The text of a manual · part 4 of 14
Series One/Series Three Data Communications User's Manual: Chapter 3 Installation and Operation of the Data Communications Module for the Series Three PC
Pages 30 to 41 of 134, from Series One/Series Three Data Communications User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the GE Fanuc IC630MDL357A, Fanuc IC630MDL357A and GE IC630MDL357A
Page 30
GEK-90477
Installation
INSTALLATION and Operation of the DCM
3-1
This chapter describes the operation of the DCM’s user interfaces (LEDs, switches, ports) and the installation of the Data Communications Module (DCMI (IC630CCM300).
DESCRIPTION
AND OPERATION
The various indicator shown in Figure 3.1.
lights, connectors, and configuration
DIP switches mn 0 MO -0 a
:n (n
CPU
I
0 l
‘. :* . l. :* . l. :* .
3 .:* :* .3 :* . :a. :*
0 l
4
\
.couu ,
0+ l l
0 4 c
, q -a-
Figure
3.1 and
OF THE DCM’S USER INTERFACES for the DCM are
TPK.A.40007
*
*
CHAPTER 3 AND OPERATION OF THE DATA COMMUNICATIONS MODULE c1 FOR THE SERIES THREE PC
FRONT
AND REAR VIEW OF THE DCM
Page 31
GEK-90477
Installation and Operation
3-2 of the DCM
LED INDICATORS The three status LED’s on the front of the DCM convey the following infor”mation:
Status LED
State
Description
DATA
On
Data being transferred to/from the communication port.
Off
Data not being transferred to/from the communication port or data incorrect due to: 1
0
20 30 DIAG
PWR
Parity overrun or framing errors; Invalid header, data block, control character, or checksum; Time out on serial sink.
On
Power-up hardware diagnostics have passed.
Off
Power-up hardware diagnostics have failed.
On
5 V dc power to DCM is connected.
Off
5 V dc power to DCM is not connected.
NOTE Power to the DCM can come from the Series Three CPU or external supply depending on position of power select switch. When the power supply select switch is in the EXT position, power must be supplied through the external power supply connector on the front of the DCM. See Figure 3.1.
Page 32
GEK-90477
FRONT installation and Operation
3-3 of the DCM
PANEL CONNECTORS a-
Three connectors 1. 2. 3.
on the front of the DCM provide
Series Three CPU (CPU Connector); External serial device (Communications External power supply.
Each of these interfaces are described an interface to:
Connector);
and below.
Series Three CPU Connector The CPU connector (25pin male, D-type) ties the DCM to the Series Three CPU. All communication with the Series Three, as well as operating power (if the power supply The cable select switch is set to internal) is transmitted through this interface. (lC630CBL395A) is provided with each DCM for the link.
Communications
Connector
The communications devices. A detailed
External connector description
(25pin female, D-type) connects the DCM to external (pin by pin) of this connector is shown in Chapter 4.
Power Supply Connector
The external power supply connector allows the DCM to receive its operating power (5 V Users with Series Three power supply dc at 0.5 A) from an external supply. lC630PWR3OOA require an external power supply to operate a DCM. Other Series Three power supplies may or may not necessitate the use of an external power supply for proper operation of the DCM. This is dependent on the number and type of I/O modules in the CPU rack. Refer to Tables 3.2 and 3.3. A three conductor cable is provided with the DCM for external power supply connection. Its color code is as follows: WHITE: BLACK: GREEN:
+5V DC (+ 5%) at 0.5 amps Logic gr&nd of power supply Power system ground.
Page 33
GEK-90477
Installation
DCM CONFIGURATION and Operation of the DCM
3-4
SWITCHES
The ON/OFF line switch is located on the front of the DCM. switches are located on the back of the DCM as shown below.
The othk configuration
TPK.A.40226
. .
I
-ON L t
I
PWR EXT
I
IN1
LL
Figure
ON/OFF-LINE
3.2
LOCATION
OF THE DCM CONFIGURATION switch which communications is recessed on the front panel with the Series Three CPU.
Switch
The ON/OFF-line disables the serial
OFF LINE: Serial communication CPU is under control ON LINE:
SWITCHES between the DCM of the programmer.
Serial communication between programmer is not functional.
the DCM of the
DCM enables or the and CPU is disabled, and and is enabled, and the
CPU
Page 34
GEK-90477
Installation and Operation of the DCM
3-5
NOTE The terminal LED indicator on the face identifies the status of the serial link between Terminal Terminal
Interaction
LED ON: LED OFF:
between the DCM ON/OFF-LINE
DCWCPU DCM/CPU of the Series Three the DCM and CPU. interface interface enabled. disabled.
switch and the CPU Keyswitch
In order to establish or maintain the serial link between the DCM and the Series Three CPU, the CPU keyswitch must be in the Run 1 or Run position, and the DCM ON/OFF-LINE switch in the ON-LINE position. If the CPU keyswitch is ever taken out of the Run l/Run position when the serial link is enabled, the link will become disabled and the TERMINAL LED will turn off. To re-enable 1. 2.
communications:
Put the CPU keyswitch back in Run 1 or Run position, Cycle the ON/OFF-LINE switch on the DCM with the final LINE.
position
NOTE Once the link is established and the TERMINAL LED is on, the Series Three CPU can be put in either Stop/Program or Run mode* by a serial request from the master device on the link. See the application examples in Chapter 5.
being
ON
Page 35
GEK-90477
Installation and Operation of the DCM
3-6
CPU (Unit) ID DIP Switches The top group of eight DIP switches located on the back of the DCM (see Figure 3.2), determine the CPU ID of l-90. The switch configuration associated with each ID is shown in Figure 3.3. TPK.A.40223
\
EXAMPLE OF UNIT 10 SWITCH SETTlNGS. EXAUPLE SWlTCH IS SET Fm UNIT ADDRESS9.
L la0
1 I L r I I
Jcr> m
Iw
. /
Jo
NOT USE0
%E;
]b
)m
WO-
, 1
UNIT ID
2 3 4 5 6 07
DIP WITCH POSITION ~8 7 6.514 3'2.1, I 1,X X xx Xl x x xx 1 Ix ~X,X x
9 10
. I
1 , , , , , ,
, , , , , / , , , ) , , , , , , , , , , 1
20
21 22 23 24 25 26 lx x x x x x 1 .x xxx1 ~ xx I .X.X ,x. , I .x.x. x
I!
14
15 16 17 18 19
Ix1 x,
X
AX
Xx
51 52 53 54 55 56 57
1
58
27
1
1
XX
28
I
I
JX
29 30
I.1 XXX Ix 59 1 - 1 _X_X.X_Xi _ 60
X
Figure
31 32 33 34 35 36 37 38
39 40 _ XI x xl 41 xx 42 I 1 lx x. ,x 43 I x xix1 , 44 x xix x 45 . X.11.. . 46 x 47 X x X 48 .X. x x, 49 50
11 12 13 x x.
UNIT ID
3.3
= Switch x in the
DIP WITCH UUIT POSITION ID 81716 51413 211 1 X'XlX X!XI 61 Ix I 62 63 IX 64 i IX ,X Xf x '. XX 65 x x ~66 Xt, , Xt, T !X 67 .x xx 68 X XXX 69 ,x xl 70 x xi x 71 . ,x .x1 ,x 72 1 1 .. x ,xl Ix x, 73 T x XI 74 X Ix, x x x 75 . IX XXX 76 x x x x, 77 OX ,xx, 1 78 , 1 /x,x 1 .x1 79 Ix x Ix i 80 /XX 1Xx1 81 1 Ix x, x I 82 IX X X -Xi 83 lxx xx 84 1 I Ix x OX x,x 85 xxx 86 x x.x X 87 I x x,x, Ix 08 X XIX! X X 89 _ . .X.X1X1X. 1 L 90
, SWITCH POSITION 18 7 615]413!2!1 xlxlx_xl Ix 1 xixlx xlxi , 1 I [l X x!x!x,xix]x 1 Xl IX X. xlI 1 1 , X .~ Xix 1 X XI ! , X XI x, Xl ~XIX ( X x1x1x X~ Xi 1 [ ~ _. .x xl I Ix X X~ ix1 ( X x ix/x x, ixlxl I . r x11 x Xl ;x xl x xix; ( XT rx xlxix (, xl x I xi .x . x. ,xl x x, 1 x Ix xx+ X iX X .x lx x X< OX Ix xx. x Ix X,XiX ,, , X .XX f .X' x x, x., i .X X./x] I(, ( DIP
OU position
DIP-SWITCH
SETTINGS
FOR CPU ID SELECTION i
Page 36
GEK-90477
Installation
Communication and Operation
Port Configuration of the DCM
3-7
DIP Switches
The bottom group of eight DIP switches on the back of the DCM selects the mode of operation for the communication port (refer to Figure 3.2 for location of switches). The various settings for the communication set up parameters are shown in Table 3.1. To execute the loop-back test the ON/OFF-LINE switch must in the Off-Line mode.
Table 3.1
COMMUNICATIONS
PORT CONFIGURATION
DATA RATE SELECTION (BPS)
DIP-SWITCH
1200 9600 19.2 k
DIP-SWITCH NUMBER 1 2 OFF OFF ON OFF OFF ON ON ON
PARITY SELECTION
DIP-SWITCH NUMBER
*300
SETTINGS
3
Parity ENABLED (Odd parity generated and checked). *Parity DISABLED (No parity is generated or checked).
ON OFF l
LOOP-BACK TEST (Special Connector Required) Enabled *Disabled
DIP-SWITCH NUMBER 4 ON OFF
TURN-AROUND DELAY
DIP-SWITCH NUMBER 5 OFF ON
* 0 ms delay 10 ms delay
KEYING SIGNAL Enabled *Disabled
*Factory set default posit ion.
DIP-SWITCH NUMBER 6 ON OFF
.
Page 37
GEK-90477
Installation and Operation of the DCM
3-8
POWER SUPPLY SELECT SWITCH There is a power internal (CPU) or switch orientation in this chapter for supply select switch on the back of the module for fhe selection of external power for the DCM. An adjacent label indicates correct for each selection. See the section, External Power Supply Connector, information on the installation of an external power supply.
USING THE DCM WITH CPU RACK
POWER
Users with Series Three power supply IC630PWR300A require an external 5 V dc power supply to operate the DCM. If power supply IC630PWR300A is used with the DCM, inconsistent CPU or communications operation will result.
NOTE Even if a high-capacity power supply is being used in the CPU rack, inconsistent CPU or communications operation may be observed depending on the number and unit load of I/O modules installed in the rack. Refer to Tables 3.2 and 3.3 for units of load supplied by the different racks and used by I/O modules and other system devices.
Table 3.2
CATALOG NUMBER
IC63OPWR30OA IC63OPWR31OA IC63OPWR314A IC630PWR320A IC63OPWR324A
* 1 unit = 10 mA.
SERIES THREE
UNITS*
DESCRIPTION
P.S.
115/230 115/230
Vat Vat
Hi Cap. Hi Cap. Hi Cap.
P.S. P.S. P.S.
24 Vdc Remote Remote
I/O I/O
P.S.
(SUPPLIED)
i
POWER SUPPLIED IN UNITS OF LOAD
Hi Cap.
Standard
OF LOAD
115/230Vac 24 Vdc
+5v
+12v
250 300 300 300 300
100 200 200 200 200 b
Page 38
GEK-90477
Installation and Operation
Table 3.3 SERIES THREE
ZATALOG NUMBER
DESCRIPTION (CIRCUITS)
3-9 of the DCM
UNITS*
OF LOAD (USED)
POWER USED IN UNITS OF LOAD +12 v +5 V
IC630CPU301A IC630MDL301A IC630MDL302A IC630MDL303A IC630MDL304A IC630MDL306A IC630MDL310A IC630MDL311A IC630MDL316B IC630MDL324A IC630MDL325A IC630MDL326A IC630MDL327A IC630MDL351A IC630MDL352A IC63OMDL353A IC63OMDL354A IC630MDL356A IC630MDL357A IC630MDL366A IC630MDL367A IC630MDL368A IC630MDL375B IC630MDL376B IC630MDL380A IC630CCM300A IC63OCCM3lOA IC630CCM311A IC630PER320A IC630PER321A IC630PER330A IC63OPER331A
CPU/Programmer Unit Inp 24 V dc sink (16) Inp 24 V dc sink (32) Inp 5-12 V dc sink (32) I/O 24 V dc sink (16/16) Inp 24 V dc sink w LEDs (32) Hi Speed Counter (1) Inp 24 V ac/dc src (16) Analog Inp 1-5, l-10 V dc (2) I/O Simulator (16) Inp 115 V ac (16) Inp 115 V ac isolated (8) Inp 230 V ac (16) Out 24 V dc sink (8) Out 24 V dc sink (16) Out 24 V dc sink (32) Out 5-12 V dc sink (32) Out 24 V dc sink w LEDs (32) Out 24 V dc src (16) Analog Out l-5 V dc, 4-20 mA (2) Analog Out -10 to +lO V dc (2) Analog Out O-10 V dc, 4-20 mA (2) Out 115 V ac (16) Out 115 V ac isolated (8) Out Relay 5-265 ac/dc (16) Data Comms Module I/O Link Local I/O Link Remote I/O Link Local F'brOpt P-P I/O Link Remote Fbr Opt P-P I/O Link Local F'brOpt M-P I/O Link Remote F%r Opt M-P
* 1 unit
Calculations
= 10 mA.
are based on the worst case--all
150 11 5 5 9 8 20 9 30 11 17 6 9 2 4 10 16 10 2 33 33 33 4 4 4 50 80 80 80 80 80 80 inputs
-
10 18 39 30 39 64 l
-
- and outputs on
Page 39
GEK-90477
Installation
INSTALLING
THE DCM
To install 1. 2. 3. 4.
and Operation of the DCM
3-10 the DCM: Set the internal/external power switch to the desired position. Position the unit address (ID) and port configuration DIP switches to the desired position (see Figure 3.3 and Table 3.1). Mount the DCM in the Series Three rack or outside the rack within about 5 feet of the CPU. With the Series Three power off, connect the DCM to the CPU using cable IC630CBL395A as shown in Figure 3.4.
If, before powering up, the DCM ON-LINE/OFF-LINE switch is placed in the ON-LINE position and the Series Three CPU switch is in the RUN position, after power up the PWR and DIAG indicators on the DCM should light in that order. In addition, the RUN and For more information on power-up TERMINAL indicators on the CPU should light. conditions affecting the CPU and communications status see Table 3.4. TPK.A.40458
Figure
3.4
CONNECTING
THE DCM TO THE CPU
Page 40
GEK-90477
Installation
POWER CYCLE and Operation
CONDITIONS
3-11 of the DCM
AFFECTING
SYSTEM OPERATION
When the power is cycled, the resulting CPU and communications status position of the DCM ON-LINE/OFF-LINE switch as shown in Table 3.4.
Table 3.4 a depends upon the
POWER CYCLE CONDITIONS AFFECTING SYSTEM OPERATION (The user program is assumed to be in CMOS RAM).
DCM
CPU KEY-SWITCH
RESULTING CPU AND C.OMMUNICATIONS STATUS ON POWER CYCLE
On-Line
Run
CPU in Run mode with TERMINAL mode indicator ON.
Off-Line
Run
CPU in Run mode with TERMINAL mode indicator OFF. \