC630CCM300) for the Series Three PC, which link these PCs to a Series Six PC, Workmaster or host computer over RS-422. IC630MDL357A, the model it is filed under, appears only in a Series Three power-load table.

Read for this summary: pages 1 to 4, 14 to 16, 30 to 32, 37 to 39, 42 to 44, 53 to 54 and 71 to 72 of 134.

What it covers
Serial RS-422 interface (DCU or DCM) between a Series One, One Junior, One Plus or Series Three PC and a Series Six PC, Workmaster or host computer p. 14
Series Three DCM
Data Communications Module IC630CCM300 p. 30
Protocol
CCM2 master-slave; the Series One or Three PC is always the slave p. 14
Data rate
19.2 kBps for direct connections; other DIP-switch selectable rates for modems p. 14
Distance and drops
RS-422 up to 4000 feet (1200 meters); up to 8 slaves multidropped p. 15, 16
Communications port
25-pin female D-type; a mating 25-pin male connector is supplied p. 42, 43
DCM power
From the Series Three CPU or an external 5 V dc supply at 0.5 A, chosen by a power select switch p. 32, 37
DCM to CPU cable
IC630CBL395A, supplied with each DCM p. 32, 39
RS-422 cable types
9184, 9302 and 222PISLCBT (Belden and NEC), for 4000 feet at 19.2 kbps p. 43
Status LEDs
DATA (data transfer), DIAG (power-up diagnostics passed), PWR (5 V dc connected) p. 31
Accessible memory
Discrete I/O, timer and counter accumulators, data registers, scratchpad, user logic and diagnostic information p. 14
Diagnostics
Power-up RAM, PROM checksum and USART tests; loop-back test with DIP switch 5 ON p. 53
Diagnostic Status Words
5 words per port, read as memory type 9 starting at word 1 p. 71

What this manual walks you through

  • Choosing a point-to-point or multidrop configuration, direct or by modem p. 15, 16
  • Reading the DCM status LEDs p. 31
  • Powering the DCM from the CPU or an external supply p. 32, 37
  • Checking the rack power budget in units of load p. 37, 38
  • Installing the DCM and connecting it to the Series Three CPU p. 39
  • Communications port pin assignments p. 42
  • Wiring the DCU or DCM directly to a Workmaster p. 53
  • Running power-up and loop-back diagnostics p. 53, 54
  • Reading the Diagnostic Status Words and error codes p. 71, 72

Good to know

  • Ground the DCU or DCM and the connected device to a common point, or the equipment may be damaged. p. 44
  • With Series Three power supply IC630PWR300A the DCM needs an external 5 V dc supply. p. 37
  • Connect the DCM to the CPU with the Series Three power off. p. 39
  • Loop-back diagnostics run only with the unit off line and connected to the CPU. p. 53

Questions this manual answers

How far can a Series Three DCM communicate over RS-422?

Up to 4000 feet (1200 meters) direct; longer distances need modems and an RS-232 to RS-422 adapter unit. p. 15

How many Series One or Series Three PCs can be multidropped?

Up to 8 slaves on RS-422, with at most 4000 feet (1200 meters) between the end devices. p. 16

What power does the Series Three DCM need?

5 V dc at 0.5 A, from the Series Three CPU or from an external supply through the front connector. p. 32

How do I run the loop-back test on a DCU or DCM?

Put the unit off line, keep it connected to the CPU, set configuration DIP switch 5 ON and fit the loop-back test connector. p. 53, 54

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Chapter 1 Introduction14
    1. Communications Capabilities Using The DCU or DCM14
    2. System Configurations Using The DCU or DCM14
  2. Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs18
    1. Description and Operation of the User Interfaces for the DCU18
    2. Installing the DCU26
    3. Power Cycle Conditions Affecting System Operation27
  3. Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC30
    1. Description and Operation of the DCM's User Interfaces30
    2. Installing the DCM39
    3. Power Cycle Conditions Affecting System Operation40
  4. Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM42
    1. Port Characteristics42
    2. Communications Port Mating Connector43
    3. Cable Selection43
    4. Catalog Numbers for GE Supplied Cables44
    5. Grounding44
    6. RS-422 Direct Cable Diagrams44
    7. Modem Configuration Cable Diagrams49
    8. DCU or DCM to Workmaster Computer Cable Diagrams52
    9. Test Diagnostics53
  5. Chapter 5 Communication Examples using the Series Six PC as a Master Device56
    1. Introduction56
    2. SCREQ Registers57
    3. Using the Password and Error Checking Features of the Series One Plus PC69
    4. Diagnostic Status Words71
    5. Diagnostic Status Word 1 Error Codes71
    6. SCREQ Command Examples75
  6. Chapter 6 Serial Interface Protocol106
    1. Introduction, Master-Slave Protocol106
    2. Master-Slave Message Transfers116
    3. Accessing the CPU Scratch Pad124
  7. Index128

From the PDF’s own bookmarks.

The whole text · 14 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 131-13
  2. Chapter 1 Introduction14-17
  3. Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs18-29
  4. Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC30-41
  5. Chapter 4 Electrical Interface Circuits and Diagnostics for the DCU and DCM42-55
  6. Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 56 to 6556-65
  7. Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 66 to 7566-75
  8. Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 76 to 8576-85
  9. Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 86 to 9586-95
  10. Chapter 5 Communication Examples using the Series Six PC as a Master Device, pages 96 to 10596-105
  11. Chapter 6 Serial Interface Protocol, pages 106 to 113106-113
  12. Chapter 6 Serial Interface Protocol, pages 114 to 121114-121
  13. Chapter 6 Serial Interface Protocol, pages 122 to 127122-127
  14. Index128-134

The file

Revision and size

Part no.GEK-90477A
RevisionDecember 1986
PublisherGE Fanuc Automation
Pages134