C.4 - Input 120V AC Module (16 points) Introduction
The input 120V AC module converts AC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 120 VAC, but can be any level between 79 and 132 volts. An "off" signal is any level below 20 VAC. The wiring configurations may be sink or source. 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C4-1. INPUT 120V AC Module (16 PT)
INPUT 120V AC
Name of module Diagnostic LED
DIAG
1 5
Indicator LEDs
9 13
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25
Door
AA52-0690
C.4 -1
Page 164
Input 120V AC Module (16 points)
Connections
A screw terminal connector is provided for each input, and for each external power source. The inputs are isolated in four groups of 4, with one additional terminal per group to determine sink or source operation. The devices for each group must be powered from the same AC source. (See Figure C4-2.) Each group can work independently from the others; some groups may be sink and others source. The AC power source for each group may be different if required. Typically just one source is used, daisy-chained from one group to the next. The AC input should be connected to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. See the power distribution diagrams in Chapter 1 for AC power connections. Figure C4-2. Screw Terminal Connector Assignments MNEMONIC
ACSS1
ACIN1
SCREW TERMINALS
FUNCTION
LED
1
AC sink/source, group 1
3
AC input 1
#1
ACIN 2
AC input 2
#2
ACIN3
AC input 3
#3
AC input 4
#4
5
ACIN4 ACSS2
ACIN5
7
AC sink/source, group 2
9
AC input 5
#5
ACIN6
AC input 6
#6
ACIN7
AC input 7
#7
AC input 8
#8
11
ACIN8 ACSS3
13
AC sink/source, group 3
ACIN9
15
AC input 9
#9
ACIN10
AC input 10
# 10
ACIN11
AC input 11
# 11
AC input 12
# 12
17
ACIN12 ACSS4
19
AC sink/source, group 4
ACIN13
21
AC input 13
# 13
AC input 14
# 14
AC input 15
# 15
AC input 16
# 16
ACIN14 ACIN15
23
ACIN16
25 AA54-0690
C.4 -2
Page 165
Input 120V AC Module (16 points)
Figure C4-3 illustrates two groups of inputs using the same AC source. The first group of four inputs are shown with devices "sinking" current through the AC Input module. The HOT terminal of the power source must be connected to the module at ACSS1. The second group of four inputs are shown with devices "sourcing" current through the AC Input module. The COMMON terminal of the power source must be connected to the module at ACSS2. Figure C4-3. Connectors for Two Groups of Inputs
SWITCHING DEVICE HOT
NAMES FOR TERMINALS ACSS1
ACIN1 AC SOURCE
SCREW TERMINALS
1
3
ACIN2 ACIN3 COMMON
ACIN4
COMMON
ACSS2
HOT
ACIN5
5 7
9
SOURCE
ACIN6 ACIN7
SINK
11
ACIN8 AA53-0690
C.4 -3
Page 166
Input 120V AC Module (16 points)
Theory of Operation
Each input is guaranteed "on" between 79 and 132 VAC and guaranteed "off" between 0 and 20 VAC. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module, where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED in the upper section of the module indicates the logic state of each input. The four LEDs representing each group are in a horizontal row. If you need to know the voltage at the field side, use a voltmeter on the terminal screws. Figure C4-4 shows the input characteristics of the module compared to IEC standards. The shaded blocks show the limits specified by the IEC, and the lines show the maximum and minimum V/I of the inputs in this module. This voltage/current curve in this graph shows that the AC input module is well within the IEC Type 1 limits. Figure C4-4. Input Characteristics Compared to IEC Standards
U IN VOLTS MIN MAX
UHMAX 132 125 UNOM 120
"ON" REGION
INPUT VOLTAGE
100
UHMIN 79
(UTMAX) 75
50
TRANSITION REGION
25 ULMAX 20 (UTMIN )
"OFF" REGION
0 1
2
ITMIN IHMIN
C.4 -4
4
6
8
10
INPUT CURRENT
12
14
15 I IN mAMPS I MAX AA55-0690
Page 167
Input 120V AC Module (16 points)
IMPORTANT Switching devices can sometimes have a leakage current that exceeds the ITmin (current allowed when off) of an input module. In order to use such a device, an impedance (typically, a resistor) needs to be used in parallel with the input. For example, some of the newer proximity switches use two wires instead of three. The third wire was used for a power or ground line. Without the third wire, the switch is easier to install. However, it requires more leakage current in the off state to power its internal circuitry. As a conservative estimate, use the following formula to calculate an external resistance value. It keeps the input voltage at or below 12V when the switching device is in the "off" state. 12V ------------------------------------------------------- ≥ R Switch Leakage – 1mA If the switch leakage specification ≤ 1.7 mA, then: 12V ------------------------ ≥ 17.1KΩ 1.7 – 1mA Use a 16 K Ω, 2W or any lower resistance and higher wattage resistor. Be sure that the wattage is adequate for the resistor remembering that: 2
V rms P = ---------R It would be acceptable to use a .15 µF (or greater) capacitor rated for 120V AC. The advantage of the capacitor is minimal power dissipation. 1 Xc = -----------2πfC
C.4 -5
Page 168
Input 120V AC Module (16 points)
Specification Table
Characteristic
Input 120V AC (16 pt) Module Specifications
Function
Monitors on/off states from up to 16 AC voltage inputs
Part number
502-03550-02
Field side connector
25-pin card edge connector, screw terminals
Input signals
Nominal 120 VAC on, 0 VAC off, conforming to IEC Type 1 inputs per IEC 1131-2 ( four groups of four inputs)
UH Max (max. allowed voltage)
132 VAC
IH Max (max. current @ 132 VAC)
8.7 mA
UL Min
0V
Guaranteed on
79 VAC
IH Min (min. current @ UH Min)
4.6 mA
Guaranteed off
20 VAC
IT Min (current allowed when off)
1 mA
Frequency
50/60 Hz ± 5%
Time delay on, max.
14 ms
Time delay off, max.
20 ms
Protection of logic circuits
Optical isolation between the logic and field sides, 1780 VAC
Indicator lights, circuits
An LED indicates its logic state of each input
Indicator light, module
The DIAG LED goes off after the module passes its diagnostic tests at power-on.
Logic side power requirements (typical)
1 mA 11 mA per energized input
Field side power dissipation, worst case
18.4 W
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
C.4 -6
@ +5V @ +5V
Page 169
Input 120V AC Module (16 points)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.4 -7
Page 170
Input 120V AC Module (16 points)
NOTES
C.4 -8