C.8 - Input 12V DC Module (32 points) Introduction
The input 12V DC module converts DC signals from 32 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 12 VDC, but can be any level between 10 and 14 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 32 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running. Figure C8-1. INPUT 12V DC Module (32 PT)
INPUT
12 V DC
Name of module Diagnostic LED
DIAG
1 5 9
Indicator LEDs
13 17 21 25 29
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AA1111-2392
C.8 -1
Page 196
Input 12V DC Module (32 points)
Connections
A screw terminal connector is provided for each output and for each external power supply connection. The inputs are isolated in four groups of eight, with one additional terminal per group for the DC source/sink connection. The devices connected to terminals in the same group have a common DC supply and are wired in the same configuration, sink or source. The external 12 VDC supply that powers the input signals should have a wire connected from its 0V (COMMON) terminal directly to the single-point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in the Hardware chapter, a 24 VDC supply is set up according to these guidelines. Set up the 12 VDC supply in the same manner.
C.8 -2
Page 197
Input 12V DC Module (32 points)
Figure C8-2. Screw Terminal Connector Assignments
MNEMONIC
SCREW TERMINALS
FUNCTION
LED
1 DCIN1 DCIN2
3
DCIN3 DCIN4
5
DCIN5 DCIN6
#1 #2 #3
DC input 3 DC input 4 DC input 5
#4 #5
7
DC input 6 DC input 7
9
DC input 8 DC sink/source, group 1
DCIN7 DCIN8
DC input 1 DC input 2
DCSS1
#6 #7 #8
11 DCIN9 DCIN10
13
DCIN11 DCIN12
15
DCIN13 DCIN14
17
DCIN15 DCIN16
19
DCSS2
DC input 9 DC input 10
#9 # 10 # 11
DC input 11 DC input 12 DC input 13
# 12 # 13 # 14 # 15
DC input 14 DC input 15 DC input 16 # 16 DC sink/source, group 2
21 DCIN17 DCIN18
23
DCIN19 DCIN20
25
DCIN21 DCIN22
27
DCIN23 DCIN24
29
DCSS3
DC input 17 DC input 18 DC input 19 DC input 20 DC input 21 DC input 22 DC input 23 DC input 24 DC sink/source, group 3
# 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24
31 DCIN25 DCIN26
33
DCIN27 DCIN28
35
DCIN29 DCIN30
37
DCIN31 DCIN32 DCSS4
39
DC input 25 DC input 26 DC input 27 DC input 28 DC input 29 DC input 30
# 25 # 26 # 27 # 28 # 29
# 30 # 31 DC input 31 # 32 DC input 32 DC sink/source, group 4 AA44-3290
C.8 -3
Page 198
Input 12V DC Module (32 points)
Figure C8-3 illustrates two groups of inputs using the same power supply. Each group can work independently of the others; some groups may be sink and others source. The DC power supply for each group may be different if required. Typically just one DC power supply is used, daisy-chained from one group to the next. The first group of eight inputs is shown with devices "sinking" current through the DC Input module. The HOT terminal of the power supply must be connected to the module at DCSS1. The second group of eight inputs are shown with devices "sourcing" current through the input module. The COMMON terminal of the power supply must be connected to the module at DCSS2. In this example the DC power supply is the same for both groups. Figure C8-3. Connectors for Two Groups of Inputs
SWITCHING DEVICE DC Supply 0V
NAMES FOR TERMINALS
DCIN1
V+
SCREW TERMINALS 1
DCIN2 DCIN3 DCIN4 DCIN5
3
DCIN6 DCIN7
7
HOT
DCIN8 DCSS1
9
HOT
DCIN9
COMMON
DCIN10 DCIN11 DCIN12 DCIN13 DCIN14 DCIN15 DCIN16 COMMON
5
SINK
11 13 15
SOURCE 17 19
DCSS2 AA59-3290
C.8 -4
Page 199
Input 12V DC Module (32 points)
Theory of Operation
Each input is guaranteed "on" at 10 to 14 VDC and guaranteed "off" at 0 to 5 VDC; polarity doesn't matter. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module, where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED in the upper section of the module indicates the logic state of each input. Each group is represented by a horizontal row of 4 LEDs. If you need to know whether voltage is present at the field side, use a voltmeter on the terminal screws. Specification Table
Characteristic
Input 12V DC (32 pt) module specifications
Function
Monitors on/off states from up to 32 DC voltage inputs
Part number
502-03643-00
Field side connector
40-pin card edge connector, screw terminals
Input signals
Nominal 12 VDC on, 0 VDC off conforming to IEC 1131-2 (four groups of eight inputs)
Maximum allowed voltage
14 VDC
Maximum current @ 14 VDC
8.5 mA
Guaranteed on
10 VDC
Minimum current @ 10 VDC
5 mA
Guaranteed off
5 VDC
Current allowed when off
2 mA
Time delay on
1 ms max.
Time delay off
1 ms max.
Protection of logic circuits
Optical isolation between the logic and field sides, 4000 V peak
Indicator lights, input circuits
An LED indicates the logic state of each input
Indicator light, module
The DIAG LED goes OFF when the module passes power-on diagnostic tests
Logic side power requirements (typi- 29 mA @ +5V cal) 7 mA per energized input @ +5V Field side power dissipation, worst case
3.8 W
C.8 -5
Page 200
Input 12V DC Module (32 points)
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.8 -6