Report Faults to CPU

Fault reports to the host can be disabled or enabled for any circuit on a block.

If fault reporting is enabled for a circuit, the block will send a message to the host if any fault occurs on that circuit.

If fault reporting is disabled, the block will not send fault reports to the CPU for that circuit.

Regardless of whether fault reporting is enabled, the block will detect faults on the circuit, and take appropriate actions. The Unit OK LED will blink when a fault occurs, and a fault report is sent to a Hand-held Monitor. The fault condition must be corrected for proper operation of the block.

If the CPU requests diagnostic information from the block using Read. Diagnostics datagrams, the block returns current diagnostics for all circuits, including any with CPU fault reporting disabled.

Hand-held Monitor Configuration Steps

1. The screen displays the current Fault Reports selection for all

REPORT FAULTS ? circuits on the block. Qn this screen,

REF oo.

YYYYYYYYYYYYYVYYY Y = report faults.thatoccur on the circuit. tgl entr nxt N = do not report faults

To select a circuit, press F1 (>). To change the I/O type of the selected circuit, press F2 (tgl).

To save the new selection, press F3 (entr).

After configuring circuits, press F4 (next) to advance to the next configuration display.

8-16 Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2

Page 18 read from a scan by OCR; it may hold reading errors

Hold Last State

Each output can be independently configured to either hold its last state or to go to its powerup default state if the block loses CPU communications for at least 3 bus scans.

For a new block, Hold Last State is disabled for each output. With Hold Last State disabled, the block sets the output to its powerup default if CPU communications are lost.

If Hold Last State is enabled, the block continues to hold the output in its current state instead of setting it to the powerup default.

Outputs remain in their last state or default indefinitely or until one of the following occurs:

= Communications with the CPU are restored. m= The Hand-held Monitor changes the output by forcing it.

= Power is removed from the block.

Hand-held Monitor Configuration Steps

1. The screen displaysthe current Hold Last State configuration of

HOLD LAST STATE? all circuits. On this)screen) REF YYYYNNNNXXXXXXXX Y = hold last state.

> tgl entr nxt N = go to,default state (configured on the next HHM screen)

X = the circuit has been configured as an input. To select a circuit, press F1 (>). To change the selection for a circuit, press F2 (tgl).

To save the new selection, press F3 (entr).

Press F4 (next) when you are ready to advance to the next configuration display.

GEK-90486D-2 Chapter 8 16 Circuit DC Input/Output Blocks 8-17

Page 19 read from a scan by OCR; it may hold reading errors

Output Default State

An output goes to its powerup default state when the block is first powered up.

If Hold Last State was NOT enabled, the block will also default the output if CPU communications are lost. On a non-redundant system, this occurs approximately 250mS after the third bus scan passes with no CPU communications. If the block is ona redundant bus downstream of a Bus Switching Module, more time is needed.

Hand-held Monitor Configuration Steps

1. The screen displays the Output Default state configuration of all

OUTPUT DEFAULT circuits. On this screen, 500 0 = default is off. 000000111XXXXxXxx = default is off.

> tgl entr nxt 1 = default is on.

X = the circuit has been configured as.an input. To select a circuit, press F1 (>). To change the selection fora circuit, press F2 (tgl).

To save the new selection, press F3 (entr).

Press F4 (next) when you are ready to advance to the next configuration display.

Report No Load

By default, each output is,configured to report No-Load diagnostics. Energizing the output activates ano-load current level. If the load does not continuously draw 50mA from the output circuit, the block sends a NO LOAD message.

Disable this diagnostic for any output where a very small load (small relay, transformer, or indicating lamp) will draw less than 50 mA.

Hand-held Monitor Configuration Steps

1. The screen displays the Report No Load configuration of all

REPORT) NO LOAD? outputs. On this screen, REF . us YYYYYYYNNXXXXXXX Y = the output will report No Load conditions.

> tgl entr nxt N = the output will not report No Load conditions.

X = the circuit has been configured as an input. To select a circuit, press F1 (>). To change the selection for a circuit, press F2 (tgl).

To save the new selection, press F3 (entr).

ah a ae hd

Press F4 (next) when you are ready to advance to the next configuration display.

8-18 Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2

Page 20 read from a scan by OCR; it may hold reading errors

Overload Shutdown

Overload Shutdown protects output loads, field wiring, and switching devices. Ifa load exceeds 2.8 amps DC for 100mS and Overload Shutdown is enabled, the block turns the output off and sends an OVERLOAD message.

Under certain conditions (see page 8-7), Overload Shutdown detection and reporting can be disabled for output loads that require more than 2 amps RMS.

Hand-held Monitor Configuration Steps

OVRLOAD SHUTDWN? REF YYYNNNNNXXXXXXXX

> tgl entr nxt

GEK-90486D-2

1.

The screen displays the Overload Shutdown configuration of all circuits. On this screen,

Y = overload will shut down output.

N = output will remain on.

X = the circuit has been configured as an input. To select a circuit, press F1 (>).

To change the selection for.a circuit, press F2 (tgl). To save the new selection, press F3 (entr).

Press F4 (next) when you are ready to advance to the next configuration display.

Chapter 8 16 Circuit DC Input/Output Blocks 8-19

Page 21 read from a scan by OCR; it may hold reading errors

B

SM Present

If the block is connected to a single bus or to just one trunk of a dual bus, BSM Present should be set to NO.

Select YES if the block is located in a cluster connected to dual busses via a Bus Switching Module.

Hand-held Monitor Configuration Steps

1. To change the BSM Present configuration, press F2 (tgl).

BSM PRESENT ? ; REF 2. To save the new selection, press F3 (entr).

STATUS = YES 3. Press F4 (next) to advance to the next configuration display. tgl entr nxt

BSM Controller

ABSM Controller is a block to which a Bus Switching Module is directly attached, which controls the BSM’s switching action., Selecting a block to be a BSM Controller block has no effect on the block’s I/O type - the block can still be configured as an inputs-only block, but circuit #1 cannot be physically used as an input. The first circuit will not be under CPU control.

To change this configuration with a Hand-held Monitor, the block must first be configured for BSM PRESENT. The BSM CONTROLLER menu will not appear if BSM PRESENT is set to/NO.

Hand-held Monitor Configuration Steps

1. To change the configuration, press F2 (tgl).

BSM CONTROLLER? ; REF 2. To save the new selection, press F3 (entr).

STATUS = NO 3. Press F4 (next) to advance to the next configuration display. tgl entr nxt

8-20

Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2

Page 22 read from a scan by OCR; it may hold reading errors

Output Default Time

When a Bus Switching Module is used, the Output Default Time must be long enough to allow the BSM to switch without causing outputs to default. Therefore, when BSM Present is selected (above), the block automatically changes its Output Default Time from 3 bus scans to 2.5 seconds.

If Hold Last State was selected, outputs will remain in their last state while the BSM Switches, instead of defaulting, so there is no need to change this selection.

If Hold Last State was set to NO for any output on a block, and total bus scan time will exceed 100mS, change this selection to 10 seconds.

Hand-held Monitor Configuration Steps

1. To change the configuration, press F2 (tgl).

OUTPUT DEF .TIME ; REF 2. Tosave the new selection, press,F3)(entr).

TIME = 2.5 SECS 3. Press F4 (next) to advance to the next configuration display. tgl entr nxt

CPU Redundancy

The block can be configured for No Controller redundancy, Hot Standby or Duplex redundancy, or Genius ModularRedundancy (GMR). For new blocks, No Controller Redundancy is selected.

In Hot Standby mode, a blockreceives output data from both CPUs but uses the data from only one of them to.drive its outputs. The block prefers outputs sent by the bus interface module (Bus’Controller or PCIM) with Device Number 31. If those outputs are not available, the block will use outputs from the bus interface module with Device Number 30. If no outputs from a CPU are available, outputs will either Hold Last State or go to their defaults.

In Duplex,redundancy mode, the block compares outputs received from two CPUs and sets any outputs for which there is disagreement to their Duplex Default state.

Select,GMR mode only for blocks that will be part of a Genius Modular Redundancy system as described in the GMR User’s Manual. Do not try to configure a block for GMR mode without referring to the detailed configuration instructions in that book.

Hand-held Monitor Configuration Steps

1. To change the current selection, press F2 (tgl).

CPU REDUNDANCY REF 2. Press F3 (entr) to save the new selection.

NO CTRL REDUND 3. Press F4 (next) to advance to the next configuration display. tgl entr nxt

GEK-90486D-2 Chapter 8 16 Circuit DC Input/Output Blocks 8-21

Page 23 read from a scan by OCR; it may hold reading errors

Duplex Default State

In Duplex Redundancy mode, if the block receives different output states for given points, the block breaks the tie by outputting the Duplex Default State to those points. For new blocks, OFF is selected for all outputs. Change it if outputs should be ON.

Hand-held Monitor Configuration Steps

1. To change the Duplex Default state, press F2 (tgl). Press F3

DUPLEX DEFAULT (entr) to save the new selection. ore 2. Press F4 (next) to advance to the next configuration display.

tgl entr nxt g Note

If the block loses communications with BOTH CPUs, individual outputs go to their configured Hold Last State or Output Default State.

Configuration Protection

This feature can be used to protect the block’s configuration, preventing changes from the CPU or Hand-held Monitor. It can only be selected from the Hand-held Monitor. To make subsequent changes, protection must be removed again using the Hand-held Monitor. For a new block, configuration is unprotected. Before a block is used in the system, its configuration should be protected.

Hand-held Monitor:Configuration Steps

1. To change the current selection, press F2 (tgl).

CONFIG PROTECT REF 2. Press F3 (entr) to save the new selection.

DISABLED 3. Press F4 (next) to return to the first configuration display. tgl entr nxt

8-22 Genius I/O Discrete and Analog Blocks User’s Manual, September 1993 GEK-90486D-2