The text of a manual · part 3 of 14
Series One/Series Three Data Communications User's Manual: Chapter 2 Installation and Operation of the Data Communications Unit for the Series One Family of PCs
Pages 18 to 29 of 134, from Series One/Series Three Data Communications User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the GE Fanuc IC630MDL357A, Fanuc IC630MDL357A and GE IC630MDL357A
Page 18
GEK-90477
Installation and Operation of the DCU
2-1
CHAPTER 2 AND OPERATION OF THE DATA COMMUNICATIONS FOR THE SERIES ONE FAMILY OF PCS
INSTALLATION
This chapter describes and the installation lc6loccM105A).
UNIT the operation of the user interfaces (LEDs, switches, and ports) of the Data Communications Unit (DCU) (IC6lOCCMlOOA,
NOTE TO SERIES ONE PLUS USERS Use only the communications
DESCRIPTION
Data with
AND OPERATION
The various indicator shown in Figure 2.1.
lights,
Communications Unit the Series One Plus PC.
(lC6lOCCM105A)
OF THE USER INTERFACES connectors, and configuration for
FOR THE DCU
DIP switches for the DCU are
TPA.C.40221
PROCGAUUEP
COhfQEC’JA \
FRCNT
VIEW
Figure
2.1
FRONT,
END, AND REAR VIEW OF THE DCU
Page 19
GEK-90477
Installation and Operation of the DCU
2-2
\
LED INDICATORS The six status
LED’s on the front of the DCU convey the following inform$tion:
Status LED
State
Description
DATA
On
Data being transferred to and from the communication port.
Off
Data not being transferred to and from the communication port or data incorrect due to: 1. Parity overrun or framing errors; 2. Invalid header, data block, control character, or checksum; 3. Time out on serial link. (Refer to Chapter 6 for more information on the protocol used).
DIAG
PWR
On
Power-up hardware diagnostics have passed.
Off
Power-up hardware diagnostics have failed.
On
5 V dc power to DCU is connected.
Off
5 V dc power to DCU is not connected.
NOTE Power to the DCU can be supplied from the rack power supply or an external supply. When the power supply select switch is in the EXT position, power must be supplied through the external power supply connector on the side of the DCU. See Figures 2.1 and 2.2.
Page 20
GEK-90477 installation and Operation of the DCU
2-3
Status LED
State
Description
RUN
On
The CPU is in the RUN mode.
Off
The CPU is not in the RUN mode.
On
The battery which provides memory back-up in the CPU is not OK.
Off
The battery which provides memory back-up in the CPU is OK.
On
There is an error; check the error code on the programmmer display and take the appropriate action. There is no CPU error.
BATT
CPU
Off
*
L
FRONT
PANEL
CONNECTORS
Two connectors on the front of the DCU provide an interface 1. 2.
Programmer (Programmer Connector), External serial device (Communications
Programmer to:
Connector).
Connector
The programmer connector is the mating connector which mates with the programmer and connects with the CPU. This permits use of the programmer while the DCU is connected to the CPU. See Figures 2.1 and 2.4.
Communications
Connector
The communications connector (2%pin female, D-type) provides a serial interface external devices. A pin-by-pin description of this connector is shown in Chapter 4.
to
Page 21
GEK-90477
Installation
DCU CONFIGURATION The configuration and Operation
2-4 of the DCU
SWITCHES switches are located on the right side of the DCU as shown below. TPK.A.40373
-
ON/OFF LINE SWITCH
COMMUNICATION PORT ore SWITCHES
-
-
UNIT ADDRESS DIP SWITCHES
EXTERNAL POWER SUPPLY CONNECTOR
END VIEW
Figure
ON/OFF-LINE
2.2
LOCAT
ON OF THE DCU CONF IGURATION
SWITCHES
Switch
The ON/OFF-LINE switch, wh ch is directly above the DIP switches on the right side of the DCU, enables or disables serial communications with the Series One, Series One Junior, or Series One Plus CPU. OFF LINE:
Serial communication CPU is under control between the DCU and the CPU of the attached programmmer.
ON LINE:
Serial communication between the programmer is disabled if attached.
DCU and
CPU is disabled and the is enabled and the
Page 22
GEK-90477
Installation and Operation
2-5 of the DCU
CPU (Unit) ID DIP Switches The bottom group of eight DIP switches located on the right side of the DCU determines the CPU ID of l-90. The switch configuration associated with each ID is shown in Figure 23. . TPA.A.40223 EXAMPLE OF UNIT lo SwlTcH SElllWM.
EkAMPLE SWITCH IS SET FOR UNIT -ESS 9.
00 b
4
I
,
UYlT ID
,
1
,
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
, , , ) / .)
, , / ,
,
L ,
, , ,
,, , )
I!
x
: 1 1
X x X X x x X X X X
_
Figure 2.3 x
1 xe X xx x. x .x. x XI x XIX 1
DIP SYlTCH POSITIOu 8 7.615'4 3~2 1 1X X X X X X~~ I .x Ix OX lx Xl ,X X x! Ix . _Xi IX .X Xl X Xi X , XtlXX
~.
XXIX
~
41 42 43 44 45 46 47 48 49 SO 51 52 53 54 55
61 62 63 64 65
DIP WITCH POSITION J7.6 514.3!2;1, 1 X X!X Xi IX + 1 [X!XiXiXiXl 1 X X X(XiXfX 1 X 1 ! 1 .X,
67 60 69
! 1
WIT ID x lx1 I
1 40
Ix x xl Ix x I x x x xxx xxlxx
.I
X
0
DIP SUXTCH WIT POSTTIOY ID 817 6.51413 .2 1 1 Xl31 I Ix 32 33 _~ xx I ! OX. . 34 .I x 35 36 37 ..i.~~:XX ! _ x X X 1 38 .X x X 39
1 1 I ix xl 1 ,x Xl .X1 Xi x _I X xl 71 IX 1x.x1 I X x xi ,x xl x XIX1
,
71 72 73 74 75 76
1 XA 79 xx xx tX X
1x1 ! ~ IXIXJ
X x XX XX
Xl X11 83 XX 184 XXX] 85
80 81
X
X
1 T11
.
X
IX
I,
T
IX x. x lXlX!Xj I I ( x, I Ix, L X ' .xl 1 I x lx! xl x lxix XI x XI ! Ixl x xl ix xl I X~XIXL XT x xlxlx 'XT x ' I XLX 1 x x11 .x 1 Lx Xl x (XX/ x1.x x . 1x1 x x ix I f
= Switch in the ON position
DIP-SWITCH
SETTINGS FOR CPU 16 SELECTION
Page 23
GEK-90477 installation
Communication and Operation
Port Configuration
2-6 of the DCU
DIP Switches
The top group of eight DIP switches on the right side of the DCU determines the set-up parameters for the communication port (refer to Figure 2.2 for location of the switches). The settings for the communication set-up parameters are shown in Table 2.1. To execute the Loop Back Test, the ON/OFF-LINE SWITCH must be in the OFF-LINE mode. Switches 7 and 8 are not used. Table 2.1
COMMUNICATIONS
PORT CONFIGURATION
DATA RATE SELECTION (BPS) *300 1200 9600
19.2 k
DIP-SWITCH
DIP-SWITCH NUMBER 1 2 OFF OFF ON OFF OFF ON ON ON
DIP-SWITCH NUMBER
PARITY SELECTION
3
Parity ENABLED (Odd parity generated and checked). *Parity DISABLED (No parity is generated or checked).
ON OFF
LOOP-BACK TEST (Special Connector Required) Enabled *Disabled
DIP-SWITCH NUMBER 4 ON OFF
TURN-AROUND DELAY
DIP-SWITCH NUMBER 5 OFF ON
* 0 ms delay 10 ms delay
DIP-SWITCH NUMBER 6 ON OFF
POWER-UP MODE** Program/Stop Mode *Run Mode
*Factory set default posit ion. **See section, Power Cycle Conditions
Affecting
System Operation.
SETTINGS
Page 24
GEK-90477
Installation and Operation
EXTERNAL
POWER SUPPLY
2-7 of the DCU
CONNECTOR
The external power supply connector (see Figure 2.2) allows the operating power (5 V dc at 0.5 A) from an external power supply. cable is provided with the DCU for external power supply connection. follows: White: +5 V dc (+S%) at 0.5 amps Black: Logic ground of power supply Green: Power system ground
DCU” to receive its A three conductor Its color code is as
POWER SUPPLY SELECT SWITCH There is a power supply select switch on the back of the module to select internal (CPU) or external power for the DCU. An adjacent label indicates correct switch orientation for each selection.
USING THE DCU WITH CPU RACK
POWER
It is recommended that a Series One high-capacity power supply, IC610CHSllOA, 114A, 120A, or l24A be used when installing a DCU in a system. If a high-capacity power supply is not used, then the DCU should be powered by an external +5 V dc power supply. If a standard (low capacity) Series One power supply is used with the DCU, inconsistent CPU or communications operation will result. NOTE l
Even if a high-capacity power supply is being used in the CPU rack, inconsistent CPU or communications operation may be observed depending on the number and unit load of I/O modules installed in the rack. Refer to Tables 2.2 and 2.3 for units of load supplied by the different racks and used by I/O modules and other system devices.
Table 2.2 SERIES ONE UNITS*
CATALOG NUMBER
DESCRIPTION +5 V
IC610CHSlOOA ICdlOCHSllOA IC6lOCHS114A IC610CHSl20A ICdlOCHSl24A IC6lOCHS130A ICdlOCHS134A * x **
S-slot std cap S-slot hi cap S-slot hi cap 24 V dc 100slot hi cap 100slot hi cap 24 V dc 100slot hi cap 100slot hi cap 24 V dc
OF LOAD (SUPPLIED)
POWER SUPPLIED IN UNITS OF LOAD +24 V EXT +24 V +9 V
40 140 140 140 140 140 140
80 80 80 160 160 170 170
20 40** 40 40** 40 so** 50
10 10 10 -
1 unit = 10 mA If an external sensor is connected to the 24 V + and - terminals on the power supply, the current used by the sensor (up to a maximum of 100 mA), should be deducted from the available listed units of load.
Page 25
GEK-90477
Installation and Operation
Table 2.3 SERIES ONE UNITS*
CATALOG NUMBER
IC6lOCPUlOlC IC6lOCPUlOSA IC610PRGlOOB IC6lOPRGlOSA 1C610MDL101A IC6lOMDLlOZA IC610MDLlO3A IC610MDLlObA 1C610MDL105A IC6lOMDL106A IC61OMDL107A IC6lOMDLllOA IC61OMDLlllA IC610MDLllZA IC610MDLllSA IC61OMDL124A IC61OMDL125A IC610MDLL26A IC610MDL127A IC610MDL15lA IC610MDLLSZA IC610MDLl53A IC610MDLlStA IC6lOMDLlSSA IC6lOMDL156A IC6lOMDL157A IC610MDL158A IC610MDL175A IC610MDL176A IC610MDL180A IC610MDL182A IC610CCMlOOA IC610CCMlOSA ICdlOCCMllOA IC6lOCCMlllA IC6lOPER151A IC610PER154A
*l unit = 10 mA.
2-8 of the DCU
DESCRIPTION (CIRCUITS)
OF LOAD (USED)
POWER USED IN UNITS OF LOAD +24 V +9 V +5 V
25 CPU 25 CPU Programmer 6 6 Programmer Inp 24 V dc sink (8) Inp 24 V dc src (16) I/O 24 V dc (4/4) I/Relay Out 24 V dc (4/4) Thumbwheel Interf (4x16) Inp 24 V dc sink w LEDs (16) Inp 24 V dc sink load (16) Hi Speed Counter (1) Inp 24 V ac/dc (8) Inp 24 V ac/dc sauce (16) I/O Fast Response (4/Z) I/O Simulator (8) Inp 115 V ac (8) Inp 115 V ac isolated (4) Inp 230 V ac (8) Out 24 V dc sink (8) Out 24 V dc sink (16) Out 24 V dc sink (4) Out 24 V dc sink/src (4) Out 24 V dc src (8) Out 24 V dc sink w LEDs (16) Out 24 V dc sink w LEDs (16) Out 24 V dc src w LEDs (16) Out 115/230 V ac (8) Out 115/230 V ac isol (4) Out Relay (8) Out Relay (16) Data Comms Unit 30 Data Comms Unit 30 I/O Link Local Module 60 I/O Link Remote Module 60 Printer I/F 26 'Low Cost PROM Writer 80
Calculations are based on the worst case--all
5 5 1 2 2 20 1 3 3 7 1 13 8 1 1 1 1 2 5 1 1 3 4 4 20 16 8 34 48 -
10 19 7 6 10 24 23
6 11
3 4 1 10 l
10 10
-
- inputs and outputs on.
Page 26
GEK-90477
Installation and Operation of the DCU
2-9 .
INSTALLING To install
THE DCU the DCU:
1. Set the internal/external power switch to the desired position. 2. Position the CPU (unit) ID and port configuration DIP switches to the desired position (see Figure 2.3 and Table 2.1). 3. With the Series One, Series One Junior, or Series One Plus CPU power off, connect the DCU to the CPU and the programmer to the DCU (if desired) as shown in Figure 2.4. If, before powering up, the ON-LINE/OFF-LINE switch is placed in the ON-LINE position, after power up the PWR, RUN, and DIAG indicators should light in that order. For more information on power--up conditions affecting the CPU and communications status see Table 2.4. NOTE The Series One CPU version must be Revision
B or later.
TPK.A.40374
L’
BOTTOM SIDE OF SERIES ONE PROGRAMMER
COMMUNICATIONS
CONNECTS TO SERIIES ONE/JUNIOR/PLUS CPU
Figure
2.4
CONNECTING
THE PROGRAMMER,
DCU, AND CPU
Page 27
GEK-90477 installation
POWER CYCLE and Operation
CONDITIONS of the DCU
AFFECTING
2-10
SYSTEM OPERATION
When power is cycled, the resulting CPU and communications status d6pends upon the position of the DCU ON-LINE/OFF-LINE switch and power-up mode switch, whether the programmer is attached or detached, the programmer mode switch position, and the condition of the CPU battery. See Table 2.4.
Table 2.4
POWER CYCLE CONDITIONS AFFECTING SYSTEM OPERATION (The user program is assumed to be in CMOS RAM).
DCU
PROGRAMMER
RESULTING CPU AND COMMUNICATIONS STATUS ON POWER CYCLE
ON-LINE/ OFF-LINE SWITCH
POWER-UP MODE DIP SWITCH 6
ATTACHED/ DETACHED
MODE KEYSWITCH POSITION
On-Line
Off(Run)
Attached
Run
CPU in Run mode with communications active.
On-Line
On(Prog)
Attached
Run
CPU in Program mode with communications active only for the following serial requests: Read or command Run/Program and Read Diagnostic Status Words. The DCU will return in the status code a hexadecimal 10 to indicate that a power cycle has occurred.
Off-Line
On or Off
Not Attached
Off-Line
On or Off
Attached
*
CPU is in the same mode in which it powered down, communication is inactive since the unit is off line. (Communications will be active on off line to on line transition).* -
CPU is in whatever mode the keyswitch is set for with communications not active.
For Series One CPUs versions A or 6, the resulting same, but the resulting CPU status is that the CPU communications inactive.
communications is in Program status is the mode with the
Page 28
GEK-90477
Installation and Operation of the DCU
2-11
NOTE The following statuses condition in the CPU.
Table 2.4
POWER CYCLE
DCU result
CONDITIONS only when there
AFFECTING
PROGRAMMER is a low battery
SYSTEM OPERATION
(continued)
RESULTING CPU AND COMMUNICATIONS STATUS ON POWER CYCLE
ON-LINE/ OFF-LINE SWITCH
POWER UP MODE DIP SWITCH 6
ATTACHED/ DETACHED
MODE KEYSWITCH POSITION
Off Line
On or Off
Not Attached
CPU in Program mode with communications inactive since unit is off line.
On Line
On(Prog)
Not Attached
CPU in Program mode with communications active. DIAG LED will be ON and and RUN LED will be OFF.
On Line
Off (Run)
Not Attached
CPU in Program mode with communications inactive. DIAG and RUN will be OFF. Unit must be manually set to Program/Stop mode and the E-21 error cleared (if it has occurred) before commmunications can resume.