Manual · GE Fanuc
GE Fanuc GEK-90842 Page 6-10, IC610MDL101 24 V DC Sink Input Module
Manual1 pagePDF 117 KB
The page is below, with its text.
Covers · 3 models
The models it covers
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
A single page (6-10) from GE manual GEK-90842 with the specifications and wiring of the IC610MDL101 24 V dc sink input module, which has 8 circuits. It says which input devices the module takes, how it is powered, its input ratings and its wiring diagram (Figure 6-8). It lets the reader check the input ratings and wire switches or relay contacts to the module.
- Device type
- 24 V dc sink input module, 8 circuits for discrete (ON/OFF) signals p. 1
- Input power
- 24 V dc sensing power from the rack power supply; no external power source needed p. 1
- Input devices
- Limit switches, pushbuttons, selector switches and relay contacts p. 1
- Response time
- 4 to 15 ms, OFF to ON and ON to OFF p. 1
- Input impedance
- 1.8 K ohms p. 1
- Weight
- 120 g p. 1
What this manual walks you through
- Wiring 24 V dc sink inputs to the module p. 1
Good to know
- All 8 circuits are powered from the one rack power supply source. p. 1
Questions this manual answers
Does the IC610MDL101 need an external power supply?
No. The rack power supply provides the 24 V dc used to sense the inputs. p. 1
How many inputs does the IC610MDL101 have?
Eight circuits, each receiving a single discrete (ON/OFF) signal. p. 1
What is the response time of the IC610MDL101 inputs?
4 to 15 ms, both OFF to ON and ON to OFF. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
I/O Specifications and Wiring
6-10
GEK-90842
24 V dc Sink Input (8 Circuits) IC610MDLlOl This module provides 8 circuits each designed to receive a single discrete (ON/OFF) signal from user supplied devices. Typical input devices include limit switches, pushbuttons, selector switches, and relay contacts. Power (24 V dc) to sense the state of these inputs is provided by the rack power supply. No external power source is required with this module. All 8 circuits are powered from this one source. Figure 6-8 provides wiring information for this module. Following a~ specifications for each of the 8
- circuits
- 8
Input Points Maximum Voltage
36 V tic TYPICAL
(open Ci=uit) Input Current Inpat Impedance
USER
WIRING
18 nA 1.8 K ohms <3vdc >3V& 4 to 15 ms 4 to 15 ms Field Side
ON Level+ OFT Leve!P OFF to ON Response ON to OFF Response CircuB Indicator
Maximum OFF Leakage llainimum ON current IElterMl Power consumption
REFERENCESMODULE046 04: 0423mA 7mA043 044
14mAforcachON CiIwit@24Vdc lOmA@9Vdc 1@9Vdc lo@ 24 V & 4.2 02 (120 g)
Units of Load Weight045 046 _1
- Voltage levels measured between common and input termin& (across input device). WIRING
IIL-e---,.‘f .COUPLERSAMPLEINPUT CIRCUIT
Figure 6-8. Wiring for 24 V at Sink Inputs
DIAGRAM047INTERNAL CONNECTlOhi