The text of a manual · part 20 of 60
PiC900 Hardware Manual: C.3 - Output 120/240V AC Module (32 or 16 point)
Pages 153 to 162 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 153
C.3 - Output 120/240V AC Module (32 or 16 point) Introduction
The 120/240V output module switches voltage for individual loads from one or more AC power sources. Each external AC source is nominally 115 VAC, but can be between 48 and 240 volts. It is available in the following configurations; 1.
32 point 120/240V AC output module
2.
16 point 120/240V AC output module
32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. Figure C3-1. OUTPUT 120/240 VAC Module
32 POINT
OUTPUT 120 V AC
FB
16 POINT
Name of module Diagnostic LED "Fuse blown" LED
DIAG
1 5
OUTPUT 120/240VAC
FB
Name of module Diagnostic LED "Fuse blown" LED
DIAG
1 5
Indicator LEDs
9 13
Indicator LEDs
9 13
17 21 25 29
1
1
3
3
5
5
7
7 9 11 13
9
Screw terminal connector
11 13
Screw terminal connector
15
15
17
17
19
19
21
21
23
23
25
25 27 29 31 33 35 37 39
Door
Door
AA1115-3092
AA46-0690
C.3 -1
Page 154
Output 120/240V AC Module (32 or 16 point)
Connections
A screw terminal connection is provided for each output, and for each external power source connection. The outputs are isolated in four groups of eight or four, with two additional terminals per group for the AC HOT and COMMON. (See Figure C3-2.) The external AC source for each group of 8 devices may be different if required. In most cases one power source is daisy-chained to each group. The AC source should be connected to the single-point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. See the power distribution diagrams in Chapter 1 for two possible AC external source set-ups.
NOTE Do not connect an AC HOT and COMMON to a group unless you plan to use one or more of its outputs.
C.3 -2
Page 155
Output 120/240V AC Module (32 or 16 point)
Figure C3-2. Screw Terminal Connector Assignments 32 point 16 point SCREW CONNECTIONS TERMINALS
SCREW CONNECTIONS TERMINALS
5
ACOUT4
7
ACOUT6 ACOUT7
9
ACOUT8 ACL2
#1 #2 #3 #4 #5 #6 #7
ACOUT1
ACOUT3
11
ACOUT9
ACOUT7
15
ACOUT12
Group 2
13
ACOUT10
17
ACOUT14 ACOUT15
19
#9 # 10 # 11 # 12 # 13 # 14 # 15 # 16
ACOUT16 ACL3
21
25
ACOUT20 ACOUT21
Group 3
23
ACOUT18 ACOUT19
27
ACOUT22 ACOUT23
29
ACOUT24 ACL4
7
ACL3
# 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24
9 11 13 15
#4
AC HOT AC output 5 AC output 7
#5 #6 #7 #8
AC HOT AC output 9 AC output 10
17
AC output 11
19
#9 # 10 # 11 # 12
AC output 12
ACCOM4
AC HOT AC COMMON
21
ACOUT14 ACOUT15
AC output 4
AC COMMON
ACOUT12
ACOUT13
#3
AC output 8
ACOUT10 ACOUT11
#2
AC output 3
AC output 6
ACCOM3 ACOUT9
#1
AC COMMON
ACOUT8
ACL4
ACCOM3 ACOUT17
5
#8 ACOUT5
AC output 1 AC output 2
ACCOM2
ACOUT6
ACOUT13
3
ACOUT4 ACL2
AC HOT AC COMMON
ACOUT2
ACCOM2
ACOUT11
1
Group 1
ACOUT2
Group 1
3
Group 2
ACCOM1
Group 3
ACL1
ACOUT1
ACOUT5
LED
1
ACCOM1
ACOUT3
FUNCTION
AC output 13 AC output 14
23
ACOUT16
AC output 15 AC output 16
Group 4
ACL1
LEDS
# 13 # 14 # 15 # 16
25 AA48-0690
31
ACCOM4 ACOUT25
33
ACOUT27
35
ACOUT28 ACOUT29
37
ACOUT30 ACOUT31 ACOUT32
Group 4
ACOUT26
# 25 # 26 # 27 # 28 # 29 # 30
39
# 31 # 32 AA1112-2492
C.3 -3
Page 156
Output 120/240V AC Module (32 or 16 point)
Each group has its own protective fuse. The "fuse blown" LED circuit is active for all groups that have a power source connected. Figure C3-3 and C3-4 illustrates the connections for one group of outputs. The common side of each load must be connected to the COMMON of the AC source. Figure C3-3. Connectors for One Group of Outputs (32 point module) AC SUPPLY
LOADS
HOT
CONNECTIONS
SCREW TERMINALS
ACL1
COMMON
1
ACCOM1 ACOUT1
3
ACOUT2 ACOUT3
5
ACOUT4 ACOUT5
7
ACOUT6 ACOUT7
9
ACOUT8
Figure C3-4. Connectors for One Group of Outputs (16 point module)
AC SUPPLY
HOT COMMON
LOADS
SCREW CONNECTIONS TERMINALS
ACL1
1
ACCOM1 ACOUT1
3
ACOUT2 ACOUT3
5
ACOUT4 AA47-0690
C.3 -4
Page 157
Output 120/240V AC Module (32 or 16 point)
Theory of Operation
Each output point is a solid state switch rated at .75A continuous for the 32 point module and 2A continuous for the 16 point module. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the load is powered. If the CPU sends a logic 0, the switch opens and power to the load is removed. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each output. If you need to know whether voltage is actually on at the field side, use a voltmeter on the terminal screws. The output switch is turned on near the zero voltage crossing of the AC power source and is turned off at zero current. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. Protecting from an Inductive Load
Arc suppression is not required for a non-inductive load or for an inductive load switched only by the Output 120/240V AC (32 pt) module. If an inductive load is in series with an external switch or contact, an external arc suppresser is required as shown in Figure C3-5 and C3-6. When an inductive load is turned off it can generate a voltage spike which may peak at several thousand volts. Such a spike can cause erratic operation and may damage the module. You must place an arc suppresser across the inductive device to absorb the excess energy.
C.3 -5
Page 158
Output 120/240V AC Module (32 or 16 point)
Figure C3-5. Arc Suppression for a Switched Inductive Load (32 pt module)
AC SUPPLY
LOADS
CONNECTIONS
SCREW TERMINALS
ACL1
HOT
1
ACCOM1
COMMON
ACOUT1
3
ACOUT2 ACOUT3
5
ACOUT4 ACOUT5 9 ACOUT6
7
ACOUT7 ACOUT8
(RC bypass)
Figure C3-6. Arc Suppression for a Switched Inductive Load (16 pt module)
AC SUPPLY
LOADS
SCREW CONNECTIONS TERMINALS ACL1
HOT COMMON
1
ACCOM1 ACOUT1
3
ACOUT2 ACOUT3
5
ACOUT4
(RC bypass)
Specifications for the RC bypass:
resistor: 220 Ω 1 Watt capacitor: 1.0 µF, 600 V
C.3 -6
AA49-0690
Page 159
Output 120/240V AC Module (32 or 16 point)
Replacing a Fuse
This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. 1.
Turn off the main disconnect switch for the system rack and the external AC power source to this module. Remove the screw terminal connector bar.
2.
Press down the latch at the top of the OUTPUT 120/240V AC (32 pt) module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.
3.
Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover. Figure C3-7. Position of Fuses
Spare fuse DIAG LED "Fuse blown" LED
LEDs for the outputs
Fuses for each group of outputs
Screw termimal connector
64 pin connector to rack
AA1116-3092
C.3 -7
Page 160
Output 120/240V AC Module (32 or 16 point)
4.
Identify the fuse that has blown, and use an insulted screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement fuse must be a fastacting 3A 250 VAC fuse. The following fuses are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.
C.3 -8
5.
Replace the module cover, making sure that the top and bottom tabs are fully engaged.
6.
Slide the module back in its slot, and turn power back on. After the diagnostic tests runs, the DIAG and the FB lights should both be off.
7.
Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.
Page 161
Output 120/240V AC Module (32 or 16 point)
Specification Table
Characteristic
Output 120/240V AC module specifications
Function
Switches an external AC source to 32 or 16 loads
Part number
32 point 16 point
AC source requirements
Nominal 115 VAC, range 48 to 240 VAC
Field side connector
32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals
Protection of logic circuits
Optical isolation between the logic and field side, 2830 VAC
Arrangement of outputs
Four groups of 8 or 4 solid-state switches. Each group can use its own AC source, or one source can be daisychained. UL 508 spacing
Fuse per group of 8
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; 32 point each switch is rated at .75 A continuous 16 point each switch is rated at 2 A continuous
Indicator lights, output circuits
An LED for each output
Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on.
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with a missing or open fuse.
Switch characteristics
Solid-state switches.
Switch voltage, maximum ON
32 point 1V AC @ .75A RMS 16 point 1.2V AC @ 2A RMS
Surge current, maximum
20 A for 2 cycles, every 2 seconds; fuse blows if this is exceeded.
Frequency
50 / 60 Hz. ± 5%
Time delay on, maximum
1/2 cycle (turns on at zero voltage)
Time delay off, maximum
1/2 cycle (turns off at zero voltage)
Minimum load current
50 mA
Leakage current in OFF state, maximum
4 mA @ 120 VAC 6 mA @ 240 VAC
502-03641-02 502-03551-02
C.3 -9
Page 162
Output 120/240V AC Module (32 or 16 point)
Response to scan loss
All outputs are reset to the OFF state
Logic side power requirements (typical)
32 point 1 mA 7 mA per energized output 16 point 1 mA 23 mA per energized output
Field side power dissipation, worst case
32 point 16 point
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards:
@ +5V @ +5V @ +5V @ +5V
11.0W 12.0W
EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information. UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.3 -10