The text of a manual · part 22 of 60
PiC900 Hardware Manual: C.5 - Output 24V DC Sink Module (32 point)
Pages 171 to 180 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 171
C.5 - Output 24V DC Sink Module (32 point) Introduction
The output 24V DC module sinks voltage for 32 individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in three configurations. 1. 32 point, all diode protected 2. 32 point, 16 diode protected/16 unprotected 3. 32 point, all unprotected 32 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C5-1. OUTPUT 24V DC Sink Module
OUTPUT 24 V DC
FB
Name of module Diagnostic LED "Fuse blown" LED
DIAG
1 5
Indicator LEDs
9 13 17 21 25 29
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AA57-3290
C.5 -1
Page 172
Output 24V DC Sink Module (32 point)
Connections
A screw terminal connection is provided for each output. The outputs are isolated in four groups of eight with one additional terminal per group (DCOUT) for the DC fused supply (DCIN HOT). (See Figure C5-3.) Two terminals are provided for DC common. There is one common for two groups of eight outputs. Two terminals are provided for the DC supply input. Each DC supply input is split into two separate fused circuits and returned to a terminal for field use (See Figure C5-2.) The "fuse blown" LED circuit is active for all groups that have a power supply connected. The DC power supply for each set of 16 devices may be different if required. In most cases one power supply is daisy-chained to all groups. The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in the Hardware chapter, a 24V DC supply was set up according to these guidelines. IMPORTANT Do not connect the DC HOT (DCIN) and COMMON (DCCOM) to a group unless you plan to use one or more of its outputs.
C.5 -2
Page 173
Output 24V DC Sink Module (32 point)
Figure C5-2. Internal Module Connections for Group 1 and 2 Outputs
OUTPUT MODULE DCCOM DCIN1 (HOT)
1 2
Blown Fuse Detector
DCSINK1
Common for Group 1
DCSINK2
Group 1 Loads DCSINK8 11
12
DCOUT1
DCOUT2 DCSINK9
Common for Group 2
DCSINK10
Group 2 Loads
DCSINK16
AA833-1591
C.5 -3
Page 174
Output 24V DC Sink Module (32 point)
Figure C5-3. Screw Terminal Connection Assignments
CONNECTIONS DCCOM1
SCREW TERMINALS
GROUPS
LEDS
1
DCIN1 (line) DCSINK1
3
DCSINK2 DCSINK3
5
DCSINK4 DCSINK5
Group 1 7
DCSINK6 DCSINK7
#7 #8
9
DCSINK8 DCOUT1
#1 #2 #3 #4 #5 #6
11
DCOUT2 DCSINK9
#9 # 10 # 11
13
DCSINK10 DCSINK11
15
DCSINK12 DCSINK13
17
# 12 # 13 # 14
19
# 15 # 16
Group 2
DCSINK14 DCSINK15 DCSINK16 DCCOM2
21
DCIN2 (line) DCSINK17
23
DCSINK18 DCSINK19
25
DCSINK20 DCSINK21
Group 3 27
DCSINK22 DCSINK23
29
# 24
DCSINK24 DCOUT3
# 17 # 18 # 19 # 20 # 21 # 22 # 23
31
DCOUT4 DCSINK25
33
DCSINK26 DCSINK27
35
DCSINK28 DCSINK29
Group 4 37
# 30
DCSINK30 DCSINK31 DCSINK32
# 25 # 26 # 27 # 28 # 29
39
# 31 # 32 AA830-1591
C.5 -4
Page 175
Output 24V DC Sink Module (32 point)
Connections for one group of outputs are illustrated in Figure C5-4. Figure C5-4. Connections for One Group of Outputs
CONNECTIONS DC 0V Supply V+
DCCOM1 HOT
SCREW TERMINALS
1
DCIN1 DCSINK1
3
DCSINK2 DCSINK3
5
DCSINK4 LOADS
DCSINK5
7
DCSINK6 DCSINK7
9
DCSINK8 DCOUT1
11 AA831-1591
Theory of Operation
Each output point is a solid state switch rated at .4 A. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the load is provided a path to common. If the CPU sends a logic 0, the switch opens and power to the load is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. In addition on the 32 point, all protected module, the outputs are protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. On the 32 point, 16 protected/16 unprotected module, 16 of the outputs are protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. The remaining 16 outputs do not have the internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads.
C.5 -5
Page 176
Output 24V DC Sink Module (32 point)
On the 32 point, all unprotected module, the outputs do not have internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads. Protecting from an Inductive Load
Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the DCOUT fused supply. When an output is energized, represented in Figure C5-5a by a closed switch, current passes through the load into the common line. When the output is de-energized, represented in C5-5b by an open switch, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. Any diode protected output in the Output 24V DC module has a diode through which reverse current can be safely routed. Figure C5-5 shows how the internal diode works with an inductive load. When the output is turned off the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts. The internal diode provides another path for current. This limits the peak reverse voltage across the load to less than 1 V. On the 32 point, all protected module, every point has this protection. You can connect an inductive load to any screw terminal. On the 32 point, 16 protected/16 unprotected module, the first 16 switches (DCSINK 1 through DCSINK 16) has this protection so you can connect an inductive load to any of these terminals. The last 16 switches (DCSINK 17 through DCSINK 32) do not have the internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads. On the 32 point, all unprotected module, none of the points has the internal diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads.
C.5 -6
Page 177
Output 24V DC Sink Module (32 point)
Figure C5-4. Diagram of Internal Protection for Inductive Loads
DC power supply V+ 0V
DC power supply V+
0V DCCOM1
OUTPUT MODULE
DCCOM1
DCIN1
DCIN1
DCOUT1 INDUCTIVE LOAD
+
OUTPUT MODULE
DCOUT1
Output switching device
Output switching device
INDUCTIVE LOAD
-
- DCSINK1 a) Output energized
+ DCSINK1 b) Output de-energized AA832-1591
NOTE If inductive loads need to be connected to any unprotected point, an external diode must be connected between the load and DCOUT. Replacing a Fuse
This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. Follow the procedure below to change a blown fuse. 1.
Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.
2.
Press down the latch at the top of the OUTPUT 24V DC module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.
3.
Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover.
C.5 -7
Page 178
Output 24V DC Sink Module (32 point)
Figure C5-5. Positions of Fuses
DIAG LED "Fuse blown" LED
LEDs for the outputs
Fuse for the second group of outputs
Screw terminal connector
64 pin connector to rack Spare fuse
AA836-1091
4.
Identify the fuse that has blown, and use an insulated screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.
C.5 -8
5.
Replace the module cover, making sure that the top and bottom tabs are fully engaged.
6.
Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.
7.
Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and the FB LEDs should both be off.
Page 179
Output 24V DC Sink Module (32 point)
Specification Table Characteristic
Output 24V DC module (32 pt sink) specifications
Function
Sinks an external DC source to 32 loads
Part number
16 protected/16 unprotected 502-03674-02 All diode protected
502-03674-22
All unprotected
502-03674-42
DC source requirements
Nominal 24V DC; range 5 to 32 VDC
Field side connector
40-pin card edge connector, screw terminals
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of outputs
Four groups of 8 solid-state switches. Two groups share a DC supply. Two DC supplies are allowed per module. (One supply may be daisy chained.) UL 508 spacing
Fuse per group of 8 switches
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; each switch is rated at .4 A continuous
Indicator lights, output circuits
An LED for each output
Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maximum ON
1.8 VDC @ .4 A
Surge current, maximum
2.5 A for 40 msec., every 2 seconds
Response to scan loss
All outputs are reset to the OFF state.
Logic side power requirements (typical)
1 mA
Field side power dissipation, worst case (at 32 VDC)
15.8 W
@ +5V
25 mA per energized output @ +5V
C.5 -9
Page 180
Output 24V DC Sink Module (32 point)
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.5 -10