Page 1 of Control Catalog, Section 6: IEC Manual Motor Starters

Spec sheet · GE

Control Catalog, Section 6: IEC Manual Motor Starters

Spec sheet48 pagesPDF 16 MB

GE Control Catalog section on Surion IEC manual motor starters (GPS1 and GPS2 series), with selection tables, accessories and specifications.

Download the PDF16 MB

Covers · 6 models

The models it covers

Summary

What is in it

Section 6 of the GE Control Catalog, covering Surion GPS1 and GPS2 IEC manual motor starters, including catalog numbers such as GPS1BHAA and GPS2BHAP. It gives an overview of the range, a selection guide, front, side and group mounted accessories, enclosures, starters integrated with AC or DC operated contactors, enclosed starters, outline drawings, accessory wiring diagrams, short circuit ratings, specifications and time current curves.

Its parts

  1. Overview
  2. Selection Guide
  3. Accessories
  4. Enclosures and Enclosure Accessories
  5. Integrated with Contactor, Open
  6. Enclosed
  7. Integrated with Contactor, Enclosed
  8. Outline Drawings
  9. Wiring Diagrams – Accessories
  10. Short Circuit Current Rating, Rating Breaking Capacity
  11. Type 2 Short Circuit Rating, Individual Group and Combination Starters
  12. Specifications
  13. Time Current Curves

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

This is Section 6 of a GE Control Catalog, revision 4/16, on Surion IEC manual motor starters: the GPS1BS and GPS1BH series in 45 mm frames and the GPS2BH series in 55 mm frames, including the GPS1BHAA and GPS2BHAP. It gives selection tables, accessories, enclosures, short circuit ratings and specifications for choosing and applying a starter.

Read for this summary: pages 1 to 7, 10 and 44 to 46 of 48.

Product type
Surion IEC manual motor starters with rotary operator, high interruption capacity: GPS1BHAA in the 45 mm frame, GPS2BHAP in the 55 mm frame p. 6
Current range
GPS1: 0.1A to 32A, motors up to 30hp at 600V; GPS2: up to 63A, motors up to and including 50 hp p. 2
Frame width
GPS1: 45mm, up to 32 amps; GPS2: 55mm, rated to 63 amps p. 2
Operator and trip
OFF-TRIP-ON operator, padlockable in OFF; Class 10 overload trip; trip test; single-phase sensitivity p. 2
Combination use
The catalog states GPS1BH* and GPS2BH* were evaluated by UL as manual self-protected combination starters (Type E), 277/480 and below p. 4
Combination rating
GPS1BH: 50kA short circuit interruption rating for 277/480V and below in combination installations p. 2
Voltage
The catalog states the UL, cUL listing allows use in installations up to 600 volts p. 3
Ambient compensation
-20°C to +60°C p. 2
Mounting
35mm DIN rail p. 2
GPS1 ratings
GPS1: 32A max. rated current, 20 Hp @ 460V, 15 kW @ 400V, 3 poles p. 46
Terminal torque
GPS1: 2.0 Nm/18 lb. in.; GPS2: 4.0 Nm/36 lb. in. p. 46
Contact accessories
Front auxiliary contacts GPAC_ _FBA; side auxiliary contacts GPAC_ _LLA/GPAC_ _LRA; side alarm/auxiliary GPAD_ _ _ _LLA; side short circuit alarm GPAE11LLA p. 7
Handle operators
GPA_HA_ handle operators work GPS1BH_ _ and GPS2BH_ _ through a panel door; shaft depth 139.8-289.8 mm (GPS1BH) or 161-311 mm (GPS2BH) p. 10
GPS2 terminal covers
GPS2: GPAPTP2A terminal covers p. 10

What this sheet walks you through

  • Choosing the starter current range from motor full load current and service factor p. 5, 6
  • Wiring a starter for a single-phase motor p. 5
  • Applying starters in individual and group installations p. 3
  • Assembling combination starters with contactors, bases and links p. 4
  • Adding front and side mounted auxiliary and alarm contacts p. 7
  • Looking up short circuit ratings and maximum fuse and breaker sizes by product number p. 44
  • Picking contactor and link sizes for Type 2 coordination p. 45
  • Operating a starter through a panel door with an external handle p. 10

Good to know

  • In panels with multiple motor circuits, combination use needs a main disconnect in sight and within 50 feet. p. 4
  • The GPAE11LLA short circuit alarm may not be used with non-metallic enclosures, because of reset button interference. p. 7
  • Contactors used with the starters must not be applied above their nameplate HP/current ratings. p. 3
  • Maximum voltage for combination control is 277/480. p. 6
  • Single-phase use requires all three overload legs to be energized. p. 5

Questions this sheet answers

How do I wire a Surion manual motor starter for a single-phase motor?

Connect terminal T2 to L3 with a separate conductor, connect power to L1 and L2, and apply the load between T1 and T3. p. 5

What current setting do I use for a motor with a service factor under 1.15?

Multiply the normal full load current by .9; for a service factor of 1.15 or greater, use the motor full load current. p. 5

Can the GPS1BH and GPS2BH starters be used without upstream branch circuit protection?

As Type E combination starters at 277/480 and below, the catalog says they may control motors without additional upstream branch circuit protection, in motor circuits only. p. 4

What does the GPAE11LLA short circuit alarm accessory do?

It indicates that the starter tripped on a short circuit rather than an overload, and it includes a manual reset. p. 4

What current range does the GPS1 line cover?

0.1A to 32A, for motors up to 30hp at 600V; the GPS2 series extends the range to 63A. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Section 6: IEC Manual Motor Starters1
    1. Table of Contents......6-11
    2. Overview......6-22
    3. Selection Guide......6-55
    4. Accessories – Front Mounted......6-77
    5. Accessories – Side Mounted......6-77
    6. Accessories – Group Mounted......6-99
    7. Accessories – External Handle Operators......6-1010
    8. Accessories – Other......6-1010
    9. Accessories – Integrated Starter Components......6-1111
    10. Enclosures and Enclosure Accessories......6-1313
    11. Integrated with Contactor, Open, AC Operated Contactors, Standard Interruption Capacity......6-1515
    12. Integrated with Contactor, Open, DC Operated Contactors, Standard Interruption Capacity......6-1616
    13. Integrated with Contactor, Open, AC Operated Contactors, High Interruption Capacity......6-1717
    14. Integrated with Contactor, Open, DC Operated Contactors, High Interruption Capacity......6-1818
    15. Integrated with Contactor, Factory Installed Accessories......6-1919
    16. Enclosed, Non-metal Enclosures, Standard Interruption Capacity......6-2020
    17. Enclosed, Factory Installed Accessories......6-2121
    18. Enclosed, Metal Enclosures, High Interruption Capacity......6-2222
    19. Enclosed, Factory Installed Accessories......6-2323
    20. Integrated with Contactor, Enclosed, AC Operated Contactors, High Interruption Capacity......6-2424
    21. Integrated with Contactor, Enclosed, DC Operated Contactors, High Interruption Capacity......6-2626
    22. Integrated with Contactors, Factory Installed Accessories......6-2828
    23. Outline Drawings......6-3030
    24. Wiring Diagrams – Accessories......6-4242
    25. Short Circuit Current Rating, Rating Breaking Capacity......6-4444
    26. Type 2 Short Circuit Rating, Individual Group and Combination Starters......6-4545
    27. Specifications......6-4646
    28. Time Current Curves......6-4747

From the PDF’s own bookmarks.

The whole text · 5 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 4841-48

The file

Revision and size

RevisionRev. 4/16
PublisherGE
Pages48
PDF16 MB
TextText from the PDF itself.

The first pages · 4 of 48

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 48
Page 2
Page 2of 48
Page 3
Page 3of 48
Page 4
Page 4of 48

More documents · 1

For the same models