Page 187
C.7 - Input/Output TTL (24/8 pts) Introduction
The TTL (Transistor-Transistor Logic) module provides 24 optically isolated input points and 8 optically isolated output points to interface with TTL devices (or other 5 VDC devices such as photoelectric sensors). The module can also be used as a feedback module to read devices like linear displacement transducers (TEMPOSONICS™, BALLUFF) or absolute encoders. These devices provide high speed, low voltage, low noise parallel digital signals.
An external +5V DC is required for operation. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C7-1. TTL (24 inputs/8 outputs)
Name of module
TTL
Diagnostic LED
DIAG
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AA1123-3792
C.7 -1
Page 188
Input/Output TTL (24/8 pts)
Connections
A screw terminal connection is provided for each input and output point and for the external power supply connection as shown in Figure C7-2. The external power supply that powers the I/O circuitry should have a wire connected from its 0V (common) terminal to the rack’s single point ground. The power disconnect switch should be the same one used for the CSM (Central Service Module). In the power distribution diagrams in Chapter 1, a DC supply is shown set up according to these guidelines.
C.7 -2
Page 189
Input/Output TTL (24/8 pts)
Figure C7-2. Screw Terminal Connection Assignments SCREW TERMINALS CONNECTIONS
CONNECTIONS TTL input 1
TTL input 2
1
TTL input 4
3
TTL input 6
5
TTL input 8
7
TTL input 10
9
TTL input 12
11
TTL input 14
13
TTL input 16
15
TTL input 18
17
TTL input 20
19
TTL input 22
21
TTL input 24
23
TTL input 3
TTL input 5
TTL input 7
TTL input 9
TTL input 11
TTL input 13
TTL input 15
TTL input 17
TTL input 19
TTL input 21
TTL input 23
25 (Not Used) COMMON
+5V supply input
27 29
(Not Used)
TTL output 2
(Not Used)
(Not Used) TTL output 1
31 TTL output 3
TTL output 4
33
TTL output 6
35
TTL output 8
37
TTL output 5
TTL output 7
39
(Not Used)
(Not Used)
AA1124-3792
C.7 -3
Page 190
Input/Output TTL (24/8 pts)
A typical input is shown in Figure C7-3. A 10K Ω pull-up resistor allows the inputs to be compatible with both totem pole and open collector output devices. Figure C7-3. Connections for TTL Input 24
TTL Input 24
10K Ω
TTL Module
23 24
100 Ω
25
External DC Power Supply
Optical Isolation
26 +5V
+5V
Common
27 28
0V SPG
AA1126-3792
An output connection is shown in Figure C7-4. Figure C7-4. Connections for TTL Output 1
TTL Module
27 28 30 Optical Isolation
32
+5V
+5V
Common
0V
29 31
56 Ω
External DC Power Supply
SPG TTL Output 1
AA1125-3792
The TTL inputs can also be connected to the digital outputs of a feedback device. These digital outputs must be of the totem pole or open collector variety and must meet the requirements listed in the specification table.
C.7 -4
Page 191
Input/Output TTL (24/8 pts)
The digital outputs of the feedback device are usually weighted from the least significant bit (LSB) to the most significant bit (MSB). Always connect the LSB to the TTL input 1. Continue to connect the remaining bits in order of significance until all available bits from the feedback device are connected. Figure C7-5 illustrates how a feedback device with 10 bits (29) of parallel data is connected to the TTL module. Figure C7-5. Connections for Digital Inputs from Feedback Device CONNECTIONS
TTL Module
1 2 3 4 5 6 7 8 9 10
TTL input 1 TTL input 2 TTL input 3 TTL input 4 TTL input 5 TTL input 6 TTL input 7 TTL input 8 TTL input 9 TTL input 10
LSB
20 1 2 2 2 23 4 2 5 2 6 2 7 2 8 2 MSB 9 2
Feed back Device
AA1127-3792
Some manufacturers of feedback devices provide a data valid signal in addition to the parallel output data. This signal is used to indicate when the parallel data is available for reading. The signal may be defined in one of two ways as shown in Figure C7-6. Figure C7-6. Valid Data
Data valid
Data valid (Outputs not changing)
(Outputs changing)
(Outputs not changing)
Data invalid
OR Data invalid Data valid (Outputs not changing)
(Outputs changing)
Data valid (Outputs not changing) AA1128-3792
This valid data signal is always connected to TTL input 24. The method of indicating valid data is defined in the servo setup software.
C.7 -5
Page 192
Input/Output TTL (24/8 pts)
Theory of Operation
The input circuitry of the TTL I/O module converts TTL level signals into logic levels that the CPU can use. A TTL device is at one of two defined voltage levels at any given moment. The voltage level corresponds to one of two defined logic levels: 1 or 0. A logic 1 (also “true” or “on”) signal is a voltage level between 2 volts and the power supply voltage (nominally 5 volts). A logic 0 (also “false” or “off”) signal is any level below 0.8 volts. These levels are compatible with TTL, LSTTL, ASTTL, and ALSTTL families.
C.7 -6
Page 193
Input/Output TTL (24/8 pts)
Specification Table Characteristics
TTL module specifications
Function
Monitors on/off states of 24 TTL inputs and controls on/off state of 8 TTL outputs.
Part number
502-03810-03
Field side connector
40 pin card edge connector, screw terminals
External power supply
+5 V ±5% 450 mA
Isolation
2500 VRMS between field side and logic side
Input characteristics
Vin high2.0 V minimum Vin low 0.8 V maximum Iin high 1µA maximum Iin low - -0.65 mA maximum Minimum input pulse width1 µsec
Output characteristics
Vol -0.8 V maximum @ Io = 10 mA (sinking) Voh -4.0 V minimum @ Io = -10 mA (sourcing) Output turn on/off time - 300 nano sec Maximum cable length - 3 meters (approximately 10 feet)
Logic side power requirements (typical)
+5V @ 450 mA
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
C.7 -7
Page 194
Input/Output TTL (24/8 pts)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.7 -8