The text of a manual · part 27 of 60
PiC900 Hardware Manual: C.10 - 24V DC Input/Output Source Module (16/8 points)
Pages 215 to 228 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 215
C.10 - 24V DC Input/Output Source Module (16/8 points) Introduction
The input section of the 24V DC I/O module converts DC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU. An "on" signal is nominally 24 VDC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 16 LEDs on the module indicate the logic state of each input. The output section of the module sources voltage for eight individual loads from one or two DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. Eight LEDs indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostics tests are running. Figure C10-1. 24V DC input/output module (16/8 source PT)
IN/OUT 24 V DC
Name of module Diagnostic LED
DIAG
INPUT 1 5 9
Input LEDs
13 OUTPUT FB
Fuse Blown LED
1
Output LEDs
5
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AG10-0493
C.10 -1
Page 216
24V DC Input/Output Source Module (16/8 points)
Connections
Inputs
A screw terminal connector is provided for each output and for each external power supply connection. The inputs are isolated in two groups of eight, with one additional terminal per group for the DC source/sink connection. The devices connected to terminals in the same group have a common DC supply and are wired in the same configuration, sink or source. Outputs
A screw terminal connection is provided for each output and for each external power supply connection. The outputs are isolated in two groups of four with two additional terminals per group for the DC HOT (DCL) and COMMON (DC COMMON). See Figure C10-4. Two terminals are provided for DC common. There is one common for each group of four outputs. Two terminals are provided for the DC supply input. The "fuse blown" LED circuit is active for any group that has a power supply connected. The DC power supply for each group of four devices may be different if required. In most cases one power supply is daisy-chained to both groups.
IMPORTANT Do not connect the DC HOT (DCL) and COMMON (DCCOMMON) to a group unless you plan to use one or more of its outputs. The external DC supplies that power the input and output signals should have a wire connected from their 0V (COMMON) terminal directly to the single-point ground used for the system rack. Their power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in the Hardware chapter, a 24 VDC supply is set up according to these guidelines.
C.10 -2
Page 217
24V DC Input/Output Source Module (16/8 points)
Figure C10-2 shows the screw terminal connections for the module. Figure C10-2. Screw Terminal Connector Assignments SCREW TERMINALS CONNECTIONS
DCIN1
CONNECTIONS 1 (Not Used) DCIN2
DCIN3
3 DCIN4
DCIN5
5 DCIN6
DCIN7
7
DCSS1
9
DCIN9
11
DCIN11
13
DCIN13
15
DCIN15
17
DCSS2
19
DCIN8
(Not Used) DCIN10 DCIN12 DCIN14 DCIN16
21
(Not Used)
23
(Not Used)
25
(Not Used)
(Not Used)
(Not Used) (Not Used) DCL 1
DC COMMON 1 27 Source Out 1
Source Out 2
29 Source Out 3
Source Out 4
31 DC COMMON 2
DCL 2
33
Source Out 6
35
Source Out 8
37
Source Out 5
Source Out 7
(Not Used)
39
(Not Used)
AG02-0393
C.10 -3
Page 218
24V DC Input/Output Source Module (16/8 points)
Figure C10-3 illustrates two groups of inputs using the same power supply. Each group can work independently of the other; one group may be sink and the other source. The DC power supply for each group may be different if required. Typically just one DC power supply is used, daisy-chained from one group to the next. The first group of eight inputs is shown with devices "sinking" current through the module. The HOT (V+) terminal of the power supply must be connected to the module at DCSS1. The second group of eight inputs are shown with devices "sourcing" current through the input module. The COMMON (0V) terminal of the power supply must be connected to the module at DCSS2. In this example the DC power supply is the same for both group. Figure C10-3. Connectors for Two Groups of Inputs SWITCHING DEVICE DC Supply 0V
NAMES FOR TERMINALS
DCIN1
V+
DCIN2
SCREW TERMINALS 1 3
DCIN3 DCIN4 DCIN5
5
DCIN6 DCIN7
7
HOT
DCIN8 DCSS1
9
HOT
DCIN9
COMMON
DCIN10
SINK
11 13
DCIN11 DCIN12
15
DCIN13
COMMON
SOURCE
DCIN14 DCIN15
17
DCIN16
19
DCSS2 AA59-3290
C.10 -4
Page 219
24V DC Input/Output Source Module (16/8 points)
Connections for one group of outputs are illustrated in Figure C10-4. Figure C10-4. Connections for One Group of Outputs
SCREW TERMINALS
LOADS DC Supply V+ 0V
DCCOMMON HOT
27
DCL Source Out 1
29
Source Out 2 Source Out 3 COMMON
31
Source Out 4
AG14-0493
Theory of Operation
Inputs
Each input is guaranteed "on" at 14 to 30 VDC and guaranteed "off" at 0 to 5 VDC. This is polarity independent. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED indicates the logic state of each input. Each group is represented by a horizontal row of 4 LEDs. If you need to know whether voltage is present at the field side, use a voltmeter on the terminal screws. The shaded blocks in Figure C10-5 show the limits specified by the IEC. The lines show the maximum and minimum V/I of the inputs in this module. The voltage/ current curve in this graph shows that the input module is well within the IEC Type 1 limits.
C.10 -5
Page 220
24V DC Input/Output Source Module (16/8 points)
Figure C10-5. Input Characteristics Compared to IEC Standards U IN VOLTS
MIN MAX
UHMAX 30 "ON" REGION
INPUT VOLTAGE
25 UNOM 24
20
UHMIN 15
(UTMAX )
TRANSITION REGION
10
ULMAX 5
(UTMIN )
0
"OFF" REGION
-5 .5 ITMIN
2 IH MIN
4
6
8
10
INPUT CURRENT
C.10 -6
12
14
15 I IN mAMPS IMAX AA40-0690
Page 221
24V DC Input/Output Source Module (16/8 points)
IMPORTANT Switching devices can sometimes have a leakage current that exceeds the ITmin (current allowed when off) of an input module. In order to use such a device, an impedance (typically, a resistor) needs to be used in parallel with the input. For example, some of the newer proximity switches use two wires instead of three. The third wire was used for a power or ground line. Without the third wire, the switch is easier to install. However, it requires more leakage current in the off state to power its internal circuitry. As a conservative estimate, use the following formula to calculate an external resistance value. It keeps the input voltage at or below 2.4V when the switching device is in the "off" state. 2.4V --------------------------------------------------------------- ≥ R Switch Leakage – 0.75mA If the switch leakage specification is ≤ 1.7 mA, then: 2.4V -------------------------------- ≥ 2.5KΩ 1.7 – 0.75mA Use a resistor less than or equal to 2.5 K Ω. Be sure that the wattage is adequate for the resistor when the switching device is in the "on" state remembering that: 2
V P = -----R
Outputs
Each output point is a solid state switch rated at .75 A. It is turned on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the device is powered. If the CPU sends a logic 0, the switch opens and power to the device is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. The four LEDs representing a group are in a horizontal row on the module. There are two rows for the two groups. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. In addition, each output is protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. C.10 -7
Page 222
24V DC Input/Output Source Module (16/8 points)
Protecting from an Inductive Load
Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the DCOUT fused supply. When an output is energized, represented on the left in Figure C10-6 by a closed switch, current passes through the load into the common line. When the output is de-energized, represented on the right in C10-6 by an open switch, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. Each output in the Output 24V DC module has a diode through which reverse current can be safely routed. Figure C10-6 shows how the internal diode works with an inductive load. When the output is turned off the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts. The internal diode provides another path for current. This limits the peak reverse voltage across the load to less than 1 V. You can connect an inductive load to any of the output source terminals. Figure C10-6. Diagram of Internal Protection for Inductive Loads (Outputs 1 to 8)
DC power supply 0V
IN/OUT MODULE
V+
DC power supply 0V V+
IN/OUT MODULE
DCL
DCL
DCCOMMON
INDUCTIVE LOAD
-
+ Source Out a) Output energized
DCCOMMON
Output switching device
+
INDUCTIVE LOAD
Output switching device
Source Out b) Output de-energized AG15-0493
Replacing a fuse
This module has two fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module lights up. The fuse is in series with the HOT line to the group to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table. C.10 -8
Page 223
24V DC Input/Output Source Module (16/8 points)
Follow the procedure below to change a blown fuse. 1.
Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.
2.
Press down the latch at the top of the module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.
3.
Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover. Figure C10-7. Positions of Fuses
DIAG LED LEDs for the outputs "Fuse blown" LED LEDs for the outputs
Fuse for the first group of outputs Screw terminal connector
Fuse for the second group of outputs 64 pin connector to rack Spare fuse
AA836-0493
4.
Identify the fuse that has blown, and use an insulated screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.
5.
Replace the module cover, making sure that the top and bottom tabs are fully engaged.
C.10 -9
Page 224
24V DC Input/Output Source Module (16/8 points)
C.10 -10
6.
Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.
7.
Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and the FB LEDs should both be off.
Page 225
24V DC Input/Output Source Module (16/8 points)
Specification Table
Characteristic
Input/Output module specifications
Function
Monitors on/off states from up to 16 DC voltage inputs Sources an external DC source to 8 loads
Part number
502-03842-02
Field side connector
40-pin card edge connector, screw terminals
Logic side power requirements (typi- 30mA@ +5V cal) 7 mA per energized input @ +5V 23 mA per energized output @ +5V for outputs Field side power dissipation worst case (at 32 VDC)
3.6 W for inputs 6.4 W for outputs
Indicator lights, input/output circuits An LED indicates the logic state of each input/output Indicator light, module
The DIAG LED goes OFF when the module passes power-on diagnostic tests
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
C.10 -11
Page 226
24V DC Input/Output Source Module (16/8 points)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
Input section(16 pt)
Input signals
UH Max (max. allowed voltage)
Nominal 24 VDC on, 0 VDC off, conforming to IEC Type 1 inputs per IEC 1131-2 (two groups of eight inputs) 30 VDC
IH Max (max. current @ 30 VDC)
7.5 mA
UL Min
Polarity independent
Guaranteed on
14 VDC
IH Min (min. current @ UH Min) 2.8 mA Guaranteed off
5 VDC
IT Min (current allowed when off)
.75 mA
C.10 -12
Page 227
24V DC Input/Output Source Module (16/8 points)
Time delay on
1 ms max.
Time delay off
1 ms max.
Protection of logic circuits
Optical isolation between the logic and field sides, 4000 V peak
Output section (8 pt source)
DC source requirements
Nominal 24V DC; range 5 to 32 VDC
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of outputs
Two groups of four solid-state switches. UL 508 spacing
Fuse per group of 8 switches
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; each switch is rated at .75 A continuous
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maximum ON
1.8 VDC @ .4 A
Surge current, maximum
2.5 A for 40 msec., every 2 seconds
Response to scan loss (present)
All outputs are reset to the OFF state
C.10 -13
Page 228
24V DC Input/Output Source Module (16/8 points)
C.10 -14