The text of a spec sheet · part 1 of 2
Series 90 PLC Serial Communications User's Manual, Chapter 2: The Communications Coprocessor Modules, pages 1 to 8
Pages 1 to 8 of 15
The original document is the PDF (211 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the GE Fanuc IC693CPU311X
Page 1
Chapter
2 The Communications Coprocessor Modules
2 section level 1 1 figure bi level 1 table_big level 1
This chapter describes the Communications Coprocessor modules (CMM311, CMM711) and explains how to install and configure the modules. Also included is a discussion of the system operation of the modules in the Series 90 PLC: The chapter is divided into two sections. !
Section 1: Description of CMM Hardware and Operation
!
Section 2: Installing and Configuring the CMM
Overview of the CMM The Communications Coprocessor Module (CMM) is a high-performance microcomputer designed to perform communications functions in a Series 90 PLC system. The CMM is closely coupled to the Series 90 PLC and may be configured to behave as two independent communications ports. For many applications, each port behaves like an independent window into the PLC for access by other devices, such as industrial computers and color graphic terminals. Many applications, which accessed the Series Six PLC user reference tables using CCM or RTU protocols, can now support the Series 90 PLC with little or no change. Many applications, which access the Series 90 PLC via the built-in serial port on the PLC CPU using SNP protocol, can now access the PLC via the CMM module. Each CMM occupies a single slot in a Series 90 PLC rack. Up to 28 CMMs may be installed in a single Series 90-70 PLC system to improve access to serial I/O devices and to access PLC memory. In Series 90-30 PLCs, up to 4 CMMs may be installed in the main rack (baseplate).
GFK-0582D
2–1
Page 2
2
Section 1: Description of CMM Hardware and Operation This section covers the following topics for both the CMM711 for the Series 90-70 PLC and the CMM311 for the Series 90-30 PLC. !
LED Indicators
!
Restart/Reset Pushbutton
!
Serial Connectors
!
System Operation
The figures below show the layout of the CMM modules:
a44901 DOOR
BD OK PORT 1 PORT 2 RESTART
MODEL 70 CMM 711 MODULE OK PORT 1 PORT 2 ON = OK, ACTIVE BLINK = COMMUNICATING PUSH TO RESTART APPLICATION
PORT 1
PORT 1 RS–232 OR RS–422 COMPATIBLE
PORT 2 RS–232 OR RS–422/485 COMPATIBLE MODULE FUNCTION
PORT 2
SERIES 90–70 COMMUNICATIONS COPROCESSOR PORT 1 & 2 RS–232 PIN SIGNAL 1 SHIELD 2 TD 3 RD 4 RTS 5 CTS 7 GROUND 8 DCD * 20 DTR * PORT 1 & 2 RS–422 PIN SIGNAL 7 GROUND 9 SD (A) 10 RTS (A) * 11 CTS (A) * 12 TERM PIN 11 * 13 RD (A) 21 SD (B) 22 RTS (B) * 23 CTS (B) * 24 TERM PIN 25 * 25 RD (B) *CONFIGURA TION DEPENDENT MODULE IC697CMM711 LABEL 44A726758–124R01
Figure 2-1. Series 90-70 CMM (CMM711)
2–2
Series 90 PLC Serial Communications User’s Manual – November 2000
GFK-0582D
Page 3
CCM Modules
2 a44902
COMM COPROC
OK US1 US2
OK US1 US2
RESTART
COMBINED SERIAL PORT PORT1 & PORT2
Figure 2-2. Series 90-30 CMM (CMM311) Except for the serial port connectors, the user interfaces for the CMM311 and CMM711 are the same. The Series 90-70 CMM711 has two serial port connectors. The Series 90-30 CMM311 has a single serial port connector supporting two ports. Each of the user interfaces are discussed below in detail.
LED Indicators The three LED indicators, as shown in the figures above, are located along the top front edge of the CMM board.
Module OK LED The MODULE OK LED indicates the current status of the CMM board. It has three states: Off: When the LED is off, the CMM is not functioning. This is the result of a hardware malfunction (that is, the diagnostic checks detect a failure, the CMM fails, or the PLC is not present). Corrective action is required in order to get the CMM functioning again. On: When the LED is steady on, the CMM is functioning properly. Normally, this LED should always be on, indicating that the diagnostic tests were successfully completed and the configuration data for the module is good. Flashing: The LED flashes during power-up diagnostics.
Serial Port LEDs The remaining two LED indicators, PORT1 and PORT2 (US1 and US2 for the Series 90-30 CMM311) blink to indicate activity on the two serial ports. PORT1 (US1) blinks when port 1 either sends or receives data; PORT2 (US2) blinks when port 2 either sends or receives data. GFK-0582D
Chapter 2 The Communications Coprocessor Modules
2–3
Page 4
2
Restart/Reset Pushbutton If the Restart/Reset pushbutton is pressed when the MODULE OK LED is on, the CMM will be re-initialized from the Soft Switch Data settings. If the MODULE OK LED is off (hardware malfunction), the Restart/Reset pushbutton is inoperative; power must be cycled to the entire PLC for CMM operation to resume.
Serial Ports The serial ports on the CMM are used to communicate with external devices. The Series 90-70 CMM (CMM711) has two serial ports, with a connector for each port. The Series 90-30 CMM (CMM311) has two serial ports, but only one connector. The serial ports and connectors for each PLC are discussed below.
Serial Ports for the CMM711 The Series 90-70 CMM has two serial ports, each of which support both RS-232 and RS-485 modes. The pin assignments of the serial ports are identical.
Note When using the RS-485 mode, the CMM can be connected to RS-422 devices as well as RS-485 devices. The connector pin assignments for both ports of the Series 90-70 CMM are shown below:
a42734 SHIELD
1
RS-232 TD
2
RS-232 RD
3
RS-232 RTS RS-232 CTS NO CONNECTION SIGNAL GROUND RS-232 DCD RS-485 SD ( A ) RS-485 RTS ( A ) RS-485 CTS ( A’ ) TERMINATION ( CTS ) RS-485 RD ( A’ )
14
RESERVED
15
RESERVED
16
RESERVED
17
RESERVED
18
RESERVED
19
RESERVED
20
RS-232 DTR
21
RS-485 SD ( B )
22
RS-485 RTS ( B )
23
RS-485 CTS ( B’ )
24
TERMINATION ( RD )
25
RS-485 RD ( B’ )
4 5 6 7 8 9 10 11 12 13
Figure 2-3. Serial Port Pin Assignments for the Series 90-70 CMM
Note In the figure above, SD (Send Data) and RD (Receive Data) are the same as TXD and RXD (used in the Series SixTM PLC). (A) and (B) are the same as – and +. A’ and B’ denote inputs, and A and B denote outputs. To terminate the RS-485 CTS input signal, jumper pins 11 and 12; to terminate the RD input signal, jumper pins 24 and 25. 2–4
Series 90 PLC Serial Communications User’s Manual – November 2000
GFK-0582D
Page 5
CCM Modules
2
Serial Ports for the IC693CMM311 The Series 90-30 CMM has a single serial connector which supports two ports. Port 1 applications must use the RS-232 interface. Port 2 applications can select either the RS-232 or RS-485 interface.
NOTE When using the RS-485 mode, the CMM can be connected to RS-422 devices as well as RS-485 devices. The connector pin assignments for the Series 90-30 CMM are shown below.
a44357 SHIELD
1
( PORT 1 ) RS-232 TD
2
( PORT 1 ) RS-232 RD ( PORT 1 ) RS-232 RTS ( PORT 1 ) RS-232 CTS NO CONNECTION SIGNAL GROUND ( PORT 1 ) RS-232 DCD ( PORT 2 ) RS-485 SD ( A ) ( PORT 2 ) RS-485 RTS ( A ) ( PORT 2 ) RS-485 CTS ( A’ ) ( PORT 2 ) TERMINATION ( CTS ) ( PORT 2) RS-485 RD ( A’ )
14
RS-232 TD ( PORT 2 )
15
RS-232 CTS ( PORT 2 )
16
RS-232 RD ( PORT 2 )
17
RS-232 DTR ( PORT 2 )
18
RS-232 DCD ( PORT 2 )
19
RS-232 RTS ( PORT 2 )
20
RS-232 DTR ( PORT 1 )
21
RS-485 SD ( B ) (PORT 2 )
22
RS-485 RTS ( B ) ( PORT 2 )
23
RS-485 CTS ( B’ ) ( PORT 2 )
24
TERMINATION ( RD ) (PORT 2)
25
RS-485 RD ( B’ ) ( PORT 2 )
3 4 5 6 7 8 9 10 11 12 13
Figure 2-4. Serial Port Pin Assignments for the IC693CMM311 The RS-485 signals for port 2 and the RS-232 signals for port 1 are assigned to the standard connector pins. The RS-232 signals for port 2 are assigned to normally unused connector pins.
IC693CBL305 Wye Cable A Wye cable (IC693CBL305) is supplied with each Series 90-30 CMM and PCM module. The purpose of the Wye cable is to separate the two ports from a single physical connector (that is, the cable separates out the signals). In addition, the Wye cable makes cables used with the Series 90-70 CMM fully compatible with the Series 90-30 CMM and PCM modules. The IC693CBL305 Wye cable is 1 foot in length and has a right angle connector on the end that connects to the serial port on the CMM module. The other end of the cable has dual connectors; one connector is labeled PORT 1, the other connector is labeled PORT 2 (see figure below). The IC693CBL305 Wye cable routes the Port 2, RS-232 signals to the RS-232 designated pins. If you do not use the Wye cable, you will need to make a special cable to connect RS-232 devices to Port 2. See the following figure for IC693CBL305 cable connection information. GFK-0582D
Chapter 2 The Communications Coprocessor Modules
2–5
Page 6
2 a44357 SHIELD
1
( PORT 1 ) RS-232 TD
2
( PORT 1 ) RS-232 RD
14
RS-232 TD ( PORT 2 )
15
RS-232 CTS ( PORT 2 )
16
RS-232 RD ( PORT 2 )
17
RS-232 DTR ( PORT 2 )
18
RS-232 DCD ( PORT 2 )
19
RS-232 RTS ( PORT 2 )
20
RS-232 DTR ( PORT 1 )
21
RS-485 SD ( B ) (PORT 2 )
22
RS-485 RTS ( B ) ( PORT 2 )
23
RS-485 CTS ( B’ ) ( PORT 2 )
24
TERMINATION ( RD ) (PORT 2)
25
RS-485 RD ( B’ ) ( PORT 2 )
3
( PORT 1 ) RS-232 RTS
4
( PORT 1 ) RS-232 CTS
5
NO CONNECTION
6
SIGNAL GROUND
7
( PORT 1 ) RS-232 DCD
8
( PORT 2 ) RS-485 SD ( A )
9
( PORT 2 ) RS-485 RTS ( A )
10
( PORT 2 ) RS-485 CTS ( A’ )
11
( PORT 2 ) TERMINATION ( CTS )
12
( PORT 2) RS-485 RD ( A’ )
13
Single Connector End
PORT 1 SHIELD
1
RS-232 TD
2
PORT 2 SHIELD
1
RS-232 TD
2
RS-232 RD
3
RS-232 RTS
4
RS-232 CTS
5
14
14
15
RS-232 RD
15
3 16
RS-232 RTS
4
RS-232 CTS
5
16
17
17
18
18
6
6 19
SIGNAL GROUND
19
7 20
RS-232 DCD a44358
8
SIGNAL GROUND
7
RS-232 DCD
8
RS-232 DTR
21
RS-485 SD ( A )
9
RS-485 RTS ( A ) RS-485 CTS ( A’) TERMINATION ( CTS )
12
RS-485 RD ( A’)
13
25 13
RS-485 RTS ( B )
23
RS-485 CTS ( B’ )
24
TERMINATION ( RD )
25
RS-485 RD ( B’ )
11
24 12
RS-485 SD ( B )
22 10
23 11
RS-232 DTR
21 9
22 10
20
Wye Connector End
1 FOOT (+2.0 INCH, -0 INCH) LABEL
RS-232 25-PIN FEMALE CONNECTOR a44225 PIN 1
PORT 1 PORT 2
PCM COMM. CABLE IC693CBL305B
PIN 1
RS-232 25-PIN MALE CONNECTOR
IC693CBL305
RS-232/RS-485 25-PIN FEMALE CONNECTOR
PIN 1
Figure 2-5. IC693CBL305 Wye Cable Connections 2–6
Series 90 PLC Serial Communications User’s Manual – November 2000
GFK-0582D
Page 7
CCM Modules
2
Section 2: Installing and Configuring the CMM
This section explains how to install the CMM in the rack (Series 90-70) or baseplate (Series 90-30) and how to configure the module using Logicmaster 90 or the windows-based programming software. Topics covered are: !
What you will Need
!
Installing the CMM
!
Configuring the CMM
What you will Need Before you can begin the installation procedure, you must have the following equipment and software packages: !
A Series 90-70 or Series 90-30 Programmable Logic Controller (PLC). (For Series 90-30, the CPU must be a model CPU331 or higher.)
!
A Communications Coprocessor Module (CMM) to install and test: -
IC697CMM711 for a Series 90-70 CMM
-
IC693CMM311 for a Series 90-30 CMM
If this application uses CCM protocol with standard default settings for a Series 90-30 CMM (CMM 311), no other equipment is required. For other applications, you will also need the following:
GFK-0582D
!
A computer with a hard disk.
!
Programming software (either Logicmaster 90 or windows-based programming software).
Chapter 2 The Communications Coprocessor Modules
2–7
Page 8
2
Installing the CMM Hardware The first step in the installation procedure is to physically install the CMM hardware and verify that it is working properly.
Overview In a single rack system, the CMM resides in the same rack as the CPU. In a Series 90-70 multiple rack system, the CMM can reside in either the CPU rack or in an expansion rack. The Series 90-30 CMM must reside in the same rack as the CPU. The following illustration shows one possible system configuration for installing a Series 90-70 CMM in a local or expansion rack:
LOCAL RACK CONFIGURATION
P S
C C P M U M
CPU RACK
P S a44915
C B P T U M
EXPANSION RACK
P S
B C R M M M
Figure 2-6. Series 90-70 CMM Configurations The power supply, CPU, and Series 90-70 Bus Expansion Module must reside in specific slots within the rack. The term Bus Expansion Module includes both Bus Transmitter Modules and Bus Receiver Modules. The CPU Module must be located in slot 1 of rack 0. The Series 90-70 system usually includes a Bus Transmitter Module (BTM). Version A of the Bus Transmitter Module must be located to the right of all other GE Fanuc boards; version B must be located in slot 2 of rack 0. If the PLC system will have more than one rack, a Bus Receiver Module (BRM) must be located in slot 1 of each expansion rack. The CMM can be placed in any slot not already allocated in any rack, with the following cautions:
2–8
!
The configuration files created by the Logicmaster 90 configuration software must match the physical configuration of the modules. If they do not, the controller may not operate as expected. Any faults will be logged in the PLC fault table.
!
When CMMs are in a Series 90-70 rack, all the slots between the CMM and the PLC CPU must be occupied. If any of these slots are empty, the CMM will not be able to communicate across the backplane to the Series 90-70 PLC CPU.
!
The Series 90-30 CMM must be in the main rack (baseplate) with the PLC CPU.
Series 90 PLC Serial Communications User’s Manual – November 2000
GFK-0582D