PiC900 Hardware Manual: C.3 - Output 120/240V AC Module (32 or 16 point)

Pages 153 to 162 of 508, from PiC900 Hardware Manual

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 153

C.3 - Output 120/240V AC Module (32 or 16 point) Introduction

The 120/240V output module switches voltage for individual loads from one or more AC power sources. Each external AC source is nominally 115 VAC, but can be between 48 and 240 volts. It is available in the following configurations; 1.

32 point 120/240V AC output module

2.

16 point 120/240V AC output module

32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C3-1. OUTPUT 120/240 VAC Module

32 POINT

OUTPUT 120 V AC

FB

16 POINT

Name of module Diagnostic LED "Fuse blown" LED

DIAG

1 5

OUTPUT 120/240VAC

FB

Name of module Diagnostic LED "Fuse blown" LED

DIAG

1 5

Indicator LEDs

9 13

Indicator LEDs

9 13

17 21 25 29

1

1

3

3

5

5

7

7 9 11 13

9

Screw terminal connector

11 13

Screw terminal connector

15

15

17

17

19

19

21

21

23

23

25

25 27 29 31 33 35 37 39

Door

Door

AA1115-3092

AA46-0690

C.3 -1

Page 154

Output 120/240V AC Module (32 or 16 point)

Connections

A screw terminal connection is provided for each output, and for each external power source connection. The outputs are isolated in four groups of eight or four, with two additional terminals per group for the AC HOT and COMMON. (See Figure C3-2.) The external AC source for each group of 8 devices may be different if required. In most cases one power source is daisy-chained to each group. The AC source should be connected to the single-point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. See the power distribution diagrams in Chapter 1 for two possible AC external source set-ups.

NOTE Do not connect an AC HOT and COMMON to a group unless you plan to use one or more of its outputs.

C.3 -2

Page 155

Output 120/240V AC Module (32 or 16 point)

Figure C3-2. Screw Terminal Connector Assignments 32 point 16 point SCREW CONNECTIONS TERMINALS

SCREW CONNECTIONS TERMINALS

5

ACOUT4

7

ACOUT6 ACOUT7

9

ACOUT8 ACL2

#1 #2 #3 #4 #5 #6 #7

ACOUT1

ACOUT3

11

ACOUT9

ACOUT7

15

ACOUT12

Group 2

13

ACOUT10

17

ACOUT14 ACOUT15

19

#9 # 10 # 11 # 12 # 13 # 14 # 15 # 16

ACOUT16 ACL3

21

25

ACOUT20 ACOUT21

Group 3

23

ACOUT18 ACOUT19

27

ACOUT22 ACOUT23

29

ACOUT24 ACL4

7

ACL3

# 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24

9 11 13 15

#4

AC HOT AC output 5 AC output 7

#5 #6 #7 #8

AC HOT AC output 9 AC output 10

17

AC output 11

19

#9 # 10 # 11 # 12

AC output 12

ACCOM4

AC HOT AC COMMON

21

ACOUT14 ACOUT15

AC output 4

AC COMMON

ACOUT12

ACOUT13

#3

AC output 8

ACOUT10 ACOUT11

#2

AC output 3

AC output 6

ACCOM3 ACOUT9

#1

AC COMMON

ACOUT8

ACL4

ACCOM3 ACOUT17

5

#8 ACOUT5

AC output 1 AC output 2

ACCOM2

ACOUT6

ACOUT13

3

ACOUT4 ACL2

AC HOT AC COMMON

ACOUT2

ACCOM2

ACOUT11

1

Group 1

ACOUT2

Group 1

3

Group 2

ACCOM1

Group 3

ACL1

ACOUT1

ACOUT5

LED

1

ACCOM1

ACOUT3

FUNCTION

AC output 13 AC output 14

23

ACOUT16

AC output 15 AC output 16

Group 4

ACL1

LEDS

# 13 # 14 # 15 # 16

25 AA48-0690

31

ACCOM4 ACOUT25

33

ACOUT27

35

ACOUT28 ACOUT29

37

ACOUT30 ACOUT31 ACOUT32

Group 4

ACOUT26

# 25 # 26 # 27 # 28 # 29 # 30

39

# 31 # 32 AA1112-2492

C.3 -3

Page 156

Output 120/240V AC Module (32 or 16 point)

Each group has its own protective fuse. The "fuse blown" LED circuit is active for all groups that have a power source connected. Figure C3-3 and C3-4 illustrates the connections for one group of outputs. The common side of each load must be connected to the COMMON of the AC source. Figure C3-3. Connectors for One Group of Outputs (32 point module) AC SUPPLY

LOADS

HOT

CONNECTIONS

SCREW TERMINALS

ACL1

COMMON

1

ACCOM1 ACOUT1

3

ACOUT2 ACOUT3

5

ACOUT4 ACOUT5

7

ACOUT6 ACOUT7

9

ACOUT8

Figure C3-4. Connectors for One Group of Outputs (16 point module)

AC SUPPLY

HOT COMMON

LOADS

SCREW CONNECTIONS TERMINALS

ACL1

1

ACCOM1 ACOUT1

3

ACOUT2 ACOUT3

5

ACOUT4 AA47-0690

C.3 -4

Page 157

Output 120/240V AC Module (32 or 16 point)

Theory of Operation

Each output point is a solid state switch rated at .75A continuous for the 32 point module and 2A continuous for the 16 point module. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the load is powered. If the CPU sends a logic 0, the switch opens and power to the load is removed. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each output. If you need to know whether voltage is actually on at the field side, use a voltmeter on the terminal screws. The output switch is turned on near the zero voltage crossing of the AC power source and is turned off at zero current. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. Protecting from an Inductive Load

Arc suppression is not required for a non-inductive load or for an inductive load switched only by the Output 120/240V AC (32 pt) module. If an inductive load is in series with an external switch or contact, an external arc suppresser is required as shown in Figure C3-5 and C3-6. When an inductive load is turned off it can generate a voltage spike which may peak at several thousand volts. Such a spike can cause erratic operation and may damage the module. You must place an arc suppresser across the inductive device to absorb the excess energy.

C.3 -5

Page 158

Output 120/240V AC Module (32 or 16 point)

Figure C3-5. Arc Suppression for a Switched Inductive Load (32 pt module)

AC SUPPLY

LOADS

CONNECTIONS

SCREW TERMINALS

ACL1

HOT

1

ACCOM1

COMMON

ACOUT1

3

ACOUT2 ACOUT3

5

ACOUT4 ACOUT5 9 ACOUT6

7

ACOUT7 ACOUT8

(RC bypass)

Figure C3-6. Arc Suppression for a Switched Inductive Load (16 pt module)

AC SUPPLY

LOADS

SCREW CONNECTIONS TERMINALS ACL1

HOT COMMON

1

ACCOM1 ACOUT1

3

ACOUT2 ACOUT3

5

ACOUT4

(RC bypass)

Specifications for the RC bypass:

resistor: 220 Ω 1 Watt capacitor: 1.0 µF, 600 V

C.3 -6

AA49-0690

Page 159

Output 120/240V AC Module (32 or 16 point)

Replacing a Fuse

This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. 1.

Turn off the main disconnect switch for the system rack and the external AC power source to this module. Remove the screw terminal connector bar.

2.

Press down the latch at the top of the OUTPUT 120/240V AC (32 pt) module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.

3.

Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover. Figure C3-7. Position of Fuses

Spare fuse DIAG LED "Fuse blown" LED

LEDs for the outputs

Fuses for each group of outputs

Screw termimal connector

64 pin connector to rack

AA1116-3092

C.3 -7

Page 160

Output 120/240V AC Module (32 or 16 point)

4.

Identify the fuse that has blown, and use an insulted screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement fuse must be a fastacting 3A 250 VAC fuse. The following fuses are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.

C.3 -8

5.

Replace the module cover, making sure that the top and bottom tabs are fully engaged.

6.

Slide the module back in its slot, and turn power back on. After the diagnostic tests runs, the DIAG and the FB lights should both be off.

7.

Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.

Page 161

Output 120/240V AC Module (32 or 16 point)

Specification Table

Characteristic

Output 120/240V AC module specifications

Function

Switches an external AC source to 32 or 16 loads

Part number

32 point 16 point

AC source requirements

Nominal 115 VAC, range 48 to 240 VAC

Field side connector

32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals

Protection of logic circuits

Optical isolation between the logic and field side, 2830 VAC

Arrangement of outputs

Four groups of 8 or 4 solid-state switches. Each group can use its own AC source, or one source can be daisychained. UL 508 spacing

Fuse per group of 8

Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm

Maximum current per group

2 A of continuous current for the group; 32 point each switch is rated at .75 A continuous 16 point each switch is rated at 2 A continuous

Indicator lights, output circuits

An LED for each output

Indicator light, module

A DIAG LED turns OFF when the module passes its diagnostic tests at power-on.

Indicator light, fuses

A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with a missing or open fuse.

Switch characteristics

Solid-state switches.

Switch voltage, maximum ON

32 point 1V AC @ .75A RMS 16 point 1.2V AC @ 2A RMS

Surge current, maximum

20 A for 2 cycles, every 2 seconds; fuse blows if this is exceeded.

Frequency

50 / 60 Hz. ± 5%

Time delay on, maximum

1/2 cycle (turns on at zero voltage)

Time delay off, maximum

1/2 cycle (turns off at zero voltage)

Minimum load current

50 mA

Leakage current in OFF state, maximum

4 mA @ 120 VAC 6 mA @ 240 VAC

502-03641-02 502-03551-02

C.3 -9

Page 162

Output 120/240V AC Module (32 or 16 point)

Response to scan loss

All outputs are reset to the OFF state

Logic side power requirements (typical)

32 point 1 mA 7 mA per energized output 16 point 1 mA 23 mA per energized output

Field side power dissipation, worst case

32 point 16 point

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards:

@ +5V @ +5V @ +5V @ +5V

11.0W 12.0W

EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information. UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.3 -10