A single page (page 6-10) from the I/O Specifications and Wiring manual GEK-90842, covering the IC610MDL101 24 V dc sink input module with 8 circuits. It gives the module's electrical specifications, its typical references and a wiring diagram. Of the models the site files it under, only the IC610MDL101 is described.
- What it is
- 24 V dc sink input module, 8 discrete (ON/OFF) circuits p. 1
- Input power
- 24 V dc sensing power comes from the rack power supply; no external supply needed p. 1
- Typical inputs
- Limit switches, pushbuttons, selector switches and relay contacts p. 1
- Maximum voltage
- 36 V dc open circuit p. 1
- Input current
- 18 mA, input impedance 1.8 K ohms p. 1
- Response time
- 4 to 15 ms OFF to ON and ON to OFF p. 1
- Leakage and ON current
- Maximum OFF leakage 3 mA; minimum ON current 7 mA p. 1
- Circuit indicator
- On the field side p. 1
- Internal power
- 14 mA for each ON circuit at 24 V dc p. 1
- Typical references
- 040 to 047 p. 1
- Weight
- 120 g p. 1
- Source manual
- I/O Specifications and Wiring, GEK-90842, page 6-10 p. 1
What this manual walks you through
Good to know
- All 8 circuits are powered from the one rack supply source. p. 1
- The ON and OFF voltage levels are measured between common and the input terminal, across the input device. p. 1
Questions this manual answers
Does the IC610MDL101 need an external power supply?
No. The 24 V dc used to sense the inputs comes from the rack power supply. p. 1
How many inputs does the IC610MDL101 have?
8 circuits, each taking one discrete ON/OFF signal from a user device. p. 1
What is the response time of the IC610MDL101 input module?
4 to 15 ms from OFF to ON and from ON to OFF. p. 1
What can I connect to an IC610MDL101?
Limit switches, pushbuttons, selector switches and relay contacts are the typical input devices. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
6-10
I/O Specifications and Wiring GEK-90842
24 V dc Sink Input (8 Circuits) IC610MDL101 This module provides 8 circuits each designed to receive a single discrete (ON/OFF) signal from user supplied devices. Typical input devices include limit switches, pushbuttons, selector switches, and relay contacts. Power (24 V dc) to sense the state of these inputs is provided by the rack power supply. No external power source is required with this module. All 8 circuits are powered from this one source. Figure 6-8 provides wiring information for this module. Following are specifications for each of the 8 circuits:
t
of Input Points Maximum Voltage (Open Circuit) Input Current Input Impedance ON Level* OFF Level* OFF to ON Response ON to OFF Response Circuit Indicator Maximum OFF Leakage Minimum ON Current Internal Power Consumption
Units of Load Weight
8 36 V dc USER WIRING
18 niA 1.8 K ohms < 3 V dc > 3 V dc 4 to 15 ms 4 to 15 ms Field Side 3 mA 7mA 14 rnA for each ON Circuit @ 24 V dc 10 mA @ 9 V dc 1 @ 9 V dc 10 @ 24 V dc oz (120 g)
. SOUL,Pnc-S1-83-0034TYPICAL " REFERENCES
040 041 042 043 044 045 046 047
it INTERNAL
CONNECTION
- Voltage levels measured between common and input terninails (across input device). WIRING DIAGRAM
40 COMMONTO OTHER CIRCUITS24 VDCrINTERNAL POWER SUPPLYLED
INPUT OPTIC:L1161 COUPLER
SAMPLE INPUT CIRCUIT
Figure 6-8. Wiring for 24 V ac Sink Inputs