C.5 - Output 24V DC Sink Module (32 point) Introduction

The output 24V DC module sinks voltage for 32 individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in three configurations. 1. 32 point, all diode protected 2. 32 point, 16 diode protected/16 unprotected 3. 32 point, all unprotected 32 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C5-1. OUTPUT 24V DC Sink Module

OUTPUT 24 V DC

FB

Name of module Diagnostic LED "Fuse blown" LED

DIAG

1 5

Indicator LEDs

9 13 17 21 25 29

1 3 5 7 9 11 13

Screw terminal connector

15 17 19 21 23 25 27 29 31 33 35 37 39

Door

AA57-3290

C.5 -1

Page 172

Output 24V DC Sink Module (32 point)

Connections

A screw terminal connection is provided for each output. The outputs are isolated in four groups of eight with one additional terminal per group (DCOUT) for the DC fused supply (DCIN HOT). (See Figure C5-3.) Two terminals are provided for DC common. There is one common for two groups of eight outputs. Two terminals are provided for the DC supply input. Each DC supply input is split into two separate fused circuits and returned to a terminal for field use (See Figure C5-2.) The "fuse blown" LED circuit is active for all groups that have a power supply connected. The DC power supply for each set of 16 devices may be different if required. In most cases one power supply is daisy-chained to all groups. The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in the Hardware chapter, a 24V DC supply was set up according to these guidelines. IMPORTANT Do not connect the DC HOT (DCIN) and COMMON (DCCOM) to a group unless you plan to use one or more of its outputs.

C.5 -2

Page 173

Output 24V DC Sink Module (32 point)

Figure C5-2. Internal Module Connections for Group 1 and 2 Outputs

OUTPUT MODULE DCCOM DCIN1 (HOT)

1 2

Blown Fuse Detector

DCSINK1

Common for Group 1

DCSINK2

Group 1 Loads DCSINK8 11

12

DCOUT1

DCOUT2 DCSINK9

Common for Group 2

DCSINK10

Group 2 Loads

DCSINK16

AA833-1591

C.5 -3

Page 174

Output 24V DC Sink Module (32 point)

Figure C5-3. Screw Terminal Connection Assignments

CONNECTIONS DCCOM1

SCREW TERMINALS

GROUPS

LEDS

1

DCIN1 (line) DCSINK1

3

DCSINK2 DCSINK3

5

DCSINK4 DCSINK5

Group 1 7

DCSINK6 DCSINK7

#7 #8

9

DCSINK8 DCOUT1

#1 #2 #3 #4 #5 #6

11

DCOUT2 DCSINK9

#9 # 10 # 11

13

DCSINK10 DCSINK11

15

DCSINK12 DCSINK13

17

# 12 # 13 # 14

19

# 15 # 16

Group 2

DCSINK14 DCSINK15 DCSINK16 DCCOM2

21

DCIN2 (line) DCSINK17

23

DCSINK18 DCSINK19

25

DCSINK20 DCSINK21

Group 3 27

DCSINK22 DCSINK23

29

# 24

DCSINK24 DCOUT3

# 17 # 18 # 19 # 20 # 21 # 22 # 23

31

DCOUT4 DCSINK25

33

DCSINK26 DCSINK27

35

DCSINK28 DCSINK29

Group 4 37

# 30

DCSINK30 DCSINK31 DCSINK32

# 25 # 26 # 27 # 28 # 29

39

# 31 # 32 AA830-1591

C.5 -4

Page 175

Output 24V DC Sink Module (32 point)

Connections for one group of outputs are illustrated in Figure C5-4. Figure C5-4. Connections for One Group of Outputs

CONNECTIONS DC 0V Supply V+

DCCOM1 HOT

SCREW TERMINALS

1

DCIN1 DCSINK1

3

DCSINK2 DCSINK3

5

DCSINK4 LOADS

DCSINK5

7

DCSINK6 DCSINK7

9

DCSINK8 DCOUT1

11 AA831-1591

Theory of Operation

Each output point is a solid state switch rated at .4 A. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the load is provided a path to common. If the CPU sends a logic 0, the switch opens and power to the load is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. In addition on the 32 point, all protected module, the outputs are protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. On the 32 point, 16 protected/16 unprotected module, 16 of the outputs are protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. The remaining 16 outputs do not have the internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads.

C.5 -5

Page 176

Output 24V DC Sink Module (32 point)

On the 32 point, all unprotected module, the outputs do not have internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads. Protecting from an Inductive Load

Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the DCOUT fused supply. When an output is energized, represented in Figure C5-5a by a closed switch, current passes through the load into the common line. When the output is de-energized, represented in C5-5b by an open switch, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. Any diode protected output in the Output 24V DC module has a diode through which reverse current can be safely routed. Figure C5-5 shows how the internal diode works with an inductive load. When the output is turned off the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts. The internal diode provides another path for current. This limits the peak reverse voltage across the load to less than 1 V. On the 32 point, all protected module, every point has this protection. You can connect an inductive load to any screw terminal. On the 32 point, 16 protected/16 unprotected module, the first 16 switches (DCSINK 1 through DCSINK 16) has this protection so you can connect an inductive load to any of these terminals. The last 16 switches (DCSINK 17 through DCSINK 32) do not have the internal clamping diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads. On the 32 point, all unprotected module, none of the points has the internal diode protection. These outputs should be used for non-inductive loads such as resistive or electronic loads.

C.5 -6

Page 177

Output 24V DC Sink Module (32 point)

Figure C5-4. Diagram of Internal Protection for Inductive Loads

DC power supply V+ 0V

DC power supply V+

0V DCCOM1

OUTPUT MODULE

DCCOM1

DCIN1

DCIN1

DCOUT1 INDUCTIVE LOAD

+

OUTPUT MODULE

DCOUT1

Output switching device

Output switching device

INDUCTIVE LOAD

-

- DCSINK1 a) Output energized

+ DCSINK1 b) Output de-energized AA832-1591

NOTE If inductive loads need to be connected to any unprotected point, an external diode must be connected between the load and DCOUT. Replacing a Fuse

This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. Follow the procedure below to change a blown fuse. 1.

Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.

2.

Press down the latch at the top of the OUTPUT 24V DC module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.

3.

Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover.

C.5 -7

Page 178

Output 24V DC Sink Module (32 point)

Figure C5-5. Positions of Fuses

DIAG LED "Fuse blown" LED

LEDs for the outputs

Fuse for the second group of outputs

Screw terminal connector

64 pin connector to rack Spare fuse

AA836-1091

4.

Identify the fuse that has blown, and use an insulated screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.

C.5 -8

5.

Replace the module cover, making sure that the top and bottom tabs are fully engaged.

6.

Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.

7.

Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and the FB LEDs should both be off.

Page 179

Output 24V DC Sink Module (32 point)

Specification Table Characteristic

Output 24V DC module (32 pt sink) specifications

Function

Sinks an external DC source to 32 loads

Part number

16 protected/16 unprotected 502-03674-02 All diode protected

502-03674-22

All unprotected

502-03674-42

DC source requirements

Nominal 24V DC; range 5 to 32 VDC

Field side connector

40-pin card edge connector, screw terminals

Protection of logic circuits

Optical isolation between the logic and field side

Grouping of outputs

Four groups of 8 solid-state switches. Two groups share a DC supply. Two DC supplies are allowed per module. (One supply may be daisy chained.) UL 508 spacing

Fuse per group of 8 switches

Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm

Maximum current per group

2 A of continuous current for the group; each switch is rated at .4 A continuous

Indicator lights, output circuits

An LED for each output

Indicator light, module

A DIAG LED turns OFF when the module passes its diagnostic tests at power-on

Indicator light, fuses

A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse

Switch characteristics

Solid-state switches

Time delay on for resistive loads

30 µsec max

Time delay off for resistive loads

300 µsec max

Leakage current in off state

0.5 mA max

Switch voltage, maximum ON

1.8 VDC @ .4 A

Surge current, maximum

2.5 A for 40 msec., every 2 seconds

Response to scan loss

All outputs are reset to the OFF state.

Logic side power requirements (typical)

1 mA

Field side power dissipation, worst case (at 32 VDC)

15.8 W

@ +5V

25 mA per energized output @ +5V

C.5 -9

Page 180

Output 24V DC Sink Module (32 point)

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.5 -10