The text of a spec sheet · part 5 of 5
Control Catalog, Section 6: IEC Manual Motor Starters, pages 41 to 48
Pages 41 to 48 of 48
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE GPS1BHAA, GE GPS2BHAP, Fanuc GPS1BHAA, GE Fanuc GPS1BHAA, Fanuc GPS2BHAP and GE Fanuc GPS2BHAP
Page 41
IEC Manual Motor Starters
Section 6
Outline Drawings Outlines and Dimensions mm (in.) For Estimating Only
Metal Enclosure for GPS1BH_/GPS2BH_ Reversing Combination Starter or Combination Starter with CPT, NEMA Type 1 (Drawing 55-216921)
Metal Enclosure for GPS1BH_/GPS2BH_ Reversing Combination Starter or Combination Starter with CPT, NEMA Type 3R/12 (Drawing 55-216922)
Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com
Control Catalog
6-41
Page 42
IEC Manual Motor Starters
Section 6
Wiring Diagrams – Accessories
6-42
GPAC_ _FBA Front Mount Auxiliary Contact
GPAC_ _LRA Side Mount Alarm/Auxiliary Contact
GPAC_ _FRA Front Mount Alarm Contact
GPAE11LLA Side Mount Short Circuit Alarm
GPAC_ _LLA Side Mount Auxiliary Contact
GPASLRA_ _Side Mount Shunt Trip
Control Catalog www.geindustrial.com
Rev. 4/16 Prices and data subject to change without notice
Page 43
IEC Manual Motor Starters
Section 6
Wiring Diagrams – Accessories
GPAULRAA_Side Mount Undervoltage Release
Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com
GPAU20L_AA_Side Mount Undervoltage Release with 2 NO early make contacts
Control Catalog
6-43
Page 44
IEC Manual Motor Starters
Section 6
Short Circuit Current Rating Rated Breaking Capacity Toggle Operation, Standard Interruption Product Number
FLA Adjustment Range kAIC @ 240V kAIC @ 480V kAIC @ 600V
Max. Fuse Size (A)
Max. C.B. Size (A)
kAIC @ 240VGroup Installation kAIC @ 480VGroup Installation kAIC @ 600VGroup Installation
GPS1BSAA GPS1BSAB GPS1BSAC GPS1BSAD GPS1BSAE GPS1BSAF GPS1BSAG GPS1BSAH GPS1BSAJ GPS1BSAK GPS1BSAL GPS1BSAM GPS1BSAN GPS1BSAP GPS1BSAR
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32
100 100 100 100 100 100 100 100 100 100 100 65 65 65 65
50 50 50 50 50 50 50 50 22 22 22 22 22 22 22
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0.75 1 1.5 2.5 4 6 10 16 25 40 50 60 80 100 125
15 15 15 15 15 15 15 15 25 40 50 60 80 100 125
100 100 100 100 100 100 100 100 100 100 100 65 65 65 65
65 65 65 65 65 65 65 65 65 65 65 50 50 50 50
25 25 25 25 25 25 25 25 25 25 25 18 18 18 10
Max Fuse or C.B.-Size (A) Minimum Group Installation Contactor Size 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 CL01 CL02 CL25 CL04
Manual motor starters are suitable for use with C-2000 contactors in series with the starter, but contactor rating must not be exceeded.
Rotary Operation, High Interruption Product Number
FLA Adjustment Range kAIC @ 240V kAIC @ 480V kAIC @ 600V
Max. Fuse Size (A)
Max. C.B. Size (A)
GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63
100 100 100 100 100 100 100 100 100 100 100 65 65 65 65 65 65 65 65 65 65 65 65 65
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0.75 1 1.5 2.5 4 6 10 16 25 40 50 60 80 100 125 40 50 60 80 100 125 150 200 250
15 15 15 15 15 15 15 15 25 40 50 60 80 100 125 40 50 60 80 100 125 150 200 250 kAIC @ 240V- kAIC @ 480VGroup Group Installation Installation 100 100 100 100 100 100 100 100 100 100 100 65 65 65 65 100 100 100 100 100 100 100 100 100
65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 35 kAIC @ 600VGroup Installation
Max Fuse or C.B. Size(A)-Group Installation kAIC @ 277Y/480VCombination Starter
Minimum Contactor Size
25 25 25 25 25 25 25 25 25 25 25 25 25 25 10 25 25 25 25 25 25 10 10 10
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 1500 1500 1500 1500 1500 1500 1500 1500 1500
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC0 CL00 or MC1 CL00 CL01 CL02 CL25 CL04 CL00 CL00 CL01 CL02 CL02 CL04 CL06 CL06 CL07
When using manual starters in combination with starter applications, use short circuit reset/indicator accessory. For GPS1BH_ starters add GPAPTIE terminal accessory. Maximum voltage for combination control is 277/480. Manual motor starters are suitable for use with C-2000 contactors in series with the starter; contactor rating must not be exceeded. When used in a combination installation, the contactor is not self-protected. Link available for GPS2* for CL04 and larger contactors only.
6-44
Control Catalog www.geindustrial.com
Rev. 4/16 Prices and data subject to change without notice
Page 45
IEC Manual Motor Starters
Section 6
Type 2 Short Circuit Rating Individual Group and Combination Starters Type 2 Coordination Under short circuit conditions, the starter must not result in danger to persons or the installation. After short circuit, the starter shall be capable of further use. No damage to the overload relay or other parts shall occur, except that welding of the contactor contacts is permitted when they are easily separated (as by a screwdriver) without significant deformation. Minimum front electrical clearance is 1” with CL06 and CL07 contactors, 0.8” with all other contactors. 100kA@240V UL508E Investigation (Individual Group or Combination)* Starter Type
FLA Adjustment Range
Product Number
Minimum Contactor Size @ 100kA @ 240V Interrupt Level
Link @ 100kA @ 240V Interrupt Level
GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63
GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU
CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL00 CL01 CL02 CL04 CL04 CL04 CL04 CL04 CL04 CL04 CL04 CL45 CL06 CL06 CL07
GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L04* GPF1L04* GPF1L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L45* GPF2L07* GPF2L07* GPF2L07*
50kA@380/400V per IEC947 (Individual Group or Combination)* Starter Type
FLA Adjustment Range
Product Number
Minimum Contactor Size @ 50kA @ 380/400V Interrupt Level
Link @ 50kA @ 380/400V Interrupt Level
GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63
GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU
CL00 CL00 CL00 LC00 CL00 CL00 CL01 CL01 CL02 CL25 CL25 CL25 CL25 CLL25 CL25 CL04 CL04 CL04 CL04 CL04 CL04 CL45 CL06 CL07
GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L04* GPF1L04* GPF1L04* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L45* GPF2L07* GPF2L07*
Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com
50kA@480V UL508E Investigation (Individual Group or Combination)* Starter Type
FLA Adjustment Range
Product Number
Minimum Contactor Size @ 50kA @ 480V Interrupt Level
Link @ 50kA @ 480V Interrupt Level
GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63
GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU
CL01 CL01 CL01 CL01 CL01 CL01 CL25 CL25 CL25 CL25 CL25 CL25 CL25 CL04 CL04 (35kA) CL04 CL04 CL04 CL04 CL04 CL45 CL06 CL06 CL07
GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L25* GPF1L04* GPF1L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L04* GPF2L45* GPF2L07* GPF2L07* GPF2L07*
25kA (or as noted) @600V UL508E Investigation (Individual Group or Combination)* Starter Type
FLA Adjustment Range
Product Number
Minimum Contactor Size @ 25kA @ 600V Interrupt Level
Link @ 25kA @ 600V Interrupt Level
GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS1 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2 GPS2
0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63 0.63-1.0 1-1.6 1.6-2.5 2.5-4 4-6.3 6.3-10 9-13 11-16 14-20 19-25 24-32 6.3-10 9-13 11-16 14-20 19-25 24-32 28-40 35-50 45-63
GPS1BHAA GPS1BHAB GPS1BHAC GPS1BHAD GPS1BHAE GPS1BHAF GPS1BHAG GPS1BHAH GPS1BHAJ GPS1BHAK GPS1BHAL GPS1BHAM GPS1BHAN GPS1BHAP GPS1BHAR GPS2BHAK GPS2BHAL GPS2BHAM GPS2BHAN GPS2BHAP GPS2BHAR GPS2BHAS GPS2BHAT GPS2BHAU
CL00 CL00 CL00 CL00 CL00 CL00 CL04 CL04 CL04 CL04 CL04 CL04 CL04 CL04 CL04 CL45 (5kA) CL45 (5kA) CL45 (5kA) CL45 (5kA) CL45 (5kA) CL45 (5kA) CL06 (10kA) CL06 (10kA) CL07 (10kA)
GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L02* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF1L04* GPF2L45* GPF2L45* GPF2L45* GPF2L45* GPF2L45* GPF2L45* GPF2L07* GPF2L07* GPF2L07*
*Maximum voltage for combination control 277/480. Minimum front electrical clearance is 1” with CL06 and CL07 contactors, and 0.8” with all other contactors.
Control Catalog
6-45
Page 46
IEC Manual Motor Starters
Section 6
Specifications Starters
Frontal Auxiliary Blocks GPS1
Protection Thermal and Magnetic Maximum Rated Current Imax 32A Maximum Rated Operational Current Ie 32A Maximum Rated HP @ 460V 20 Hp Maximum Rated kW @ 400V 15 kW Power Loss 0.16-25A: 7 W 32A: 8.5 W Width Height Depth
45 mm 90 mm 75 mm (GPS1BS*)/ 92.5 mm (GPS1BH*) No. of Poles 3 Operation Toggle (GPS1BS*)/ Rotary (GPS1BH*) Mounting Position Turning to Front 30° Mounting Position Turning to Back 90° Mounting Position Turning to Side 180° DIN Rail Mounting Yes Mounting Screws 2 M4 (#6 screws) with Optional Mounting Tab Operation Altitude Up to 2000 Meters (6500 Feet) Storage Temperature –40 to +80° C (–40 to 176° F) Operation Temperature
–20 to +60° C (–4 to 140° F)
Temperature Compensation
–20 to +60° C (–4 to 140° F)
Rated Insulation Voltage Ui 690V Rated Operation Voltage Ue 690V Rated Voltage UL, cUL 600V Rated Frequency 50/60 Rated Impulse Withstand Strength Uimp 8KV Utilization Category IEC 60947-4-1 AC3 Overload Trip Class IEC 60947-4-1 10 Number of Current Ranges 15 Magnetic Release Ie Max Setting 13X Shock Resistance to IEC60068-2-25 30 g (width 20 ms) Vibration Resist., 50-150 Hz (X,Y,Z axis) 5G Std DIN Rail Mtg Vib. Res., 50-150 Hz (X,Y,Z axis) 8G DIN Rail Vib. Clamps Protection Degree (per IEC529) IP20 Safe from Finger Touch
GPS2 Thermal and Magnetic 63A 63A 40 hp 30kW 6.3-32A: 11W 40-50A: 15W 63A: 17W 55 mm 120 mm 107.5 mm 3 Rotary 30° 90° 180° Yes Yes Up to 2000m (6500 ft) –40 to +80° C (–40 to 176° F) –20 to +60° C (–4 to 140° F) –20 to +60° C (–4 to 140° F) 690V 690V 600V 50/60 8KV AC3 10 9 13X 30 g (width 20 ms) Contact factory Contact factory IP20 Safe from Finger Touch 50,000 ops 25,000 ops 25
Mechanical Performance 100,000 ops (70,000 for 32 Amp) Electrical Performance 100,000 ops (70,000 for 32 Amp) Max. Operation per Hour 25 (Motor Start Up) Phase Failure Protection Yes Yes Trip Test Function Yes Yes Trip Indication Yes Yes Terminal Type Pozidrive 2/Slotted Comb. Pozidrive 2/Slotted Comb. Max. Size Wire 1 Conductor w/o End Sleeve, solid or stranded 1-10 mm2/18-8 AWG 1-25 mm2/18-2 AWG stranded 2 Conductor w/o End Sleeve, solid or stranded 1-6 mm2/18-10 AWG 1-25 mm2/18-4 AWG stranded 1 Conductor w/ End Sleeve, stranded 1-6 mm2 stranded 1-16 mm2 2 Conductor w/ End Sleeve, stranded 1-6 mm2 stranded 1-16 mm2 Torque 2.0 Nm/18 lb. in. 4.0 Nm/36 lb. in. Standards IEC 60947-1, 60947-2, 60947-4 Yes Yes Din VDE66OT 100/101/102 Yes Yes UL 508/CSA 22.2 Yes Yes Marking CE Yes Yes Approvals UL, cUL listed Yes Yes Shipping Approvals On Request On Request PTB Test On Request On Request
6-46
Control Catalog
UL Contact Rating per NEMA ICS3-125 Continuous Ampere Rating Rated Operation AC Voltage Ue Rated Operational AC Current Ie AC Utilization Category Rated Operation DC Voltage Ue Rated Operational DC Current Ie DC Utilization Category Terminal Type Max. Size Wire (75°C Cu wire only) 2 conductor Torque
B300, Q300 5 115V, 230V 1.5A AC15 48V, 110V, 220V 1.38A, 0.55A, 0.27A DC13 Pozidrive2/Slotted Comb. 0.5-2.5 mm2/18-14 AWG 0.8Nm/7 lb. in.
Frontal Mount with 1NO or 1NC Contact; Frontal Mount Alarm with 1NO or 1NC Contact.
Lateral Auxiliary Blocks UL Contact Rating per NEMA ICS3-125 Rated Operation AC Voltage Ue Rated Operational AC Current Ie AC Utilization Category Rated Operation DC Voltage Ue Rated Operational DC Current Ie DC Utilization Category Terminal Type Max. Size Wire (75°C Cu wire only) 2 conductor Torque Width
A600, P300 125V, 230V, 400V, 500V, 690V 4A, 4A, 2.2A, 0.5A, 0.6A AC15 48V, 110V, 220V 5A, 1.3A, 0.5A DC13 Pozidrive2/Slotted Comb. 0.5-2.5 mm2/18-14 AWG 0.8Nm/7 lb. in. Adds 9 mm
Lateral Mount Auxiliary with 2NO, 1NO+1NC or 2NC contacts; Lateral Mount Alarm/Auxiliary with 1NO+1NO, 1NO+1NC, 1NC+1NO, 1NC+1NC; Short Circuit Signal Contact 1NO+1NC (SPDT)
Shunt Trip Power Consumption Pick-up (va/watts) Power Consumption Tripping Voltage Max. Operation Supply Power Consumption Pick-Up Voltage Max. Size Wire (75°C Cu wire only) 2 conductor Torque Width
21/12 0.7-1.1 Ve 5 ms for DC coil 0.85 - 1.1 Ve 0.5-2.5 mm2/18-14 AWG 0.8Nm/7 lb. in. Adds 18 mm
Undervoltage Release Power Consumption Pick-up (va/watts) Power Consumption Holding (va/watts) Power Consumption Tripping Voltage Power Consumption Pick-Up Voltage Torque Max. Size Wire (75°C Cu wire only) 2 conductor Width www.geindustrial.com
21/12 8/1.2 0.35-0.7 Ve 0.85-1.1 Ve 0.8Nm/7 lb. in. 0.5-2.5 mm2/18-14 AWG Adds 18 mm
Rev. 4/16 Prices and data subject to change without notice
Page 47
IEC Manual Motor Starters
Section 6
Time Current Curves
GPS1
The thermal release trip current curve applies to cold state. For single phase and DC loads the three phase must be connected in series. The magnetic release is based on the rated current In, which is the maximum value of the setting range of the manual motor starter. If the current is set to a lower value, the tripping current is increased by a corresponding factor. The short circuit release is set at the factory to a value equivalent to 13 times the rated current of the manual motor starter.
Rev. 4/16 Prices and data subject to change without notice www.geindustrial.com
Control Catalog
6-47
Page 48
IEC Manual Motor Starters
Section 6
Time Current Curves
GPS2
The thermal release trip current curve applies to cold state. For single phase and DC loads the three phase must be connected in series. The magnetic release is based on the rated current In, which is the maximum value of the setting range of the manual motor starter. If the current is set to a lower value, the tripping current is increased by a corresponding factor. The short circuit release is set at the factory to a value equivalent to 13 times the rated current of the manual motor starter.
6-48
Control Catalog www.geindustrial.com
Rev. 4/16 Prices and data subject to change without notice