PiC900 Hardware Manual: C.7 - Input/Output TTL (24/8 pts)

Pages 187 to 194 of 508, from PiC900 Hardware Manual

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 187

C.7 - Input/Output TTL (24/8 pts) Introduction

The TTL (Transistor-Transistor Logic) module provides 24 optically isolated input points and 8 optically isolated output points to interface with TTL devices (or other 5 VDC devices such as photoelectric sensors). The module can also be used as a feedback module to read devices like linear displacement transducers (TEMPOSONICS™, BALLUFF) or absolute encoders. These devices provide high speed, low voltage, low noise parallel digital signals.

An external +5V DC is required for operation. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C7-1. TTL (24 inputs/8 outputs)

Name of module

TTL

Diagnostic LED

DIAG

1 3 5 7 9 11 13

Screw terminal connector

15 17 19 21 23 25 27 29 31 33 35 37 39

Door

AA1123-3792

C.7 -1

Page 188

Input/Output TTL (24/8 pts)

Connections

A screw terminal connection is provided for each input and output point and for the external power supply connection as shown in Figure C7-2. The external power supply that powers the I/O circuitry should have a wire connected from its 0V (common) terminal to the rack’s single point ground. The power disconnect switch should be the same one used for the CSM (Central Service Module). In the power distribution diagrams in Chapter 1, a DC supply is shown set up according to these guidelines.

C.7 -2

Page 189

Input/Output TTL (24/8 pts)

Figure C7-2. Screw Terminal Connection Assignments SCREW TERMINALS CONNECTIONS

CONNECTIONS TTL input 1

TTL input 2

1

TTL input 4

3

TTL input 6

5

TTL input 8

7

TTL input 10

9

TTL input 12

11

TTL input 14

13

TTL input 16

15

TTL input 18

17

TTL input 20

19

TTL input 22

21

TTL input 24

23

TTL input 3

TTL input 5

TTL input 7

TTL input 9

TTL input 11

TTL input 13

TTL input 15

TTL input 17

TTL input 19

TTL input 21

TTL input 23

25 (Not Used) COMMON

+5V supply input

27 29

(Not Used)

TTL output 2

(Not Used)

(Not Used) TTL output 1

31 TTL output 3

TTL output 4

33

TTL output 6

35

TTL output 8

37

TTL output 5

TTL output 7

39

(Not Used)

(Not Used)

AA1124-3792

C.7 -3

Page 190

Input/Output TTL (24/8 pts)

A typical input is shown in Figure C7-3. A 10K Ω pull-up resistor allows the inputs to be compatible with both totem pole and open collector output devices. Figure C7-3. Connections for TTL Input 24

TTL Input 24

10K Ω

TTL Module

23 24

100 Ω

25

External DC Power Supply

Optical Isolation

26 +5V

+5V

Common

27 28

0V SPG

AA1126-3792

An output connection is shown in Figure C7-4. Figure C7-4. Connections for TTL Output 1

TTL Module

27 28 30 Optical Isolation

32

+5V

+5V

Common

0V

29 31

56 Ω

External DC Power Supply

SPG TTL Output 1

AA1125-3792

The TTL inputs can also be connected to the digital outputs of a feedback device. These digital outputs must be of the totem pole or open collector variety and must meet the requirements listed in the specification table.

C.7 -4

Page 191

Input/Output TTL (24/8 pts)

The digital outputs of the feedback device are usually weighted from the least significant bit (LSB) to the most significant bit (MSB). Always connect the LSB to the TTL input 1. Continue to connect the remaining bits in order of significance until all available bits from the feedback device are connected. Figure C7-5 illustrates how a feedback device with 10 bits (29) of parallel data is connected to the TTL module. Figure C7-5. Connections for Digital Inputs from Feedback Device CONNECTIONS

TTL Module

1 2 3 4 5 6 7 8 9 10

TTL input 1 TTL input 2 TTL input 3 TTL input 4 TTL input 5 TTL input 6 TTL input 7 TTL input 8 TTL input 9 TTL input 10

LSB

20 1 2 2 2 23 4 2 5 2 6 2 7 2 8 2 MSB 9 2

Feed back Device

AA1127-3792

Some manufacturers of feedback devices provide a data valid signal in addition to the parallel output data. This signal is used to indicate when the parallel data is available for reading. The signal may be defined in one of two ways as shown in Figure C7-6. Figure C7-6. Valid Data

Data valid

Data valid (Outputs not changing)

(Outputs changing)

(Outputs not changing)

Data invalid

OR Data invalid Data valid (Outputs not changing)

(Outputs changing)

Data valid (Outputs not changing) AA1128-3792

This valid data signal is always connected to TTL input 24. The method of indicating valid data is defined in the servo setup software.

C.7 -5

Page 192

Input/Output TTL (24/8 pts)

Theory of Operation

The input circuitry of the TTL I/O module converts TTL level signals into logic levels that the CPU can use. A TTL device is at one of two defined voltage levels at any given moment. The voltage level corresponds to one of two defined logic levels: 1 or 0. A logic 1 (also “true” or “on”) signal is a voltage level between 2 volts and the power supply voltage (nominally 5 volts). A logic 0 (also “false” or “off”) signal is any level below 0.8 volts. These levels are compatible with TTL, LSTTL, ASTTL, and ALSTTL families.

C.7 -6

Page 193

Input/Output TTL (24/8 pts)

Specification Table Characteristics

TTL module specifications

Function

Monitors on/off states of 24 TTL inputs and controls on/off state of 8 TTL outputs.

Part number

502-03810-03

Field side connector

40 pin card edge connector, screw terminals

External power supply

+5 V ±5% 450 mA

Isolation

2500 VRMS between field side and logic side

Input characteristics

Vin high2.0 V minimum Vin low 0.8 V maximum Iin high 1µA maximum Iin low - -0.65 mA maximum Minimum input pulse width1 µsec

Output characteristics

Vol -0.8 V maximum @ Io = 10 mA (sinking) Voh -4.0 V minimum @ Io = -10 mA (sourcing) Output turn on/off time - 300 nano sec Maximum cable length - 3 meters (approximately 10 feet)

Logic side power requirements (typical)

+5V @ 450 mA

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

C.7 -7

Page 194

Input/Output TTL (24/8 pts)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.7 -8