The text of a manual · part 23 of 60
PiC900 Hardware Manual: C.6 - Output Relay Module (8 points)
Pages 181 to 186 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 181
C.6 - Output Relay Module (8 points) Introduction
The relay output module can switch eight relay contacts. Four relays are normally open(NO)/normally closed(NC) form C type and four are normally open (NO) form A type. Eight LEDs in the upper section of the module indicate the logic state that drives each relay. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C6-1. OUTPUT Relay Module (8 PT) OUTPUT RELAY
Name of module Diagnostic LED
DIAG 1 2 3 4
Indicator LEDs
5 6 7 8
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25
Door
AA1064-4491
C.6 -1
Page 182
Output Relay Module (8 points)
Connections
A screw terminal connection is provided for each side of the contact. The form C type has three connections; normally open (NO), normally closed (NC), and the common terminal (CT). Only two of the connections can be wired at any time. The common terminal connection must be wired with either the normally open or the normally closed connection depending on the application. The form A type has two connections; one for each side of the contact. Figure C6-2. Screw Terminal Connector Assignments
CONNECTION
CT 1
NOT USED
CT 2
NOT USED
CT 3
SCREW TERMINALS
CONNECTION
1
NO 1
3
NC 1
5
NO 2
7
NC 2
9
NO 3
11
NC 3
13
NO 4
15
NC 4
17
NO 5
19
NO 6
21
NO 7
23
NO 8
25
NOT
2
4
6
8
10
12 NOT USED
CT 4
NOT USED
14
16 18
NO 5
NO 6
NO 7
NO 8
20
22
24
AA1068-4491
C.6 -2
Page 183
Output Relay Module (8 points)
If the normally open contact of the form C type is required for the application, wire as shown in Figure C6.3. Figure C6-3. Connections for Form C Normally Open Relay Module
1
CT1 3
Power Supply AC or DC
NO 1 Load
NC (not connected)
Common SPG AA1069-4491
If the normally closed contact of the form C type is required for the application, wire as shown in Figure C6-4. Figure C6-4. Connections for Form C Normally Closed Relay Module
1
NO 1 (not connected)
Power Supply AC or DC
CT 1 3
NC 1
Load
Common
SPG
AA1070-4491
To wire the normally open contact of form A, refer to Figure C6-5.
C.6 -3
Page 184
Output Relay Module (8 points)
Figure C6-5. Connections for Form A Normally Open Relay Module
23 24
Power Supply AC or DC
NO 8 NO 8
Load
Common
SPG AA1071-4491
Theory of Operation
A relay is composed of a coil and a set of contacts. When current is passed through the coil, the relay is energized. When no current flows through the coil, the relay is de-energized. The contacts close or open depending on the state of the coil. When the contacts are closed, current can pass through them. When the contacts are open, no current passes. There are three configurations for contacts referred to as form A, B and C as illustrated in Figure C6-6. The relay output module has form A and form C available. Normally Open Form A
Coil
Normally open contact
Figure C6-6. Relay Forms A, B, and C Normally Closed Normally Open/Normally Closed Form B Form C
Coil
Normally open contact
Normally closed contact Coil
Common
AA1065-4491 AA1066-4491
Normally closed contact AA1067-4491
A relay is energized or de-energized according to the logic state sent to it by the CPU. If the CPU sends a logic 1, the relay is energized. If the CPU sends a logic 0, the relay is de-energized. The logic state for each relay is updated every time the CPU scans the program. The names of the two types of contacts - normally open and normally closed reflect the state of the contacts when the coil is de-energized.
C.6 -4
Page 185
Output Relay Module (8 points)
For example, a normally open contact will not pass current when the coil is deenergized. If the coil is energized, the contacts close and current will pass. The normally closed contact will pass current when the coil is de-energized. If the coil is energized the contacts open and no current will pass. These states are summarized in Table C6-1. Table C6-1. Summary of NO and NC Relays
Normally Open
Normally Closed
Energized (LED on)
contacts closed/current flow contacts open/no current flow
De-energized (LED off)
contacts open/no current flow contacts closed/current flow
The LED for each output reflects the state of the coil. The LED is on when the coil is energized and off when the coil is de-energized. Specification Table
Characteristic
Output relay (8) module specification
Function
Switches eight relay contacts
Part number
502-03644-02
Field side connector
25 pin card edge connector, screw terminals
Output channels
8
Relay characteristics Contact types
Four form C (NO/NC) Four form A (NO)
Maximum switching voltage
280 VAC resistive load; 50 VDC resistive load
Minimum switching current
100 mA
Maximum switching current (DC)
0-24VDC 40VDC
Maximum switching current (AC)
0-120 VAC @ 3 A280 VAC @ 2.5A
Initial contact resistance
100 mΩ
Turn on time (resistive load)
10 msec maximum
Turn off time (resistive load)
10 msec maximum
Expected life, electrical
105 operations minimum
Expected life, mechanical
107 operations minimum
Breakdown voltage between contacts
750 Vrms for 1 minute
@ 3 A 30 VDC @ 1.5 A 50 VDC
@ 2.5A @ 1.0A
C.6 -5
Page 186
Output Relay Module (8 points)
Breakdown voltage between contacts and coil
1500 Vrms for 1 minute
Maximum switching frequency
20 energize/deenergize cycles/min. (to satisfy expected life ratings)
Indicator light, module
DIAG LED turns off after the module passes its diagnostic tests. A logic side LED for each relay turns on when the logic side energizes the relay.
Isolation
Electromechanical relay provides protection between logic and field side
Logic side power requirements (typical)
1 mA @ 5V 5 mA @ +15V 39 mA per energized output @ +15V (Pt 1-4) 24 mA per energized output @ +15V (Pt 5-8)
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8KV air discharge) per NEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.6 -6