C.9 - 24V DC Input/Output Sink Module (16/8 points) Introduction
The input section of the 24V DC I/O module converts DC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU. An "on" signal is nominally 24 VDC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 16 LEDs indicate the logic state of each input. The output section of the module sinks voltage for eight individual loads from one DC power supply. The external supply is nominally 24 volts, but can be between 5 and 32 volts. Eight LEDs on the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in the active circuit is open or missing. The DIAG LED goes on briefly while the diagnostics tests are running. Figure C9-1. 24V DC Input/Output Module (16/8 sink pt)
IN/OUT 24 V DC
Name of module Diagnostic LED
DIAG
INPUT 1 5 9
Input LEDs
13 OUTPUT FB
Fuse Blown LED
1
Output LEDs
5
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AG10-0493
C.9 -1
Page 202
24V DC Input/Output Sink Module (16/8 points)
Connections
Inputs
A screw terminal connector is provided for each input and for each external power supply connection. The inputs are isolated in two groups of eight, with one additional terminal per group for the DC source/sink connection. The devices connected to terminals in the same group have a common DC supply and are wired in the same configuration, sink or source. Outputs
A screw terminal connection is provided for each output. The outputs are isolated in one group of eight with one additional terminal (DCOUT) for the DC fused supply (DCL HOT). See Figure C9-3. One terminal is provided for DC common and one terminal is provided for the DC supply input. The DC supply input is a fused circuit and returns to a terminal for field use. The "fuse blown" LED circuit is active when a power supply is connected. Figure C9-2 shows the internal fuse circuitry. Figure C9-2. Internal Module Connections for Outputs
Output section of module DCCOMMON DCL (HOT)
27 28
Blown Fuse Detector
DCSINK1 Common
DCSINK2
Loads DCSINK8 39
DCOUT
AG12-0493
C.9 -2
Page 203
24V DC Input/Output Sink Module (16/8 points)
IMPORTANT Do not connect the DC HOT (DCL) and COMMON (DCCOMMON) to the group unless you plan to use one or more of its outputs. The external DC supplies that power the input and output signals should have a wire connected from their 0V (COMMON) terminal directly to the single-point ground used for the system rack. Their power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in the Hardware chapter, a 24 VDC supply is set up according to these guidelines. Figure C9.3 shows all the screw terminal connections.
C.9 -3
Page 204
24V DC Input/Output Sink Module (16/8 points)
Figure C9-3. Screw Terminal Connector Assignments SCREW TERMINALS CONNECTIONS
CONNECTIONS
DCIN1
1 (Not Used)
DCIN3
3
DCIN5
5
DCIN2
DCIN4 DCIN6 DCIN7
7
DCSS1
9
DCIN9
11
DCIN11
13
DCIN13
15
DCIN15
17
DCSS2
19
DCIN8
(Not Used) DCIN10 DCIN12 DCIN14 DCIN16
21
(Not Used)
23
(Not Used)
25
(Not Used)
(Not Used)
(Not Used) (Not Used)
COMMON 27
DCL Sink Out 1 Sink Out 2
29 Sink Out 3
Sink Out 4
(Not Used)
31 33 (Not Used) Sink Out 5
Sink Out 6
35
Sink Out 8
37
Sink Out 7
DCOUT (Not Used)
39 AG01-0393
C.9 -4
Page 205
24V DC Input/Output Sink Module (16/8 points)
Figure C9-4 illustrates two groups of inputs using the same power supply. Each group can work independently of the other; one group may be sink and the other source. The DC power supply for each group may be different if required. Typically just one DC power supply is used, daisy-chained from one group to the next. The first group of eight inputs is shown with devices "sinking" current through the module. The HOT (V+) terminal of the power supply must be connected to the module at DCSS1. The second group of eight inputs are shown with devices "sourcing" current through the module. The COMMON (0V) terminal of the power supply must be connected to the module at DCSS2. In this example the DC power supply is the same for both groups. Figure C9-4. Connectors for Two Groups of Inputs SWITCHING DEVICE DC Supply 0V
NAMES FOR TERMINALS
DCIN1
V+
DCIN2
SCREW TERMINALS 1 3
DCIN3 DCIN4 DCIN5
5
DCIN6 DCIN7
7
HOT
DCIN8 DCSS1
9
HOT
DCIN9
COMMON
DCIN10
SINK
11 13
DCIN11 DCIN12
15
DCIN13
COMMON
SOURCE
DCIN14 DCIN15
17
DCIN16
19
DCSS2 AA59-3290
Connections for one group of outputs are illustrated in Figure C9-5.
C.9 -5
Page 206
24V DC Input/Output Sink Module (16/8 points)
Figure C9-5. Connections for One Group of Outputs
CONNECTIONS DC 0V Supply V+
SCREW TERMINALS
DCCOMMON HOT
27
DCL DCSINK1
28
29
DCSINK2 DCSINK3
30
31
DCSINK4
32 LOADS
DCSINK5
35
DCSINK6 DCSINK7
36
37
DCSINK8 DCOUT1
38
39
Theory of Operation
Inputs
Each input is guaranteed "on" at 14 to 30 VDC and guaranteed "off" at 0 to 5 VDC. This is polarity independent. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED on the module indicates the logic state of each input. Each group is represented by a horizontal row of four LEDs. If you need to know whether voltage is present at the field side, use a voltmeter on the terminal screws. The shaded blocks in Figure C9-6 show the limits specified by the IEC. The lines show the maximum and minimum V/I of the inputs in this module. The voltage/ current curve in this graph shows that the input module is well within the IEC Type 1 limits.
C.9 -6
Page 207
24V DC Input/Output Sink Module (16/8 points)
Figure C9-6. Input Characteristics Compared to IEC Standards
U IN VOLTS
MIN MAX
UHMAX 30 "ON" REGION
INPUT VOLTAGE
25 UNOM 24
20
UHMIN 15
(UTMAX )
TRANSITION REGION
10
ULMAX 5
(UTMIN )
0
"OFF" REGION
-5 .5 ITMIN
2 IH MIN
4
6
8
10
INPUT CURRENT
12
14
15 I IN mAMPS IMAX AA40-0690
C.9 -7
Page 208
24V DC Input/Output Sink Module (16/8 points)
IMPORTANT Switching devices can sometimes have a leakage current that exceeds the ITmin (current allowed when off) of an input module. In order to use such a device, an impedance (typically, a resistor) needs to be used in parallel with the input. For example, some of the newer proximity switches use two wires instead of three. The third wire was used for a power or ground line. Without the third wire, the switch is easier to install. However, it requires more leakage current in the off state to power its internal circuitry. As a conservative estimate, use the following formula to calculate an external resistance value. It keeps the input voltage at or below 2.4V when the switching device is in the "off" state. 2.4V --------------------------------------------------------------- ≥ R Switch Leakage – 0.75mA If the switch leakage specification is ≤ 1.7 mA, then: 2.4V -------------------------------- ≥ 2.5KΩ 1.7 – 0.75mA Use a resistor less than or equal to 2.5 K Ω. Be sure that the wattage is adequate for the resistor when the switching device is in the "on" state remembering that: 2
V P = -----R
Outputs
Each output point is a solid state switch rated at .4 A. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the load is provided a path to common. If the CPU sends a logic 0, the switch opens and power to the load is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. A fuse in series with the source protects against current overload in case the outputs are shorted to ground.
C.9 -8
Page 209
24V DC Input/Output Sink Module (16/8 points)
Protecting from an Inductive Load
The outputs should be used for non-inductive loads such as resistive or electronic loads. Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the DCOUT fused supply. When an output is energized, current passes through the load into the common line. When the output is de-energized, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. When the output is turned off, the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts.
IMPORTANT If inductive loads need to be connected to the outputs, an external diode must be connected between the load and DCOUT as shown in Figure C9-7 below. Figure C9-7. Connecting an External Diode DC power supply V+
IN/OUT MODULE
0V DCCOMMON
DCL
DCOUT INDUCTIVE LOAD
-
Output switching device
+ SINK OUT 1 AG13-0493
C.9 -9
Page 210
24V DC Input/Output Sink Module (16/8 points)
Replacing a Fuse
This module has one fuse for the outputs. The fuse is checked only when external power is applied. If power is applied and the fuse is blown or missing, the FB LED on the module lights up. The fuse is in series with the HOT line to the group to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table. Follow the procedure below to change a blown fuse. 1.
Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.
2.
Press down the latch at the top of the module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.
3.
Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover. Figure C9-8. Positions of Fuses
DIAG LED LEDs for the inputs "Fuse blown" LED LEDs for the outputs
Fuse for the outputs
Screw terminal connector
64 pin connector to rack Spare fuse
AA836-0493
C.9 -10
Page 211
24V DC Input/Output Sink Module (16/8 points)
4.
Use an insulated screwdriver or fuse puller to remove the fuse. Put a new fuse in the slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.
5.
Replace the module cover, making sure that the top and bottom tabs are fully engaged.
6.
Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.
7.
Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and FB LEDs should both be off.
C.9 -11
Page 212
24V DC Input/Output Sink Module (16/8 points)
Specification Table Characteristic
Module specifications
Function
Monitors on/off states from up to 16 DC voltage inputs Sinks an external DC source to eight loads
Part number
502-03843-02
Field side connector
40-pin card edge connector, screw terminals
Logic side power requirements (typical)
30 mA @ 7 mA per energized input @ 25 mA per energized output @
Field side power dissipation (worst case at 32V DC)
3.6 W for inputs 4.0 W for outputs
5V +5V +5V
Indicator lights, input/output circuits An LED for each input/output Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to the eight outputs when a fuse is missing or open
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed C.9 -12
File No. E126417 NRAQ Programmable Controllers
Page 213
24V DC Input/Output Sink Module (16/8 points)
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Input section(16 pt)
Input signals
Nominal 24 VDC on, 0 VDC off, conforming to IEC Type 1 inputs per IEC 1131-2 (two groups of eight inputs)
UH Max (max. allowed voltage)
30 VDC
IH Max (max. current @ 30 VDC)
7.5 mA
UL Min
Polarity independent
Guaranteed on
14 VDC
IH Min (min. current @ UH Min)
2.8 mA
Guaranteed off
5 VDC
IT Min (current allowed when off)
.75 mA
Time delay on
1 ms max.
Time delay off
1 ms max.
Protection of logic circuits
Optical isolation between the logic and field sides 4000 V peak
Output section (8 pt sink) DC source requirements
Nominal 24V DC; range 5 to 32 VDC
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of outputs
One group of 8 solid-state switches. UL 508 spacing
Fuse per group of 8 switches
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; each switch is rated at .4 A continuous
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maximum ON
1.8 VDC @ .4 A
Surge current, maximum
2.5 A for 40 msec., every 2 seconds
Response to scan loss (present)
All outputs are reset to the OFF state
C.9 -13
Page 214
24V DC Input/Output Sink Module (16/8 points)
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.9 -14