For the Giddings & Lewis 502-03550-02

Page 181

C.6 - Output Relay Module (8 points) Introduction

The relay output module can switch eight relay contacts. Four relays are normally open(NO)/normally closed(NC) form C type and four are normally open (NO) form A type. Eight LEDs in the upper section of the module indicate the logic state that drives each relay. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C6-1. OUTPUT Relay Module (8 PT) OUTPUT RELAY

Name of module Diagnostic LED

DIAG 1 2 3 4

Indicator LEDs

5 6 7 8

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25

Door

AA1064-4491

C.6 -1

Page 182

Output Relay Module (8 points)

Connections

A screw terminal connection is provided for each side of the contact. The form C type has three connections; normally open (NO), normally closed (NC), and the common terminal (CT). Only two of the connections can be wired at any time. The common terminal connection must be wired with either the normally open or the normally closed connection depending on the application. The form A type has two connections; one for each side of the contact. Figure C6-2. Screw Terminal Connector Assignments

CONNECTION

CT 1

NOT USED

CT 2

NOT USED

CT 3

SCREW TERMINALS

CONNECTION

1

NO 1

3

NC 1

5

NO 2

7

NC 2

9

NO 3

11

NC 3

13

NO 4

15

NC 4

17

NO 5

19

NO 6

21

NO 7

23

NO 8

25

NOT

2

4

6

8

10

12 NOT USED

CT 4

NOT USED

14

16 18

NO 5

NO 6

NO 7

NO 8

20

22

24

AA1068-4491

C.6 -2

Page 183

Output Relay Module (8 points)

If the normally open contact of the form C type is required for the application, wire as shown in Figure C6.3. Figure C6-3. Connections for Form C Normally Open Relay Module

1

CT1 3

Power Supply AC or DC

NO 1 Load

NC (not connected)

Common SPG AA1069-4491

If the normally closed contact of the form C type is required for the application, wire as shown in Figure C6-4. Figure C6-4. Connections for Form C Normally Closed Relay Module

1

NO 1 (not connected)

Power Supply AC or DC

CT 1 3

NC 1

Load

Common

SPG

AA1070-4491

To wire the normally open contact of form A, refer to Figure C6-5.

C.6 -3

Page 184

Output Relay Module (8 points)

Figure C6-5. Connections for Form A Normally Open Relay Module

23 24

Power Supply AC or DC

NO 8 NO 8

Load

Common

SPG AA1071-4491

Theory of Operation

A relay is composed of a coil and a set of contacts. When current is passed through the coil, the relay is energized. When no current flows through the coil, the relay is de-energized. The contacts close or open depending on the state of the coil. When the contacts are closed, current can pass through them. When the contacts are open, no current passes. There are three configurations for contacts referred to as form A, B and C as illustrated in Figure C6-6. The relay output module has form A and form C available. Normally Open Form A

Coil

Normally open contact

Figure C6-6. Relay Forms A, B, and C Normally Closed Normally Open/Normally Closed Form B Form C

Coil

Normally open contact

Normally closed contact Coil

Common

AA1065-4491 AA1066-4491

Normally closed contact AA1067-4491

A relay is energized or de-energized according to the logic state sent to it by the CPU. If the CPU sends a logic 1, the relay is energized. If the CPU sends a logic 0, the relay is de-energized. The logic state for each relay is updated every time the CPU scans the program. The names of the two types of contacts - normally open and normally closed reflect the state of the contacts when the coil is de-energized.

C.6 -4

Page 185

Output Relay Module (8 points)

For example, a normally open contact will not pass current when the coil is deenergized. If the coil is energized, the contacts close and current will pass. The normally closed contact will pass current when the coil is de-energized. If the coil is energized the contacts open and no current will pass. These states are summarized in Table C6-1. Table C6-1. Summary of NO and NC Relays

Normally Open

Normally Closed

Energized (LED on)

contacts closed/current flow contacts open/no current flow

De-energized (LED off)

contacts open/no current flow contacts closed/current flow

The LED for each output reflects the state of the coil. The LED is on when the coil is energized and off when the coil is de-energized. Specification Table

Characteristic

Output relay (8) module specification

Function

Switches eight relay contacts

Part number

502-03644-02

Field side connector

25 pin card edge connector, screw terminals

Output channels

8

Relay characteristics Contact types

Four form C (NO/NC) Four form A (NO)

Maximum switching voltage

280 VAC resistive load; 50 VDC resistive load

Minimum switching current

100 mA

Maximum switching current (DC)

0-24VDC 40VDC

Maximum switching current (AC)

0-120 VAC @ 3 A280 VAC @ 2.5A

Initial contact resistance

100 mΩ

Turn on time (resistive load)

10 msec maximum

Turn off time (resistive load)

10 msec maximum

Expected life, electrical

105 operations minimum

Expected life, mechanical

107 operations minimum

Breakdown voltage between contacts

750 Vrms for 1 minute

@ 3 A 30 VDC @ 1.5 A 50 VDC

@ 2.5A @ 1.0A

C.6 -5

Page 186

Output Relay Module (8 points)

Breakdown voltage between contacts and coil

1500 Vrms for 1 minute

Maximum switching frequency

20 energize/deenergize cycles/min. (to satisfy expected life ratings)

Indicator light, module

DIAG LED turns off after the module passes its diagnostic tests. A logic side LED for each relay turns on when the logic side energizes the relay.

Isolation

Electromechanical relay provides protection between logic and field side

Logic side power requirements (typical)

1 mA @ 5V 5 mA @ +15V 39 mA per energized output @ +15V (Pt 1-4) 24 mA per energized output @ +15V (Pt 5-8)

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8KV air discharge) per NEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.6 -6