Page 79

A.7 - PiC9011/9012 - CSM/CPU (Document 108-31046-00)

(This document is archived and available from Giddings & Lewis by requesting part number 108-31046-00.)

A.7 -1

Page 80

PiC9011/9012 - CSM/CPU (Document 108-31046-00)

NOTE

A.7 -2

Page 81

A.8 - PiC904X- CSM/CPU Central Service Module/Central Processing Unit Introduction

The PiC904X CSM/CPU module occupies the 1/2 slot in the rack. The CSM/CPU converts AC or DC power to regulated DC power. It supplies this power to the modules in the rack through the bus. The PiC904X CSM/CPU controls the system and executes the application program. Figure A8-1. PiC904X CSM/CPU Module

CSM/CPU

Name of module

SCAN/BAT/PWR/DIAG IN OUT IN OUT PROG/USER PORTS TX ACT

LEDs

ARCNET CONFIG IN OUT BLOCK I/O

Key slot

Run

PiC90™

Stop

GIDDINGS & LEWIS® Programmable industrial Controller

ON

Power switch OFF

L / LINE1 N / LINE2

Power connector

E / GRND

PiCPro

RS232 port connector (to computer workstation)

P-P and User Block I/O Port

Communications port for peer-to-peer or block I/O (optional) RS232 port connector (to user serial interface) Door

A.8 -1

Page 82

PiC904X- CSM/CPU Central Service Module/Central Processing Unit

Connections

The CSM/CPU module receives power through a 3-pin power connector. Figure A8-2 illustrates the connections as listed below. Module

AC Power Source 110VAC

L / LINE 1 to Hot

AC Power Source 220VAC

DC Power Source 24VDC

Line1

+24V

N / LINE 2 to Common

Line2

24V Common

E / GRND

Single Point Ground

Single Point Ground to Single Point Ground

Figure A8-2. Power to the System CSM/CPU Module

Power Source

ON OFF

110V AC 220V AC

24V DC

HOT Line 1 +24V DC COMMON Line 2 24V DC COMMON GROUND GROUND GROUND

L / LINE 1 N / LINE 2 E / GRND SPG

Serial Ports

The PiCPro Port (9-pin D connector) communicates with the workstation serial port and the User Port (10-pin screw terminal connector) communicates with an optional serial interface device. Figure A8-3. Pinouts for the Two RS232 Communications Ports

GRD 5 DTR (output) 4 Transmit Data (output) 3 Receive Data (input) 2 + 5 VDC (output) 1 (50 mA max.)

(50 mA max.) 9 (output) - 12 VDC 8 NC = Not Connected 7 (output) RTS 6 (output) + 12 VDC (50 mA max.)

PiCPro Port

1 2 3 4 5 6 7 8 9 10 User Port

- 12 VDC (50 mA max.) + 12 VDC (50 mA max.) + 5 VDC (50 mA max.) DTR = Data terminal ready RTS = Request to send NC = Not Connected CTS = Clear to send GRD = ground Receive data Transmit data

Outputs

Inputs Output AA27-1390

The PiCPro Port allows the PiC904X to communicate with the workstation. This port is used when downloading an application program from the workstation into RAM memory. It may also be used to exchange data between the workstation and the PiC904X system while the PiC904X system is running.

A.8 -2

Page 83

PiC904X- CSM/CPU Central Service Module/Central Processing Unit

The pinout for the PiCPro Port cable is shown below. PiCPro Cable Pinout 9-pin female 9-pin female (to PC) (to PiCPro Port)

3 to

RD

2

2 to

TD

3

5 to GND 5

NOTE: Other pins may be connected in the cable received from Giddings & Lewis, but only pins 2, 3, and 5 are used. The User Port is used to communicate with a touch-screen, a hand-held controller, or other serial interface device. Peer-to-Peer (ARCNET) and Block I/O Expansion (Optional)

Peer-to-peer and block I/O expansion are optional on the PiC904X. The PiC90s with this communication capability have a communications port with a 10-pin screw terminal connector to the left of the user port. (See Figure 7-1.) The top two pins are used for peer-to-peer communication connections using twisted pair wire*. The next four pins are used for block I/O expansion (up to 77 block modules) where the maximum distance between block modules is 200 feet using shielded twisted pair wire*. The 7th pin is a shield connection. When using shielded wire, connect the shields to it. *Use shielded cables when it is necessary to meet EMC standards. The recommended wire has 100Ω characteristic impedance. Figure A8-4. Pinout for ARCNET and Block I/O Expansion Port 1 2 3 4 5 6 7 8 9 10

+ -

Peer-to-peer twisted pair interface

Out + Out In + In Shield NC NC NC

Block I/O

Peer-to-Peer(ARCNET)/ Block I/O communications port

A.8 -3

Page 84

PiC904X- CSM/CPU Central Service Module/Central Processing Unit

CAUTION The network is polarity dependent. In peer-to-peer communications, always connect the positive (+) of the twisted pair interface of the first PiC to the positive (+) of the twisted pair interface of the second PiC and the negative (-) to the negative (-), etc. In block I/O expansion systems, connect the positive (+) of the twisted pair out of the CPU module to the positive (+) of the twisted pair in on the next block I/O module and the negative (-) to the negative (-), etc. Connect the positive (+) of the twisted pair in of the CPU module to the positive (+) of the twisted pair out on the next block I/O module and the negative (-) to the negative (-), etc. See Appendix N1 Peer-to-Peer Communication Connections for information on connecting PiCs on a network. See Appendix N2 I/O Expansion Connections for more information on block I/O expansion.

A.8 -4

Page 85

PiC904X- CSM/CPU Central Service Module/Central Processing Unit

LEDs

There are 11 LEDs on the PiC904X CSM/CPU as shown in Figure A8-5 below. This section describes these LEDs. Figure A8-5. LEDs SCAN/BAT/PWR/DIAG IN OUT IN OUT PROG/USER PORTS TX ACT ARCNET CONFIG IN OUT BLOCK I/O

Status LEDs

The CSM/CPU module has four LEDs to indicate status as shown in the top row in Figure A8-5 above. They are described below. NOTE: During normal operation the DIAG and BATT LEDs should be off, and the PWR and SCAN LEDs should be on. Scan (SCAN)

ON

The processor is executing the application program.

OFF

Scan is lost and there is an orderly shut down procedure followed.

Battery (BAT) ON

Goes on briefly while the battery is checked at power-on.

OFF

Battery passed power up test.

Flashing Replace lithium battery. See replacement procedure that follows. Power (PWR)

ON

Power is on to the system. It indicates that the +5V supply is within tolerance. See the specification sheet.

OFF

No power to the system

Diagnostic (DIAG)

ON

On briefly during startup diagnostics. If it remains ON, module has failed startup diagnostics.

OFF

Normal operation

Flashing Flashes error codes under certain conditions.

These codes are listed in Appendix M.

A.8 -5

Page 86

PiC904X- CSM/CPU Central Service Module/Central Processing Unit

Communication LEDs

There are seven communication LEDs shown in Figure A8-5: two for RS232 communication, two for ARCNET communication, and three for Block I/O communication. They are described below. PiCPro Programming Port Data In (IN)

ON

Data being received at programming port

OFF

No data being received at programming port

PiCPro Programming Port Data Out (OUT)

ON

Data being transmitted from programming port

OFF

No data being transmitted from programming port

RS232 User Port Data In (IN)

ON

Data being received at user port

OFF

No data being received at user port

RS232 User Port Data Out (OUT)

ON

Data being transmitted from user port

OFF

No data being transmitted from user port

ARCNET Transmit Status (TX)

ON

Normal network activity

OFF

Not active part of network

Blinking

Network reconfiguration

ARCNET Active Status (ACT)

Flash/ON

Data being transferred to/from ARCNET interface

OFF

No data transfer

BLOCK I/O Module Configuration (CONFIG)

ON

Communication established with block I/O modules

OFF

Communication not established with block I/O modules

BLOCK I/O Data In (IN)

ON

Indicates the CPU is receiving data from block I/O modules

OFF

Indicates the CPU is not receiving data from block I/O modules

BLOCK I/O Data Out (OUT)

ON

Indicates the CPU is transmitting data to block I/O modules

OFF

Indicates the CPU is not transmitting data to block I/O modules

A.8 -6