Page 21

IEC Manual Motor Starters

Section 6

Enclosed Factory Installed Accessories Enclosed Starter Accessories Product Number Structure Select product from table on page 6-20. Select starter and enclosure accessories from tables below. Product Number Digits 1 G

2 P

3 1

4 3

5 A

6 7 A A Starter Auxiliary Contacts and Alarms

8 A

9 A

10 1

11 B Pilot Lights

12 A Pilot Lights

Starter Auxiliary Contacts and Alarms Replace Digit 6 in product number with digit corresponding to appropriate accessory. Accessory Auxiliary Contact Alarm + (Auxiliary Contact) Alarm + (Auxiliary Contact)

Contacts 1NO-1NC 1NO + (1NO) 1NC + (1NO)

List Price Adder, GO-10A2A $27.00 $36.00 $36.00

Product No. Digit 6 P 1 3

Pilot Lights Leads unwired for field configuration. Replace Digits 11 & 12 in product number with digits corresponding to lens color and voltage. Lens Color Red Green Clear

110/220 RJ GJ TJ

Voltage (50/60Hz) 380/440 RU GU TU

220/240 RN GN TN

480/500 RX GX TX

List Price Adder, GO-10A2A $27.00 $27.00 $27.00

600 RY GY TY

Modification Example Motor FLA is 1.9 amps. Requirement is for a Type 1 enclosed starter for 1 HP at 460V modified with a 1NO-NC aux contact and a red pilot light also at 460V. Step 1. Enclosed Starter 2. 1NO-1NC Aux. Contact 3. Red Pilot Light (460V) 4. Final Product No. & List Price

1 G G G G

2 P P P P

3 1 1 1 1

4 3 3 3 3

5 G G G G

6 A P P P

Digit No. 7 A A A A

8 A A A A

9 A A A A

10 1 1 1 1

11 B B R R

12 A A X X

List Price GO-10A2A $155.00 $27.00 $27.00 $209.00

Product selection from table on page 6-20 Digit #6: Starter Auxiliary Contacts and Alarms Digits #11 and #12: Pilot Lights

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-21

Page 22

IEC Manual Motor Starters

Section 6

Enclosed Metal Enclosures High Interruption Capacity Product Number Selection Instructions Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3. 45 mm (Rotary Operator) Individual or Type E Combination1 Installation Manual Motor Starter Type GPS1BH_ _ FLA Adjustment Range 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 3 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 7 1/2 10 15 20

1/2 3/4 1 1/2 3 3 5 10 10 15 20 25

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 3 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 7 1/2 10 15 20

1/2 3/4 1 1/2 3 3 5 10 10 15 20 25

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

1/8 1/4 1/2 1/2 3/4 1 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

1/8 1/4 1/2 1/2 3/4 1 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

Enclosure Type

Product Number

List Price GO-10A2A

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP11AAAAA5BA GP11BAAAA5BA GP11CAAAA5BA GP11DAAAA5BA GP11EAAAA5BA GP11FAAAA5BA GP11GAAAA5BA GP11HAAAA5BA GP11JAAAA5BA GP11KAAAA5BA GP11LAAAA5BA GP11MAAAA5BA GP11NAAAA5BA GP11PAAAA5BA GP11RAAAA5BA GP11AAAAA7BA GP11BAAAA7BA GP11CAAAA7BA GP11DAAAA7BA GP11EAAAA7BA GP11FAAAA7BA GP11GAAAA7BA GP11HAAAA7BA GP11JAAAA7BA GP11KAAAA7BA GP11LAAAA7BA GP11MAAAA7BA GP11NAAAA7BA GP11PAAAA7BA GP11RAAAA7BA

$190.00 $190.00 $190.00 $190.00 $205.00 $205.00 $205.00 $205.00 $205.00 $205.00 $230.00 $230.00 $230.00 $245.00 $245.00 $295.00 $295.00 $295.00 $295.00 $310.00 $310.00 $310.00 $310.00 $310.00 $310.00 $335.00 $335.00 $335.00 $350.00 $350.00

55 mm (Rotary Operator) Individual or Type E Combination1 Installation Manual Motor Starter Type GPS2BH_ _ FLA Adjustment Range 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

Enclosure Type

Product Number

List Price GO-10A2A

1 2 3 5 7 1/2 10 10 15 15 1 2 3 5 7 1/2 10 10 15 15

1 1/2 3 5 5 7 1/2 10 10 15 20 1 1/2 3 5 5 7 1/2 10 10 15 20

3 5 10 10 15 20 25 30 40 3 5 10 10 15 20 25 30 40

5 7 1/2 10 15 20 25 25 40 50 5 7 1/2 10 15 20 25 25 40 50

1/4 1/2 1 1 1/2 2 2 3 3 5 1/4 1/2 1 1 1/2 2 2 3 3 5

1/2 1 1/2 2 3 3 5 5 7 1/2 10 1/2 1 1/2 2 3 3 5 5 7 1/2 10

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP12KAAAA5BA GP12LAAAA5BA GP12MAAAA5BA GP12NAAAA5BA GP12PAAAA5BA GP12RAAAA5BA GP12SAAAA5BA GP12TAAAA5BA GP12UAAAA5BA GP12KAAAA7BA GP12LAAAA7BA GP12MAAAA7BA GP12NAAAA7BA GP12PAAAA7BA GP12RAAAA7BA GP12SAAAA7BA GP12TAAAA7BA GP12UAAAA7BA

$390.00 $390.00 $390.00 $390.00 $390.00 $390.00 $420.00 $420.00 $447.00 $430.00 $430.00 $430.00 $430.00 $430.00 $430.00 $460.00 $460.00 $487.00

1For combination installation add short circuit alarm GPAE11LLA. For combination installation using GPS1BH - starters add GPAPT1E terminal protector. See page 6-10 for field installation kits. For factory modified starters select t-z for GPS2BH - starters or x-z for GPS1BH - starters on page 6-23. Maximum voltage for combination control is 277/480. Enclosed Motor Starters (Without Contactors), Metallic Enclosures, Rotary Operated (Black Operator), Individual, Non-combination or Type E Combination Installation.

6-22

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 23

IEC Manual Motor Starters

Section 6

Enclosed Factory Installed Accessories Modifications & Accessories for Enclosed Motor Starters, Metallic Enclosures, Rotary Operated To specify modifications to your enclosed starter, use the tables below to determine product number digit substitutions and list price adders. Enclosed Starter Modification Product Number Structure Select product from tables on page 6-22. Select starter, handle, or enclosure accessory from tables below. Product Number Digits 1 G

2 P

3 1

4 1

5 G

6 7 A A Starter Auxiliary Contacts and Alarms

8 A

9 A

10 11 7 B Enclosure Type/ Pilot Light Operator Handle Color

12 A Pilot Light

Starter Auxiliary Contacts, Short Circuit Alarm & Alarm Contact Replace Digit 6 in product number with digit corresponding to appropriate accessory. Accessories Aux. Contact Aux. Contact Alarm Contact Aux. Contact Short Circuit Alarm Aux. Contact + (Short Circuit Alarm) Aux. Contact + (Short Circuit Alarm) + [Alarm Contact] Short Circuit Alarm + Terminal Cover* Short Circuit Alarm + Terminal Cover* Short Circuit Alarm + Terminal Cover* Alarm + (Aux. Contact) Alarm + (Aux. Contact)

Contacts 1NO 1NC 1NO 1NO-1NC 1NO-1NC 1NO + (1NO-1NC) 1NO-1NC + (1N0-1NC) + [1NO] 1NO + 1NC 1NO + 1NC 1NO + 1NC 1NO + (1N0) 1NC + (1NO)

Product No. Digit 6 B C G P T U W X Y Z 1 3

Mounting Front Front Front Left Left Front (Left) Front (Left) [Front] Lateral Left Lateral Left Lateral Left Left Left

List Price Adder, GO-10A2A $18.00 $18.00 $21.00 $27.00 $20.00 $40.00 $61.00 $32.00 $32.00 $32.00 $36.00 $36.00

*for GPS1BH_ _ units only

Red/Yellow Rotary Operator Replace Digit 10 in product number with digit corresponding to enclosure type. Product No. Digit 10 6 8

Enclosure Type Type 11 Type 3R/12

List Price Adder, GO-10A2A $0.00 $0.00

1For use only with GPS2BH_ _ starters.

Pilot Lights Includes both red and green lenses for field installation. Replace Digits 11 & 12 in product number with digits corresponding to voltage. Product No. Digits 11 & 12 GC GJ GL GN GS GX GY

Voltage (60 Hz) 24 120 208 277 240 460 600

List Price Adder, GO-10A2A $96.00 $96.00 $96.00 $96.00 $96.00 $96.00 $96.00

Modification Example Motor FLA is 1.9 amps. Requirement is for a Type 1 enclosed starter for 1 HP at 460V modified with a 1NO-NC aux contact, a red/ yellow operator and a pilot light also at 460V. Step 1. Enclosed Starter 2. 1NO-1NC Aux. Contact 3. Red/Yellow Operator 4. Red Pilot Light (460V) 5. Final Product No. & List Price

1 G G G G G

2 P P P P P

3 1 1 1 1 1

4 1 1 1 1 1

5 G G G G G

6 A P P P P

Digit No. 7 A A A A A

8 A A A A A

9 A A A A A

10 7 7 8 8 8

11 B B B G G

12 A A A X X

List Price GO-10A2A $310.00 $27.00 $0.00 $96.00 $433.00

Product selection from table on page 6-22 Digit #6: Starter Auxiliary Contacts and Alarms Digit #10: Red/Yellow Rotary Operator/Enclosure Type Digit #11 and #12: Pilot Light

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-23

Page 24

IEC Manual Motor Starters

Section 6

Integrated with Contactor Enclosed, AC Operated Contactors High Interruption Capacity Product Number Selection Instructions Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3. Select product from tables. See pages 6-28 and 6-29 for starter, contactor or enclosure modifications. 45 mm (Rotary Operator) Individual, Non-Combination or Combination2 Installation Manual Motor Starter Type GPS1BH_ _ FLA Adjustment Range 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

1/4 1/2 3/4 1 2

1/3 1/2 3/4 1 1/2 3

1/2 3/4 1 2 3 5

1/2 3/4 1 1/2 3 5 7 1/2

1/8 1/4 1/2

1/10 1/6 1/3 1/2 1 1/2

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 25

1/8 1/4 1/2 1/2 1 1 1/2 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

1/4 1/2 3/4 1 2

1/3 1/2 3/4 1 1/2 3

1/2 3/4 1 2 3 5

1/2 3/4 1 1/2 3 5 7 1/2

1/8 1/4 1/2

1/10 1/6 1/3 1/2 1 1/2

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 25

1/8 1/4 1/2 1/2 1 1 1/2 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

Contactor Size

Contactor Max Amps

Enclosure Type

Product Number1

List Price GO-10A2A

MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL01 CL02 CL25 CL04 CL04 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL01 CL02 CL25 CL04 CL04

9 9 9 9 9 9 9 9 9 9 10 10 10 10 10 10 10 10 10 10 13.8 17.5 22 32 32 9 9 9 9 9 9 9 9 9 9 10 10 10 10 10 10 10 10 10 10 13.8 17.5 22 32 32

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP26AAM1*A1AA GP26BAM1*A1AA GP26CAM1*A1AA GP26DAM1*A1AA GP26EAM1*A1AA GP26FAM1*A1AA GP26GAM1*A1AA GP26HAM1*A1AA GP26JAM1*A1AA GP26KAM1*A1AA GP26AA00*A1AA GP26BA00*A1AA GP26CA00*A1AA GP26DA00*A1AA GP26EA00*A1AA GP26FA00*A1AA GP26GA00*A1AA GP26HA00*A1AA GP26JA00*A1AA GP26KA00*A1AA GP26LA01*A1AA GP26MA02*A1AA GP26NA25*A1AA3 GP26PA04*A1AA GP26RA04*A1AA GP26AAM1*A3AA GP26BAM1*A3AA GP26CAM1*A3AA GP26DAM1*A3AA GP26EAM1*A3AA GP26FAM1*A3AA GP26GAM1*A3AA GP26HAM1*A3AA GP26JAM1*A3AA GP26KAM1*A3AA GP26AA00*A3AA GP26BA00*A3AA GP26CA00*A3AA GP26DA00*A3AA GP26EA00*A3AA GP26FA00*A3AA GP26GA00*A3AA GP26HA00*A3AA GP26JA00*A3AA GP26KA00*A3AA GP26LA01*A3AA GP26MA02*A3AA GP26NA25*A3AA3 GP26PA04*A3AA GP26RA04*A3AA

$411.00 $411.00 $411.00 $411.00 $426.00 $426.00 $426.00 $426.00 $426.00 $426.00 $453.00 $453.00 $453.00 $453.00 $468.00 $468.00 $468.00 $468.00 $468.00 $468.00 $516.00 $531.00 $545.00 $589.00 $589.00 $456.00 $456.00 $456.00 $456.00 $471.00 $471.00 $471.00 $471.00 $471.00 $471.00 $498.00 $498.00 $498.00 $498.00 $513.00 $513.00 $513.00 $513.00 $513.00 $513.00 $561.00 $576.00 $590.00 $634.00 $634.00

1Complete product number by replacing asterisk (*) with appropriate coil digit from table below. 2For combination installation add short circuit alarm GPAE11LLA. For combination installation using GPS1BH - starters add GPAPT1E terminal protector. See page 6-10 for field installation kits. For factory modified starters select t-z for GPS2BH - starters or x-z for GPS1BH - starters on page 6-28. Maximum voltage for combination control is 277/480. 31NO aux contact front mounted.

Enclosed Assembled Motor Starters with AC Contactors, Rotary Operated (Black Operator), Individual Non-Combination or Combination Installation. Includes 1NO auxiliary contact integrated into MC* and CL* unless noted. Integrated contact is on left side of CL* contactors.

Replace asterisk (*) in product number with coil digit. Coil Selection 60Hz 50Hz Coil Digit* for MC Contactors Coil Digit* for CL Contactors

6-24

24, C, 24 24, 1

Control Catalog

120 110 J J

208, M L

240, - S

AC Voltage 240-277 277, 220-230 N, - N www.geindustrial.com, 380 U, 480 380/400, U, 415, W

480 415 W, 600 500 Y Y

Rev. 4/16 Prices and data subject to change without notice

Page 25

IEC Manual Motor Starters

Section 6

Integrated with Contactor Enclosed, AC Operated Contactors High Interruption Capacity

High Interruption Capacity (Rotary Operator), Metal Enclosure, Integrated with AC Contactor

55 mm (Rotary Operator) Individual, Non-Combination or Combination2 Installation Manual Motor Starter Type GPS2BH_ _ FLA Adjustment Range 11-16 14-20 19-25 24-32 28-40 35-50 45-63 11-16 14-20 19-25 24-32 28-40 35-50 45-63

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

Contactor Size

Contactor Max Amps

Enclosure Type

Product Number1

List Price GO-10A2A

3 5 7 1/2 10 10 15 15 3 5 7 1/2 10 10 15 15

5 5 7 1/2 10 10 15 20 5 5 7 1/2 10 10 15 20

10 10 15 20 25 30 40 10 10 15 20 25 30 40

10 15 20 25 25 40 50 10 15 20 25 25 40 50

1 1 1/2 2 2 3 3 5 1 1 1/2 2 2 3 3 5

2 3 3 5 5 7 1/2 10 2 3 3 5 5 7 1/2 10

CL04 CL04 CL04 CL04 CL45 CL06 CL07 CL04 CL04 CL04 CL04 CL45 CL06 CL07

32 32 32 32 34 48 62 32 32 32 32 34 48 62

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP22MA04*A1AA GP22NA04*A1AA GP22PA04*A1AA GP22RA04*A1AA GP22SA45*A1AA3 GP22TA06*A1AA4 GP22UA07*A1AA4 GP22MA04*A3AA GP22NA04*A3AA GP22PA04*A3AA GP22RA04*A3AA GP22SA45*A3AA3 GP22TA06*A3AA3 GP22UA07*A3AA3

$681.00 $681.00 $681.00 $681.00 $727.00 $776.00 $796.00 $726.00 $726.00 $726.00 $726.00 $772.00 $821.00 $888.00

1Complete product number by replacing asterisk (*) with appropriate coil digit from table below. 2For combination installation add short circuit alarm GPAE11LLA. For combination installation using GPS1BH - starters add GPAPT1E terminal protector. See page 6-10 for field installation kits. For factory modified starters select t-z for GPS2BH - starters or x-z for GPS1BH - starters on page 6-28. Maximum voltage for combination control is 277/480. 31NO aux contact front mounted. 41NO-1NC aux contact front mounted.

Enclosed Assembled Motor Starters with AC Contactors, Rotary Operated (Black Operator), Individual Non-Combination or Combination Installation Includes 1NO auxiliary contact integrated into MC* and CL* unless noted. Integrated contact is on left side of CL* contactors.

Replace asterisk (*) in product number with coil digit. Coil Selection 60Hz 50Hz Coil Digit* for MC Contactors Coil Digit* for CL Contactors

Rev. 4/16 Prices and data subject to change without notice

24, C, 24 24, 1 www.geindustrial.com

120 110 J J

208, M L

240, - S

AC Voltage 240-277 277, 220-230 N, - N, 380 U, 480 380/400, U

Control Catalog, 415, W

480 415 W, 600 500 Y Y

6-25

Page 26

IEC Manual Motor Starters

Section 6

Integrated with Contactor Enclosed, DC Operated Contactors High Interruption Capacity Product Number Selection Instructions Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3. Select product from tables. See pages 6-28 and 6-29 for starter, contactor or enclosure modifications. 45 mm (Rotary Operator) Individual, Non-Combination or Combination2 Installation Manual Motor Starter Type GPS1BH_ _ FLA Adjustment Range 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 0.1-0.16 0.16-.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4.0-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

1/4 1/2 3/4 1 2

1/3 1/2 3/4 1 1/2 3

1/2 3/4 1 2 3 5

1/2 3/4 1 1/2 3 5 5

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 25

1/4 1/2 3/4 1 2

1/3 1/2 3/4 1 1/2 3

1/2 3/4 1 2 3 5

1/2 3/4 1 1/2 3 5 5

1/4 1/2 3/4 1 2 3 3 5 7 1/2 10

1/3 1/2 3/4 1 1/2 3 3 5 5 7 1/2 10

1/2 3/4 1 2 3 5 7 1/2 10 10 15 20

1/2 3/4 1 1/2 3 5 7 1/2 10 10 15 20 25

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

1/8 1/4 1/2

1/10 1/6 1/3 1/2 1 1/2

1/8 1/4 1/2 1/2 1 1 1/2 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

1/8 1/4 1/2

1/10 1/6 1/3 1/2 1 1/2

1/8 1/4 1/2 1/2 1 1 1/2 1 1/2 2

1/10 1/6 1/3 1/2 1 1/2 2 2 3 3 5

Contactor Size

Contactor Max Amps

Enclosure Type

Product Number1

List Price GO-10A2A

MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL01 CL02 CL25 CL04 CL04 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 MC1 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL01 CL02 CL25 CL04 CL04

9 9 9 9 9 9 9 9 9 9 10 10 10 10 10 10 10 10 10 10 13.8 17.5 22 32 32 9 9 9 9 9 9 9 9 9 9 10 10 10 10 10 10 10 10 10 10 13.8 17.5 22 32 32

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP36AAM1#A1AA GP36BAM1#A1AA GP36CAM1#A1AA GP36DAM1#A1AA GP36EAM1#A1AA GP36FAM1#A1AA GP36GAM1#A1AA GP36HAM1#A1AA GP36JAM1#A1AA GP36KAM1#A1AA GP36AA00#A1AA GP36BA00#A1AA GP36CA00#A1AA GP36DA00#A1AA GP36EA00#A1AA GP36FA00#A1AA GP36GA00#A1AA GP36HA00#A1AA GP36JA00#A1AA GP36KA00#A1AA GP36LA01#A1AA GP36MA02#A1AA GP36NA25#A1AA3 GP36PA04#A1AA GP36RA04#A1AA GP36AAM1#A3AA GP36BAM1#A3AA GP36CAM1#A3AA GP36DAM1#A3AA GP36EAM1A3AA GP36FAM1#A3AA GP36GAM1#A3AA GP36HAM1#A3AA GP36JAM1#A3AA GP36KAM1#A3AA GP36AA00#A3AA GP36BA00#A3AA GP36CA00#A3AA GP36DA00#A3AA GP36EA00#A3AA GP36FA00#A3AA GP36GA00#A3AA GP36HA00#A3AA GP36JA00#A3AA GP36KA00#A3AA GP36LA01#A3AA GP36MA02#A3AA GP36NA25#A3AA3 GP36PA04#A3AA GP36RA04#A3AA

$421.00 $421.00 $421.00 $421.00 $436.00 $436.00 $436.00 $436.00 $436.00 $480.00 $480.00 $480.00 $480.00 $480.00 $495.00 $495.00 $495.00 $495.00 $495.00 $495.00 $544.00 $558.00 $577.00 $632.00 $632.00 $466.00 $466.00 $466.00 $466.00 $481.00 $481.00 $481.00 $481.00 $481.00 $525.00 $525.00 $525.00 $525.00 $525.00 $540.00 $540.00 $540.00 $540.00 $540.00 $540.00 $589.00 $603.00 $622.00 $677.00 $677.00

1Complete product number by replacing crosshatch (#) with appropriate coil digit from table below. 2For combination installation add short circuit alarm GPAE11LLA. For combination installation using GPS1BH - starters add GPAPT1E terminal protector. See page 6-10 for field installation kits. For factory modified starters select t-z for GPS2BH - starters or x-z for GPS1BH - starters on page 6-28. Maximum voltage for combination control is 277/480. 31NO aux contact front mounted.

Includes 1NO auxiliary contact integrated into MC* and CL* unless noted. Integrated contact is on left side on CL* contactors.

Replace crosshatch (#) in product number with coil digit. Coil Selection Coil Digit # for MC Contactors Coil Digit # for CL Contactors

6-26

12 B B

24 D D

Control Catalog

DC Voltage 48 G G

125 L K

250 S T www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 27

IEC Manual Motor Starters

Section 6

Integrated with Contactor Enclosed, DC Operated Contactors High Interruption Capacity

High Interruption Capacity (Rotary Operator), Metal Enclosure, Integrated with DC Contactor

55 mm (Rotary Operator) Individual, Non-Combination or Combination2 Installation Manual Motor Starter Type GPS2BH_ _ FLA Adjustment Range 11-16 14-20 19-25 24-32 28-40 11-16 14-20 19-25 24-32 28-40

Three Phase Horsepower @ 200V

Three Phase Horsepower @ 230V

Three Phase Horsepower @ 460V

Three Phase Horsepower @ 575V

Single Phase Horsepower @ 115V

Single Phase Horsepower @ 230V

Contactor Size

Contactor Max Amps

Enclosure Type

Product Number1

List Price GO-10A2A

3 5 7 1/2 10 10 3 5 7 1/2 10 10

5 5 7 1/2 10 10 5 5 7 1/2 10 10

10 10 15 20 25 10 10 15 20 25

10 15 20 25 25 10 15 20 25 25

1 1 1/2 2 2 3 1 1 1/2 2 2 3

2 3 3 5 5 2 3 3 5 5

CL04 CL04 CL04 CL04 CL45 CL04 CL04 CL04 CL04 CL45

32 32 32 32 34 32 32 32 32 34

Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 1) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12) Metal (Type 3R/12)

GP32MA04#A1AA GP32NA04#A1AA GP32PA04#A1AA GP32RA04#A1AA GP32SA45#A1AA3 GP32MA04#A3AA GP32NA04#A3AA GP32PA04#A3AA GP32RA04#A3AA GP32SA45#A3AA3

$724.00 $724.00 $724.00 $724.00 $811.00 $769.00 $769.00 $769.00 $769.00 $856.00

1Complete product number by replacing crosshatch (#) with appropriate coil digit from table below. 2For combination installation add short circuit alarm GPAE11LLA. For combination installation using GPS1BH - starters add GPAPT1E terminal protector. See page 6-10 for field installation kits. For factory modified starters select t-z for GPS2BH - starters or x-z for GPS1BH - starters on page 6-28. Maximum voltage for combination control is 277/480. 31NO aux contact front mounted.

Includes 1NO auxiliary contact integrated into MC* and CL* unless noted. Integrated contact is on left side on CL* contactors.

Replace crosshatch (#) in product number with coil digit. Coil Selection Coil Digit # for MC Contactors Coil Digit # for CL Contactors

Rev. 4/16 Prices and data subject to change without notice

12 B B

24 D D

DC Voltage 48 G G www.geindustrial.com

125 L K

250 S T

Control Catalog

6-27

Page 28

IEC Manual Motor Starters

Section 6

Integrated with Contactor Factory Installed Accessories Enclosed Assembled Starters, Metallic Enclosures, Rotary Operated To specify modifications to your enclosed starter, use the tables below to determine product number digit substitutions and list price adders. Enclosed Starter Modification Product Number Structure Select product from tables on pages 6-24 through 6-27. Select starter, contactor, or enclosure modifications from table below. Product Number Digits 1 G

2 P

3 2

4 6

5 G

6

7 0

8 0

9 * (Coil)

Starter Auxiliary Contact and Alarm

10 11 A Contactor Enclosure Type/ Auxiliary Contact Operator Handle and Surge Suppressor Color

12

13

CPT

Pilot Devices

Starter Auxiliary Contact and Alarm Replace product number Digit 6 with appropriate digit and add price adder to list price. Accessories Aux. Contact Aux. Contact Alarm Contact Aux. Contact Short Circuit Alarm Aux. Contact + (Short Circuit Alarm) Aux. Contact + (Short Circuit Alarm) + [Alarm Contact] Short Circuit Alarm + Terminal Cover Short Circuit Alarm + Terminal Cover Short Circuit Alarm + Terminal Cover Alarm + (Aux. Contact) Alarm + (Aux. Contact)

Contacts 1NO 1NC 1NO 1NO-1NC 1NO-1NC 1NO + (1NO-1NC) 1NO-1NC + (1NO-1NC) + [1NO]

Mounting Front Front Front Left Left Front (Left) Front (Left) [Front]

Product No. Digit 6 B C G P T U W

List Price Adder, GO-10A2A $18.00 $18.00 $21.00 $27.00 $20.00 $40.00 $61.00

1NO + 1NC 1NO + 1NC 1NO + 1NC 1NO + (1NO) 1NC + (1NO)

Lateral Left Lateral Left Lateral Left Left Left

X Y Z 1 3

$32.00 $32.00 $32.00 $36.00 $36.00

Replace asterisk (*) in product number with coil digit. Coil Selection – AC Voltage 60Hz 50Hz Coil Digit* for MC Contactors Coil Digit* for CL Contactors

24, C, 24 24, 1

120 110 J J

208, M L

240, - S

AC Voltage 240-277 277, 220-230 N, - N, 380 U, 480 380/400, U, 415, W

480 415 W, 600 500 Y Y

Coil Selection – DC Voltage Coil Digit * for MC Contactors Coil Digit * for CL Contactors

12 B B

DC Voltage 48 G G

24 D D

125 L K

250 S T

Contactor Auxiliary Contact and Surge Suppressor Replace product number Digit 10 with appropriate digit and add price adder to list price.

Product No. Digit 10 Product No. Digit 10 Additional Auxiliary Contacts and Coil Surge Suppressors Standard Coil Surge Suppressor1 Auxiliary Contact Auxiliary Contact + Coil Surge Suppressor1 Auxiliary Contact Auxiliary Contact + Coil Surge Suppressor1 Auxiliary Contact Auxiliary Contact + Coil Surge Suppressor1

Contacts, - 1NO 1NO 1NC 1NC 1NO-1NC 1NO-1NC

Mounting by Contactor Type CL MC, - - - Front Left Front Left Front Left Front Left Front Front Front Front

MC,CL00, CL01 CL02, CL04 A2 B C D E F G H

CL25, CL45 A3 B C D E F G5 H5

CL06, CL07 A4 B C D E F G H

List Price Adder, GO-10A2A $0.00 $27.00 $18.00 $45.00 $18.00 $45.00 $27.00 $54.00

1RC suppressor AC coil to 230V; diode suppressor for DC coil 2Includes internal 1NO holding interlock 3Includes 1NO front mounted auxiliary for holding interlock 4Includes 1NO front mounted auxiliary for holding interlock and 1NC auxiliary for general use 5Not available for CL25

6-28

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice

Page 29

IEC Manual Motor Starters

Section 6

Integrated with Contactor Factory Installed Accessories Enclosed Assembled Starters, Metallic Enclosures, Rotary Operated Red/Yellow Rotary Operator Replace Digit 11 in product number with digit corresponding to enclosure type. Oversize enclosure is required for CPT and reversing control or optional if more space is desired. Replace product number Digit 11 with appropriate digit and add price adder to list price. If selecting CPT (below), oversize enclosure is included and this modification is not required. See CPT table. Standard Enclosure List Price Adder, Product No. Digit 11 GO-10A2A 2 $0.00 4 $0.00

Enclosure Type Type 1 Type 3R/12

Oversize Enclosure Yellow/Red Operator – Product No. Digit 11 6 8

Black Operator – Product No. Digit 11 5 7

List Price Adder, GO-10A2A $70.00 $70.00

Control Power Transformer Includes oversized enclosure (required for CPT). Replace product number Digits 11 and 12 with appropriate digits and add price adder to list price. Voltage Primary 480/240V 208V 277V 575V 480/240V 208V 277V 575V

Secondary 120V 120V 120V 120V 24V 24V 24V 24V

Operator Color Black Black Black Black Black Black Black Black

50VA Product No. Digits 11 & 12 Type 1 Type 3R/12 5B 7B 5C 7C 5D 7D 5E 7E 5K 7K 5L 7L 5M 7M 5N 7N

List Price Adder, GO-10A2A $230.00 $230.00 $230.00 $230.00 $230.00 $230.00 $230.00 $230.00

150VA Product No. Digits 11 & 12 Type 1T Type 3R/12 5F 7F 5G 7G 5H 7H 5J 7J 5P 7P 5Q 7Q 5R 7R 5S 7S

List Price Adder, GO-10A2A $275.00 $275.00 $275.00 $275.00 $275.00 $275.00 $275.00 $275.00

For red/yellow operator, replace 5 with 6, or 7 with 8 in Digit 11 above.

Pilot Devices Replace product number Digit 13 with appropriate digit and add price adder to list price. Pilot Device START/STOP Push Button START/STOP Mushroom Head Push Button START/STOP Push Button with Red/Green ON Pilot Light1 START/STOP Push Button with Red/Green OFF Pilot Light thru Aux.1 ON/OFF Selector Switch ON/OFF Selector Switch with Red/Green ON Pilot Light1 ON/OFF Selector Switch with Red/Green OFF Pilot Light thru Aux.1 H-O-A Selector Switch H-O-A Selector Switch with Red/Green ON Pilot Light1 H-O-A Selector Switch with Red/Green OFF Pilot Light thru Aux.1 Red/Green OFF Pilot Light thru Aux.1 H-O-A Selector Switch with START Push Button

Product No. Digit 13 B C D E F G H J K L M N

List Price Adder, GO-10A2A $144.00 $144.00 $288.00 $315.00 $72.00 $216.00 $243.00 $72.00 $216.00 $243.00 $171.00 $144.00

1Pilot lights comes with both red and green lenses for field installation.

Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com

Control Catalog

6-29

Page 30

IEC Manual Motor Starters

Section 6

Outline Drawings Outlines and Dimensions mm (in.) For Estimating Only

Manual Motor Starter - GPS1BS_ (toggle)

Manual Motor Starter - GPS2BH_ (rotary)

Manual Motor Starter - GPS1BH_ (rotary)

6-30

Control Catalog www.geindustrial.com

Rev. 4/16 Prices and data subject to change without notice