Series One/Series Three Data Communications User's Manual: Chapter 1 Introduction

Pages 14 to 17 of 134, from Series One/Series Three Data Communications User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the GE Fanuc IC630MDL357A, Fanuc IC630MDL357A and GE IC630MDL357A

Page 14

GEK-90477

1-1

Introduction

\

CHAPTER 1 INTRODUCTION

The serial interface to the Series Onefn family of PCs is essentially the same as the interface to the Series ThreeTn PC. For this reason the user information for both have been combined into one manual. The differences are primarily related to the physical package which affects the installation of the interface. To differentiate between the two interfaces, the terms below are used throughout this manual. Data Communications

Unit (DCU)

-

Data Communications

Module (DCM) -

This chapter describes the capabilities communications with the Series One Family Three programmable cant rol lers.

COMMUNICATIONS

CAPABILITIES

Series One, Series One Junior, and Series One Plus PC Interface Series Three PC Interface and system configurations of programmable controllers for serial and Series

USING THE DCU OR DCM

The DCU and DCM provide a serial, RS-422 interface between a Series One, Series One Junior, Series One Plus, or Series Three PC and a device such as a Series Six’” PC, Workmasterfn computer or other host computer. Memory types that can be accessed through the DCU or DCM include: 0

0 l

0 0

Discrete input and output points, Timer and counter accumulator references Three PC data registers), Scratchpad (including using the password capability for the Series One Plus PC), User logic, and Diagnostic information.

(and Series One Plus PC and Series and the user logic error checking

Using the CCM2 protocol, the host computer or Series Six PC can have supervisory control over one or more PCs of the Series One family or one or more Series Three PCs. The data transfer rates as well as other communications parameters for the DCU and DCM are DIP-switch selectable. The primary data transfer rate for direct connections is 19.2 kBps. Other data transfer rates are provided for special purpose interfaces which include modem configurations.

SYSTEM CONFIGURATIONS

USING THE DCU OR DCM

A system configuration refers to the way in which various devices are combined to form a communications net work. both point-to-point and mul t idrop As explained below, configurations are possible through the DCU or DCM. For details on constructing cables, see Chapter 4, Electrical Interface Circuits. In all configurations, the Series One, Series One Junior, Series One Plus, or Series Three PC is the Slav; device, and the host computer, Workmaster, or Series Six PC is the master device. A slave can respond only to requests from a master.

Tn Trademark of General .

Electric

Company.

Page 15

GEK-90477

Introduction l-2

When a Workmaster computer or other host computer must be written to handle the protocol requirements interface Protocol.

POINT-TO-POINT is the master device, host software as explained in Chapter 6, Serial

CONFIGURATIONS

In the point-to-point configuration, only two elements can be connected to the same communication line. The communication line can be connected directly using the M-422 electrical interface capability (4000 feet, 1200 meters, maximum), or connected through modems and an M-232 to M-422 adapter unit for longer distances over telephone lines. TPK.A.40369

MASTER

Figure 1 .l

SLAVE

POINT-TO-POINT

CONFIGURATION

(DIRECT) TPK.A.40370

.

UASTER

?

l

SERIES SIX PC OR HOSTCOUPUTER

Jb* I RS-232 q' MODEM ' . 4

SLAVE l

RS-232 RS-422 SERIESONE$UNIOR/PLUS RS-232 1 UOOEM 1 1 ADAPTER L c . UNIT SERIESTHREEPC 4 l l

Figure 1.2

POINT-TO-POINT

CONFIGURATION

(USING MODEMS)

4

Page 16

1-3

GEK-90477 introduction

MULTIDROP

CONFIGURATIONS

This configuration permits the connection of a host computer or Series Six! PC to a group of Series One, Series One Junior, Series One Plus, or Series Three PCs. As with point-to-point connections, either M-422 capability or modems can be used. A maximum of 8 slaves can be connected using RS-422. The maximum distance between the two end devices in the multidrop is 4000 feet (1200 meters). When RS-232 modems are used, an M-232 adapter unit must be included M-422 signals from the DCU or DCM to RS-232 signals for the modems.

to convert

TPK.A.40371

4

MASTER SERIES SIX PC OR HOST COMPUTER b

L

SLAVE

\

9 RS-422 l

SLAVE

7 ,

Figure

1.3 MULTIDROP

?

SERIES ONE/JUNIOR/PLUS . OR SERIESTHREEPC . .

I

1

SERIES ONE/JUNIOR/PLUS OR SERIES THREE PC

CONFIGURATION

(DIRECT) TiK.A.40372 c

MASTER

*

SERIES SIX PC OR HOST COMPUTER l

*rL RS-232 ' RS-232 k L RS-232 1 MODEM I 'r 1 YODEM 1 ADAPTER , 6 UNIT l

4 rL * 1 UODEM

*Up to 8 slave devices

Figure can be multidropped

1.4

MULTIDROP

SLAVE

I

.

r .

RS-232

RS-232

.

RS-422 SERIES ONE~$NIOR/'PLUS

1 mit:TER 1 from the RS-232 Adapter

CONFIGURATION

SLAVE

.

, l

.

RS-422 SERIESONE&UNIOR/PLUS 1 SERIESTHREEPC .

1

SERIES THREEPC

Unit.

(USING MODEMS)

1

Page 17