For the GE GPS1BHAA, GE GPS2BHAP, Fanuc GPS1BHAA, GE Fanuc GPS1BHAA, Fanuc GPS2BHAP and GE Fanuc GPS2BHAP

Page 1

IEC Manual Motor Starters

Overview.........................................................................................................6-2 Selection Guide............................................................................................6-5 Accessories – Front Mounted ...............................................................6-7 Accessories – Side Mounted .................................................................6-7 Accessories – Group Mounted .............................................................6-9 Accessories – External Handle Operators ...................................6-10 Accessories – Other................................................................................6-10 Accessories – Integrated Starter Components .........................6-11 Enclosures and Enclosure Accessories .........................................6-13 Integrated with Contactor, Open, AC Operated Contactors, Standard Interruption Capacity ...........................6-15 Integrated with Contactor, Open, DC Operated Contactors, Standard Interruption Capacity ...........................6-16 Integrated with Contactor, Open, AC Operated Contactors, High Interruption Capacity.....................................6-17 Integrated with Contactor, Open, DC Operated Contactors, High Interruption Capacity.....................................6-18 Integrated with Contactor, Factory Installed Accessories..............................................................................................6-19

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Section 6

Enclosed, Non-metal Enclosures, Standard Interruption Capacity.....................................................6-20 Enclosed, Factory Installed Accessories .......................................6-21 Enclosed, Metal Enclosures, High Interruption Capacity ......6-22 Enclosed, Factory Installed Accessories .......................................6-23 Integrated with Contactor, Enclosed, AC Operated Contactors, High Interruption Capacity ........6-24 Integrated with Contactor, Enclosed, DC Operated Contactors, High Interruption Capacity ........6-26 Integrated with Contactors, Factory Installed Accessories .........................................................6-28 Outline Drawings .....................................................................................6-30 Wiring Diagrams – Accessories ........................................................6-42 Short Circuit Current Rating, Rating Breaking Capacity .......6-44 Type 2 Short Circuit Rating, Individual Group and Combination Starters..........................................................................6-45 Specifications.............................................................................................6-46 Time Current Curves...............................................................................6-47

Control Catalog

6-1

Page 2

IEC Manual Motor Starters

Section 6

Overview GE’s Surion IEC motor starters are compact and reliable. They are flexible, quick in installation and available in 45mm and 55mm widths. The GPS1 line spans current ranges from 0.1A to 32A for use with motors up to 30hp at 600V. The GPS2 series extends this current range to 63A for use with motors up to and including 50 hp. Surion GPS1 starters are available in two versions. The GPS1BS_ _ series, with a toggle operator, is suitable for individual and group installations. Short circuit interruption capacity ranges up to 100kA @ 240V, 50kA @ 480V and 10kA @ 600V for individual installations and 100 kA @ 240V, 65kA @ 480V and 25kA @ 600V for group installations. The GPS1BH_ _ series, with a rotary operator, carries equivalent or higher short circuit ratings and is also suitable for combination installations with a short circuit interruption rating of 50kA for 277/480V and below. The GPS2BH_ _ series also features a rotary operator and is suitable for all three types of installations. Complete short circuit ratings are listed on page 6-44. All Surion IEC motor starters include the following features:, 45mm width up to 32 amps, 55mm width rated to 63 amps, Three position operator: OFF-TRIP-ON, Padlockable in the OFF position, Class 10 overload trip characteristics, Ambient compensated –20°C to +60°C, Single-phase sensitivity, Anti tamper cover over current adjustment dial, Trip test, Complete range of common accessories, Finger-safe terminals, Pz 2 slotted/combination screws, 35mm DIN rail mounting

45 mm Standard Interruption Capacity

55 mm High Interruption Capacity

Surion is global. It is available around the world in the same form, with the same product number, with both IEC and US markings, making international applications simple and sure. Surion starters are flexible in application. They not only comply with the IEC installation requirements, such as Disconnects, Main Switch, Emergency Off and Maintenance Service Switch, they may also be used in a wide variety of US applications. Surion starters may be used as, Manual starters, Group installed starters, Combination starter – manual self-protected (Type E) GPS1BH* and GPS2BH* versions, Combination starter – with C-2000 contactor or mini-contactor

Integrated With Contactor

A complete range of accessories extends the application flexibility of the line. Front and side mounted auxiliary contacts, alarm contacts, short circuit reset/indicator alarm, shunt trip and undervoltage release (with or without early make auxiliary contacts) allow Surion to easily adapt to your specific needs. Input busbars further speed and simplify group installations. Enclosures and accessories extend flexibility. Bases, links and other components allow you to assemble integrated starters.

Accessories

6-2

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 3

IEC Manual Motor Starters

Section 6

Overview Individual Installation

Group Installation

Manual motor starters (UL-508, Part III) are devices that provide a means of controlling (switching on and off) a motor. UL-508 allows a manual motor starter to be applied in individual installations between a branch short circuit protection device (circuit breaker or fuse) and a motor (see Figure 1A).

Manual motor starters may be applied in group applications per Article 430-53 of the National Electrical Code. Refer to the NEC for specific requirements. Group installations are used when multiple loads are tapped off of a single branch short circuit protective device (circuit breaker or fuse). A manual motor starter is placed between the branch disconnect and each motor (see Figure 2A).

The UL, cUL listing allows Surion starters to be utilized in installations up to 600 volts. Short circuit ratings are listed in the tables on page 6-44. GE’s type MC or CL contactors may be used in series with the motor starter for remote motor operation as shown in Figure 1B. Contactors must not be applied at ratings above their nameplate HP/current ratings.

The UL, cUL listing allows starters to be utilized in installations up to 600 volts. Short circuit ratings are listed in the tables on page 6-44. GE’s type MC or CL contactors may be used in series with the motor starter for remote motor operation (see Figure 2B). Contactors must not be applied at ratings above their nameplate HP/current ratings.

or or

Figure 1A

Figure 2A or or

Figure 1B

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Figure 2B

Control Catalog

6-3

Page 4

IEC Manual Motor Starters

Section 6

Overview Combination Starters Surion GPS1BH* and GPS2BH* Manual Motor Starters may be used as combination starters (UL508 Part IV) and have been evaluated by UL as manual self-protected combination motor starters (Type E) for applications 277/480 and below. They provide coordinated branch circuit short circuit protection consistent with Section 430-52(c) (6) of the NEC; a disconnecting means consistent with Section 430-109 (a) (5); a motor starter and coordinated motor overload protection (see Figure 3A). These starters may be used for controlling motors without additional upstream branch circuit protection. They may be used in place of branch devices in motor circuits only. When used in panels with multiple motor circuits, a main circuit disconnect is required in sight and within 50 feet for the protection of service personnel. Surion GPS1BH* and GPS2BH* Manual Self Protected Combination Starters may also be used with a contactor when a high number of operations are required or remote switching is desired. A combination motor starter (see Figure 3B) is created by linking the self-protected manual motor starter with an evaluated contactor that has been tested for the combination. All C-2000 contactors and mini-contactors are suitable for use with Surion starters which, when used in this configuration, are suitable as combination motor starters. Using bases and links (see page 6-12) combination motor starters may be easily assembled by distributors, OEM’s or end users. This integrated starter approach allows the user to service or replace the load switching means (contactor) and/or the interrupting/disconnecting means (Surion starter) should the need arise.

Figure 3A

For combination starter installations, the standards require a means to differentiate between a short circuit and overload trip conditions. Surion delivers this means through the use of the Short Circuit Alarm Accessory GPAE11LLA (sold separately – see page 6-7). This accessory provides specific indication of a short circuit trip condition and includes a manual reset. Add GPAPT1E terminal cover to GPS1BH* for Type E and combination starter applications. Figure 3B

6-4

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 5

IEC Manual Motor Starters

Section 6

Selection Guide Selection and Pricing Surion comprises a complete range of compact, reliable motor starters, rated from 0.1A to 63A, in 45mm and 55mm frame widths. It represents a motor protection system for switching and protecting three-phase induction motors to 50hp at 600 volts. Surion starters are available worldwide. They are specifically designed to deliver total connectivity with GE’s other IEC motor starters and controls, and they can be combined with our MC and CL contactors to form integrated solutions. A full complement of accessories create solutions for all types of applications. You can choose from frontal auxiliary and alarm contacts, lateral auxiliary contacts, alarm/auxiliary and short circuit trip indicators, shunt trip, undervoltage release (with or without early make auxiliary contacts), enclosures, group bus bars and more. You can also select assembled versions.

45 mm Standard Interruption Capacity (Toggle)

Product Number Selection Instructions Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3. Reference Publications Instructions:

DEH-40111

45 mm High Interruption Capacity (Rotary)

55 mm High Interruption Capacity (Rotary)

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-5

Page 6

IEC Manual Motor Starters

Section 6

Selection Guide 45 mm Standard Interruption Capacity (Toggle Operator) Individual or Group Installation, with or without C-2000 contactors or mini-contactors FLA Adjustment Range 0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32

Three Phase Horsepower @ 200-208V

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

Three Phase Horsepower @ 220-240V

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

Three Phase Horsepower @ 440-480V

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

Three Phase Horsepower @ 575-600V

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 30

Single Phase Horsepower @ 115V

1/8 1/4 1/2 1/2 1 1 1/2 2 2

Single Phase Horsepower @ 230V

Instantaneous Short Circuit Release Amps

Product Number

List Price GO-10A2C

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

2.1 3.3 5.2 8.2 13 20.8 32.5 52 81.9 130 169 208 260 325 416

GPS1BSAA GPS1BSAB GPS1BSAC GPS1BSAD GPS1BSAE GPS1BSAF GPS1BSAG GPS1BSAH GPS1BSAJ GPS1BSAK GPS1BSAL GPS1BSAM GPS1BSAN GPS1BSAP GPS1BSAR

$88.00 $88.00 $88.00 $88.00 $100.00 $100.00 $100.00 $100.00 $100.00 $100.00 $120.00 $120.00 $120.00 $135.00 $135.00

45 mm High Interruption Capacity (Rotary Operator) Individual, Group or Combination1, 2 Installation, with or without C-2000 contactors or mini-contactors FLA Adjustment Range 0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32

Three Phase Horsepower @ 200-208V

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

Three Phase Horsepower @ 220-240V

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

Three Phase Horsepower @ 440-480V

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

Three Phase Horsepower @ 575-600V

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 30

Single Phase Horsepower @ 115V

1/8 1/4 1/2 1/2 1 1 1/2 2 2

Single Phase Horsepower @ 230V

Instantaneous Short Circuit Release Amps

Product Number

List Price GO-10A2C

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

2.1 3.3 5.2 8.2 13 20.8 32.5 52 81.9 130 169 208 260 325 416

GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR

$110.00 $110.00 $110.00 $110.00 $125.00 $125.00 $125.00 $125.00 $125.00 $125.00 $150.00 $150.00 $150.00 $165.00 $165.00

55 mm High Interruption Capacity (Rotary Operator) Individual, Group or Combination2 Installation, with or without C-2000 contactors or mini-contactors FLA Adjustment Range 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63

Three Phase Horsepower @ 200-208V

Three Phase Horsepower @ 220-240V

Three Phase Horsepower @ 440-480V

Three Phase Horsepower @ 575-600V

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

Instantaneous Short Circuit Release Amps

Product Number

List Price GO-10A2C

2 3 3 5 7 1/2 10 10 15 15

3 3 5 5 7 1/2 10 10 15 20

5 7 1/2 7 1/2 10 15 20 25 30 40

7 1/2 10 10 15 20 25 30 40 50

1/2 1/2 1 1 1/2 2 2 3 3 5

1 1/2 2 2 2 3 5 7 1/2 10 10

130 169 208 260 325 416 520 650 819

GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU

$245.00 $245.00 $245.00 $245.00 $245.00 $245.00 $275.00 $275.00 $302.00

1When using manual starters in combination starter applications, use short circuit reset/indicator accessory. For GPS1BH_ _starters add GPAPT1E terminal accessory. 2Maximum voltage for combination control is 277/480.

Product Number Selection Instructions Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3.

6-6

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 7

IEC Manual Motor Starters

Section 6

Accessories Front Mounted (Internal) Accessories - Auxiliary and Alarm Contacts Snap away the dust cover(s) and up to two front mounted accessories slide into the starter, increasing application flexibility without increasing width. Accessory Type

For Use With

Mounting Position

Contact Configuration

Product Number

List Price GO-10A2C

Auxiliary Contact (Front Mount) Auxiliary Contact (Front Mount) Alarm Contact (Front Mount) Alarm Contact (Front Mount) Front Aux. Position Cover (Package of 10)

GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2*

Left or right front Left or right front Right front Right front

1NC 1NO 1NC 1NO

GPAC01FBA GPAC10FBA GPAL01FRA GPAL10FRA

$12.00 $12.00 $14.00 $14.00

GPS1*/GPS2*

Left or right front

N/A

GPAC0VF1A

$0.50

GPAC_ _FBA Front Mounted Auxiliary Contacts

Side Mounted Accessories - Auxiliary and Alarm Contacts Snap on accessories - maximum of [(2) auxiliary contact blocks] or [(1) auxiliary contact block plus (1) alarm/aux. block or (1) short circuit indicator] or [(1) alarm/auxiliary plus (1) short circuit indicator] left and (2) auxiliary contact blocks or (1) shunt trip or (1) undervoltage release right. Accessory Type

For Use With

Mounting Position

Contact Configuration

Product Number

List Price GO-10A2C

Auxiliary Contact (Side Mount Auxiliary Contact (Side Mount) Auxiliary Contact (Side Mount) Auxiliary Contact (Side Mount) Auxiliary Contact (Side Mount) Auxiliary Contact (Side Mount) Alarm/Auxiliary Contact (Side Mount) Alarm/Auxiliary Contact (Side Mount) Alarm/Auxiliary Contact (Side Mount) Alarm/Auxiliary Contact (Side Mount) Short Circuit Alarm (Side Mount)

GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2*

Left Left Left Right Right Right Left Left Left Left Left

2NC 1NO + 1NC 2NO 2NC 1NO + 1NC 2NO 1NC Alarm + 1NC Aux. 1NC Alarm + 1NO Aux. 1NO Alarm + 1NC Aux. 1NO Alarm + 1NO Aux. 1NO + 1NC

GPAC02LLA1 GPAC11LLA1 GPAC20LLA1 GPAC02LRA1 GPAC11LRA1 GPAC20LRA1 GPAD0101LLA GPAD0110LLA GPAD1001LLA GPAD1010LLA GPAE11LLA2

$18.00 $18.00 $18.00 $18.00 $18.00 $18.00 $24.00 $24.00 $24.00 $24.00 $15.00

GPAC_ _FRA Front Mounted Alarm Contacts

1GPS1BSAR and GPS1BHAR (24-32 FLA starters) can accept all accessory combinations noted above except that only one lateral auxiliary contact block may be used on this size. 2GPAE11LLA short circuit alarm may not be used with non-metallic enclosures due to reset button interference.

GPAC_ _LLA/GPAC_ _LRA Side Mounted Auxiliary Contacts

GPAD_ _ _ _LLA Side Mounted Alarm/Auxiliary Contact

GPAE11LLA Side Mounted Short Circuit Alarm Terminal Identification and Wiring Diagrams: See page 6-42

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-7

Page 8

IEC Manual Motor Starters

Section 6

Accessories Side Mounted Accessories - Shunt Trip Snap on accessories - maximum of (2) auxiliary contact blocks or (1) shunt trip or (1) undervoltage release right side. Accessory Type

For Use With

Mounting Position

Coil Voltage

Product Number

List Price GO-10A2C

Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip Shunt Trip

GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2*

Right Right Right Right Right Right Right Right Right Right Right Right

24V 60/50 Hz 48V 60 Hz 60V 60 Hz, 48V 50 Hz 120V 60 Hz, 110-127V 50 Hz 208V 60 Hz 240V 60 Hz, 220V 50 Hz 277V 60 Hz, 240V 50 Hz 380/400V 50 Hz 460-480V 60 Hz, 415-440V 50 Hz 600V 60 Hz, 500V 50 Hz 24-60V DC 110-240V DC

GPASLRAA1 GPASLRAAF GPASLRAAG GPASLRAAJ GPASLRAAM GPASLRAAN GPASLRAAR GPASLRAAU GPASLRAAW GPASLRAAY GPASLRADD GPASLRADJ

$48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00

GPASLRA_ _Shunt Trip

De-energizes the controller when external signal is applied to shunt coil.

Side Mounted Accessories - Undervoltage Release Snap on accessories - maximum of (2) auxiliary contact blocks or (1) shunt trip or (1) undervoltage release right side. Accessory Type

For Use With

Mounting Position

Coil Voltage

Product Number

List Price GO-10A2C

Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release

GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2* GPS1*/GPS2*

Right Right Right Right Right Right Right Right Right Right Right

24V 60 Hz 24V 50 Hz 48V 60 Hz 48V 50 Hz 120V 60Hz, 110-127V 50 Hz 208V 60 Hz 240-260V 60 Hz, 220/230V 50 Hz 277V 60 Hz, 240V 50 Hz 380/400V 50 Hz 460-480V 60 Hz, 415-440V 50 Hz 600V 60 Hz, 500V 50 Hz

GPAULRAAC GPAULRAAD GPAULRAAF GPAULRAAG GPAULRAAJ GPAULRAAM GPAULRAAN GPAULRAAR GPAULRAAU GPAULRAAW GPAULRAAY

$48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00

GPAULRAA_Undervoltage Release

Provides protection from low voltage conditions; requires 85-110% voltage across D1 and D2 prior to starting motor; requires reset of starter upon undervoltage condition or loss of voltage.

Side Mounted Accessories - Undervoltage Release Snap on accessories - maximum of (2) auxiliary contact blocks or (1) shunt trip or (1) undervoltage release right side. Accessory Type Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release

For Use With

Mounting Position

Coil Voltage

Product Number

List Price GO-10A2C

GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS* GPS1BS*

Right Right Right Right Right Right Right Right Right Right Right

24V 60 Hz 24V 50 Hz 48V 60 Hz 48V 50 Hz 120V 60 Hz, 110-127V 50 Hz 208V 60 Hz 240-260V 60 Hz, 220/230V 50 Hz 277V 60 Hz, 240V 50 Hz 380/400V 50 Hz 460-480V 60 Hz, 415-440V 50 Hz 600V 60 Hz, 500V 50 Hz

GPAU20LTAAC GPAU20LTAAD GPAU20LTAAF GPAU20LTAAG GPAU20LTAAJ GPAU20LTAAM GPAU20LTAAN GPAU20LTAAR GPAU20LTAAU GPAU20LTAAW GPAU20LTAAY

$66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00

GPAU20LTAA_Undervoltage Release with 2NO early make contacts

With 2NO early make contacts (provides protection from low voltage conditions; early make contacts energize release coil when operator is turned to ON position and voltage is 85-110% Ve; requires reset of starter upon undervoltage condition or loss of voltage)

Side Mounted Accessories - Undervoltage Release Snap on accessories - maximum of (2) auxiliary contact blocks] or (1) shunt trip or (1) undervoltage release right side. Accessory Type Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release Undervoltage Release

For Use With

Mounting Position

Coil Voltage

GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH* GPS1BH*/GPS2BH*

Right Right Right Right Right Right Right Right Right Right Right

24V 60 Hz 24V 50 Hz 48V 60 Hz 48V 50 Hz 120V 60 Hz, 110-127V 50 Hz 208V 60 Hz 240-260V 60 Hz, 220/230V 50 Hz 277V 60 Hz, 240V 50 Hz 380/400V 50 Hz 460-480V 60 Hz, 415-440V 50 Hz 600V 60 Hz, 500V 50 Hz

Product Number GPAU20LCAAC GPAU20LCAAD GPAU20LCAAF GPAU20LCAAG GPAU20LCAAJ GPAU20LCAAM GPAU20LCAAN GPAU20LCAAR GPAU20LCAAU GPAU20LCAAW GPAU20LCAAY

List Price GO-10A2C $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00

GPAU20LCAA_Undervoltage Release with 2NO early make contacts

With 2NO early make contacts (provides protection from low voltage conditions; early make contacts energize release coil when operator is turned to ON position and voltage is 85-110% Ve; requires reset of starter upon undervoltage condition or loss of voltage)

6-8

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 9

IEC Manual Motor Starters

Section 6

Accessories Group Mounted Starter Accessories Accessory Type

For Use With

Maximum Amps

Spacing

Input Busbar Input Busbar Input Busbar Input Busbar Input Busbar

GPS1* GPS1* GPS1* GPS1* GPS1*

63A max. 63A max. 63A max. 63A max. 63A max.

45mm 45mm 45mm 45mm 54mm

Input Busbar

GPS1*

63A max.

54mm

Input Busbar

GPS1*

63A max.

54mm

Input Busbar

GPS1*

63A max.

54mm

Input Busbar

GPS1*

63A max.

63mm

Input Busbar

GPS1*

63A max.

63mm

Input Busbar Input Busbar Input Busbar Input Busbar

GPS2* GPS2* GPS2* GPS2*

120A max. 120A max. 120A max. 120A max.

55mm 55mm 55mm 64mm

Input Busbar

GPS2*

120A max.

64mm

Input Busbar

GPS2*

120A max.

64mm

Input Busbar

GPS2*

120A max.

73mm

Input Busbar

GPS2*

120A max.

73mm

Power Input GPS1* Busbar Terminal

63A max.

Power Input GPS2* Busbar Terminal

120A max.

Terminal Covers

GPS1*

Terminal Covers

GPS2*

Product Description

Terminal No. of Type Controllers

Used with no auxiliaries Pin Used with no auxiliaries Pin Used with no auxiliaries Pin Used with no auxiliaries Pin Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 2 aux or 1 aux+1 Fork aux/alarm or shunt or UV (two 9mm auxiliaries or one 18mm auxiliary) Used with 2 aux or 1 aux+1 Fork aux/alarm or shunt or UV (two 9mm auxiliaries or one 18mm auxiliary) Used with no auxiliaries Pin Used with no auxiliaries Pin Used with no auxiliaries Pin Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 1 aux or 1 aux Pin alarm (one 9mm auxiliary) Used with 1 aux or 1 aux) Pin alarm (one 9mm auxiliary) Used with 2 aux or 1 aux + Pin aux/alarm or shunt or UV (two 9mm auxiliaries or one 18mm auxiliary) Used with 2 aux or 1 aux + Pin aux/alarm or shunt or UV (two 9mm auxiliaries or one 18mm auxiliary) Used with GP1B Pozidrive busbars above Wire size – AWG 10-4 Torque – 38 lbs.-in. Used with GPB2 Allen Screw busbars above Wire Size - AWG 8 - 1/0 Torque - 54 lbs. in. Slips over unused GPB1BO_ _ (45mm) or GPB1B1_ _ (54mm) pin type input busbar terminals to provide touch protection Snaps over unused GPB2B0_ _ (55mm) or GPB2B1_ _ (64mm) pin type busbar terminals to provide touch protection

Product Number

List Price GO-10A2C

2 3 4 5 2

GPB1B02A GPB1B03A GPB1B04A GPB1B05A GPB1B12A

$12.00 $16.00 $20.00 $25.00 $14.00

3

GPB1B13A

$18.00

4

GPB1B14A

$22.00

5

GPB1B15A

$27.00

2

GPB1B22A

$22.00

4

GPB1B24A

$27.00

2 3 4 2

GPB2B02A GPB2B03A GPB2B04A GPB2B12A

$32.00 $40.00 $48.00 $34.00

3

GPB2B13A

$42.00

4

GPB2B14A

$50.00

2

GPB2B22A

$34.00

4

GPB2B24A

$50.00

GPB1FA

$16.00

GPB2FA

$28.00

GPB1GA

$2.50

GPB2GA

$3.00

GPB_B_ _ _Input Busbar

GPB_FA Power Input Busbar Terminal

GPB_GA Terminal Cover

Input Busbar simplifies group installations; different forms accommodate different accessories.

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-9

Page 10

IEC Manual Motor Starters

Section 6

Accessories External Handle Operators Allows operation of GPS1BH_ _ and GPS2BH_ _ starters through a panel door. Shaft mounting depth inside the panel can range from 5.5” - 11.4” (139.8 - 289.8 mm) for GPS1BH_ _ and 6.3” - 12.25” (161 - 311 mm) for GPS2BH_ _. For Use With

Handle Type

Product Number

List Price GO-10A2C

GPS1* GPS1* GPS2* GPS2*

Black Red/Yellow Black Red/Yellow

GPA1HAB GPA1HAR GPA2HAB GPA2HAR

$35.00 $35.00 $40.00 $40.00

GPA_HA_Handle Operator

Other Accessories Accessory Type

For Use With

Snap-in Tabs Terminal Covers Terminal Covers

GPS1* GPS2* GPS1BH*

Product Number

List Price GO-10A2C

For Screw Mounting GPS1 to panel1 GPAKS1A IP20 (package of 6) GPAPTP2A Additional protective cover required for GPAPT1E combination control. Easily suited for field installation. May not use front mounted internal accessories with cover in place. Cannot use GPB1 busbars with protective cover.

$.15 ea. $1.00 $12.00

Description

1Packaged in quantities of 10.

GPAKS1A Snap-in Tabs

GPAPTP2A Terminal Covers for GPS2*

GPAPT1E Terminal Covers for GPS1BH*

6-10

Control Catalog www.geindustrial.com