The text of a manual · part 28 of 60
PiC900 Hardware Manual: C.11 - Input Switch Module (16 switches)
Pages 229 to 234 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 229
C.11 - Input Switch Module (16 switches) Introduction
The input switch module converts the position status of 16 on/off switches mounted on the face plate into logic levels that the CPU can use. The on/off position status of each switch is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. 16 LEDs in the upper section of the module indicate the logic state of each switch input. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C11-1. INPUT switch module (16)
INPUT
24V DC
Name of module Diagnostic LED
DIAG
1 5
Indicator LEDs
9 13
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
Face mounted switches
Door
ON/OFF ON/OFF
Theory of Operation
The switch module contains the same circuitry as the input 24VDC module. In addition, it has an internal 5V to 15VDC converter. This 15VDC source is electrically isolated from the logic and is routed to each face mounted switch. Each
C.11 -1
Page 230
Input Switch Module (16 switches)
switch can then supply either 15VDC (on) or 0V (off) to an optically isolated input. The switch’s on/off state is converted to a corresponding logic 1 or 0. This logic state is transmittted through the system bus to the CPU module where the processor uses it as data in the ladder program. An LED in the upper section of the module indicates the logic state of each input. Specification Table Characteristic
Input switch (16) module specifications
Function
Monitors on/off states from up to 16 face mounted switches
Part number
502-03651-00
Field side connector
25-pin card edge connector, face plate, switches
Protection of logic circuits
Optical isolation between the logic and field sides
Indicator lights, input circuits
An LED indicates the logic state of each switch
Indicator light, module
The DIAG LED goes OFF when the module passes power-on diagnostic tests
Logic side power requirements (typical)
2 mA @ +5V 11mA per energized input @ +5V
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
C.11 -2
Page 231
Input Switch Module (16 switches)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm.
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.11 -3
Page 232
Input Switch Module (16 switches)
C.11 -4
Page 233
Appendix D - Servo/Feedback Modules