Page 163

C.4 - Input 120V AC Module (16 points) Introduction

The input 120V AC module converts AC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 120 VAC, but can be any level between 79 and 132 volts. An "off" signal is any level below 20 VAC. The wiring configurations may be sink or source. 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C4-1. INPUT 120V AC Module (16 PT)

INPUT 120V AC

Name of module Diagnostic LED

DIAG

1 5

Indicator LEDs

9 13

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25

Door

AA52-0690

C.4 -1

Page 164

Input 120V AC Module (16 points)

Connections

A screw terminal connector is provided for each input, and for each external power source. The inputs are isolated in four groups of 4, with one additional terminal per group to determine sink or source operation. The devices for each group must be powered from the same AC source. (See Figure C4-2.) Each group can work independently from the others; some groups may be sink and others source. The AC power source for each group may be different if required. Typically just one source is used, daisy-chained from one group to the next. The AC input should be connected to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. See the power distribution diagrams in Chapter 1 for AC power connections. Figure C4-2. Screw Terminal Connector Assignments MNEMONIC

ACSS1

ACIN1

SCREW TERMINALS

FUNCTION

LED

1

AC sink/source, group 1

3

AC input 1

#1

ACIN 2

AC input 2

#2

ACIN3

AC input 3

#3

AC input 4

#4

5

ACIN4 ACSS2

ACIN5

7

AC sink/source, group 2

9

AC input 5

#5

ACIN6

AC input 6

#6

ACIN7

AC input 7

#7

AC input 8

#8

11

ACIN8 ACSS3

13

AC sink/source, group 3

ACIN9

15

AC input 9

#9

ACIN10

AC input 10

# 10

ACIN11

AC input 11

# 11

AC input 12

# 12

17

ACIN12 ACSS4

19

AC sink/source, group 4

ACIN13

21

AC input 13

# 13

AC input 14

# 14

AC input 15

# 15

AC input 16

# 16

ACIN14 ACIN15

23

ACIN16

25 AA54-0690

C.4 -2

Page 165

Input 120V AC Module (16 points)

Figure C4-3 illustrates two groups of inputs using the same AC source. The first group of four inputs are shown with devices "sinking" current through the AC Input module. The HOT terminal of the power source must be connected to the module at ACSS1. The second group of four inputs are shown with devices "sourcing" current through the AC Input module. The COMMON terminal of the power source must be connected to the module at ACSS2. Figure C4-3. Connectors for Two Groups of Inputs

SWITCHING DEVICE HOT

NAMES FOR TERMINALS ACSS1

ACIN1 AC SOURCE

SCREW TERMINALS

1

3

ACIN2 ACIN3 COMMON

ACIN4

COMMON

ACSS2

HOT

ACIN5

5 7

9

SOURCE

ACIN6 ACIN7

SINK

11

ACIN8 AA53-0690

C.4 -3

Page 166

Input 120V AC Module (16 points)

Theory of Operation

Each input is guaranteed "on" between 79 and 132 VAC and guaranteed "off" between 0 and 20 VAC. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module, where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED in the upper section of the module indicates the logic state of each input. The four LEDs representing each group are in a horizontal row. If you need to know the voltage at the field side, use a voltmeter on the terminal screws. Figure C4-4 shows the input characteristics of the module compared to IEC standards. The shaded blocks show the limits specified by the IEC, and the lines show the maximum and minimum V/I of the inputs in this module. This voltage/current curve in this graph shows that the AC input module is well within the IEC Type 1 limits. Figure C4-4. Input Characteristics Compared to IEC Standards

U IN VOLTS MIN MAX

UHMAX 132 125 UNOM 120

"ON" REGION

INPUT VOLTAGE

100

UHMIN 79

(UTMAX) 75

50

TRANSITION REGION

25 ULMAX 20 (UTMIN )

"OFF" REGION

0 1

2

ITMIN IHMIN

C.4 -4

4

6

8

10

INPUT CURRENT

12

14

15 I IN mAMPS I MAX AA55-0690

Page 167

Input 120V AC Module (16 points)

IMPORTANT Switching devices can sometimes have a leakage current that exceeds the ITmin (current allowed when off) of an input module. In order to use such a device, an impedance (typically, a resistor) needs to be used in parallel with the input. For example, some of the newer proximity switches use two wires instead of three. The third wire was used for a power or ground line. Without the third wire, the switch is easier to install. However, it requires more leakage current in the off state to power its internal circuitry. As a conservative estimate, use the following formula to calculate an external resistance value. It keeps the input voltage at or below 12V when the switching device is in the "off" state. 12V ------------------------------------------------------- ≥ R Switch Leakage – 1mA If the switch leakage specification ≤ 1.7 mA, then: 12V ------------------------ ≥ 17.1KΩ 1.7 – 1mA Use a 16 K Ω, 2W or any lower resistance and higher wattage resistor. Be sure that the wattage is adequate for the resistor remembering that: 2

V rms P = ---------R It would be acceptable to use a .15 µF (or greater) capacitor rated for 120V AC. The advantage of the capacitor is minimal power dissipation. 1 Xc = -----------2πfC

C.4 -5

Page 168

Input 120V AC Module (16 points)

Specification Table

Characteristic

Input 120V AC (16 pt) Module Specifications

Function

Monitors on/off states from up to 16 AC voltage inputs

Part number

502-03550-02

Field side connector

25-pin card edge connector, screw terminals

Input signals

Nominal 120 VAC on, 0 VAC off, conforming to IEC Type 1 inputs per IEC 1131-2 ( four groups of four inputs)

UH Max (max. allowed voltage)

132 VAC

IH Max (max. current @ 132 VAC)

8.7 mA

UL Min

0V

Guaranteed on

79 VAC

IH Min (min. current @ UH Min)

4.6 mA

Guaranteed off

20 VAC

IT Min (current allowed when off)

1 mA

Frequency

50/60 Hz ± 5%

Time delay on, max.

14 ms

Time delay off, max.

20 ms

Protection of logic circuits

Optical isolation between the logic and field sides, 1780 VAC

Indicator lights, circuits

An LED indicates its logic state of each input

Indicator light, module

The DIAG LED goes off after the module passes its diagnostic tests at power-on.

Logic side power requirements (typical)

1 mA 11 mA per energized input

Field side power dissipation, worst case

18.4 W

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

C.4 -6

@ +5V @ +5V

Page 169

Input 120V AC Module (16 points)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.4 -7

Page 170

Input 120V AC Module (16 points)

NOTES