The text of a manual · part 19 of 60
PiC900 Hardware Manual: C.2 - Input 24V DC Module (32 or 16 points)
Pages 143 to 152 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 143
C.2 - Input 24V DC Module (32 or 16 points) Introduction
The input 24V DC module converts DC signals from devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 24 VDC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. The module is available in the following configurations. 1.
32 point 24V DC input module
2.
6 point 24V DC input module
32 or 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running. Figure C2-1. INPUT 24V DC Module 32 point 16 point
INPUT
24 V DC
Name of module
INPUT 24 V DC
Diagnostic LED
DIAG
1
Name of module Diagnostic LED
DIAG
1
5 5 9
Indicator LEDs
13
Indicator LEDs
9 13
17 21 25 29
1
1
3
3
5
5
7
7 9
9 11 13
Screw terminal connector
11 13
15
15
17
17
19
19
21
21
23
23
25
25
Screw terminal connector
27 29 31 33 35 37 39
Door
Door
AA42-2290
AA37-0690
C.2 -1
Page 144
Input 24V DC Module (32 or 16 points)
Connections
A screw terminal connector is provided for each input and for each external power supply connection. The inputs are isolated in four groups of eight or four, with one additional terminal per group for the DC source/sink connection. The devices connected to terminals in the same group have a common DC supply and are wired in the same configuration, sink or source. The external DC supply that powers the input signals should have a wire connected from its 0V (COMMON) terminal directly to the single-point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in Chapter 1, a 24 VDC supply is set up according to these guidelines.
C.2 -2
Page 145
Input 24V DC Module (32 or 16 points)
Figure C2-2. Screw Terminal Connector Assignments 32 point 16 point
SCREW CONNECTIONS TERMINALS
FUNCTION
LED
DC input 1 DC input 2
#1
DCSS1
#2 #3
DCIN1
DCIN4
5
DCIN5 DCIN6
7
DC input 6 DC input 7
9
DC input 8 DC sink/source
DCIN7 DCIN8
DC input 3 DC input 4 DC input 5
DCSS1
#4 #5 #6 #7 #8
13
DCIN11 DCIN12
15
DCIN13 DCIN14
17
DCIN15 DCIN16
19
DCSS2
DCIN3
DC input 9 DC input 10 DC input 11 DC input 12 DC input 13
DC input 14 DC input 15 DC input 16 DC sink/source
#9 # 10 # 11 # 12 # 13 # 14 # 15
23
DCIN19 DCIN20
25
DCIN21 DCIN22
27
DCIN23 DCIN24
29
DCSS3
5
DC input 3 DC input 4
#1 #2 #3 #4
7 DCSS2
DC sink/source 9
DCIN7
DC input 5 DC input 6
11
DCIN8
DC input 7 DC input 8
#5 #6 #7 #8
13 DCSS3 DCIN9
DC sink/source 15
DCIN10 DCIN11
# 16
DC input 9 DC input 10
17
DCIN12
DC input 11 DC input 12
#9 # 10 # 11 # 12
19 DC input 17 DC input 18 DC input 19 DC input 20 DC input 21 DC input 22 DC input 23
Group 3
DCIN18
DC input 1 DC input 2
DCIN4
21 DCIN17
3
DCIN6
Group 2
DCIN10
DC sink/source
DCIN 2
DCIN5
11 DCIN9
1
Group 1
3
DCIN3
LED
Group 2
DCIN2
Group 1
1 DCIN1
FUNCTION
Group 3
SCREW TERMINALS
DC input 24 DC sink/source
# 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24
DCSS4 DCIN13
DC sink/source 21
DCIN14 DCIN15
DC input 13 DC input 14
23
DCIN16
DC input 15 DC input 16
Group 4
CONNECTIONS
# 13 # 14 # 15 # 16
25
31 DCIN26
33
DCIN27 DCIN28
35
DCIN29 DCIN30
37
DCIN31 DCIN32 DCSS4
39
DC input 25 DC input 26 DC input 27 DC input 28 DC input 29 DC input 30
Group 4
DCIN25
DC input 31 DC input 32 DC sink/source
# 25 # 26 # 27 # 28 # 29 # 30 # 31 # 32
C.2 -3
Page 146
Input 24V DC Module (32 or 16 points)
Figure C2-3 and C2-4 illustrates two groups of inputs using the same power supply. Each group can work independently of the others; some groups may be sink and others source. The DC power supply for each group may be different if required. Typically just one DC power supply is used, daisy-chained from one group to the next. The first group of eight inputs is shown with devices "sinking" current through the DC Input module. The HOT terminal of the power supply must be connected to the module at DCSS1. The second group of eight inputs are shown with devices "sourcing" current through the input module. The COMMON terminal of the power supply must be connected to the module at DCSS2. In this example the DC power supply is the same for both groups. Figure C2-3. Connectors for Two Groups of Inputs (32 point module)
SWITCHING DEVICE DC Supply 0V
SCREW CONNECTIONS TERMINALS
DCIN1
V+
DCIN2
1 3
DCIN3 DCIN4 DCIN5
5
DCIN6 DCIN7
7
HOT
DCIN8 DCSS1
9
HOT
DCIN9
COMMON
DCIN10
SINK
11 13
DCIN11 DCIN12
15
DCIN13
COMMON
SOURCE
DCIN14 DCIN15
17
DCIN16
19
DCSS2 AA59-3290
C.2 -4
Page 147
Input 24V DC Module (32 or 16 points)
Figure C2-4. Connectors for Two Groups of Inputs (16 point module)
SWITCHING DEVICES DC Supply
CONNECTIONS
SCREW TERMINALS
1 V+
HOT
0V
DCSS1 DCIN1
3
SINK
DCIN2 DCIN3 COMMON
DCIN4
COMMON
DCSS2
HOT
DCIN5
5
7
9
DCIN6 DCIN7
SOURCE 11
DCIN8 AA38-0690
C.2 -5
Page 148
Input 24V DC Module (32 or 16 points)
Theory of Operation
Each input is guaranteed "on" at 14 to 30 VDC and guaranteed "off" at 0 to 5 VDC; polarity doesn't matter. Its on/off state is converted to a corresponding logic 1 or 0. This logic state is transmitted through the system bus to the CPU module, where the processor uses it as data in the ladder program. The logic side of the input is optically isolated from the field side. An LED in the upper section of the module indicates the logic state of each input. Each group is represented by a horizontal row of 4 LEDs. If you need to know whether voltage is present at the field side, use a voltmeter on the terminal screws. The shaded blocks in Figure C2-5 show the limits specified by the IEC. The lines show the maximum and minimum V/I of the inputs in this module. The voltage/ current curve in this graph shows that the input module is well within the IEC Type 1 limits. Figure C2-5. Input Characteristics Compared to IEC Standards
U IN VOLTS
MIN MAX
UHMAX 30 "ON" REGION
INPUT VOLTAGE
25 UNOM 24
20
UHMIN 15
(UTMAX )
TRANSITION REGION
10
ULMAX 5
(UTMIN )
0
"OFF" REGION
-5 .5 ITMIN
2 IH MIN
4
6
8
10
INPUT CURRENT
C.2 -6
12
14
15 I IN mAMPS IMAX AA40-0690
Page 149
Input 24V DC Module (32 or 16 points)
IMPORTANT Switching devices can sometimes have a leakage current that exceeds the ITmin (current allowed when off) of an input module. In order to use such a device, an impedance (typically, a resistor) needs to be used in parallel with the input. For example, some of the newer proximity switches use two wires instead of three. The third wire was used for a power or ground line. Without the third wire, the switch is easier to install. However, it requires more leakage current in the off state to power its internal circuitry. As a conservative estimate, use the following formula to calculate an external resistance value. It keeps the input voltage at or below 2.4V when the switching device is in the "off" state. 2.4V --------------------------------------------------------------- ≥ R Switch Leakage – 0.75mA If the switch leakage specification is ≤ 1.7 mA, then: 2.4V -------------------------------- ≥ 2.5KΩ 1.7 – 0.75mA Use a resistor less than or equal to 2.5 K Ω. Be sure that the wattage is adequate for the resistor when the switching device is in the "on" state remembering that: 2
V P = -----R
C.2 -7
Page 150
Input 24V DC Module (32 or 16 points)
Specification Table
Characteristic
Input 24V DC module specifications
Function
Monitors on/off states from DC voltage inputs
Part number
32 point 16 point
Field side connector
32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals
502-03605-00 502-03548-00
Input signals (exceed IEC standards) Nominal 24 VDC on, 0 VDC off, conforming to IEC Type 1 inputs per IEC 1131-2 (four groups of eight or four inputs) UH Max (max. allowed voltage)
30 VDC
IH Max (max. current @ 30 VDC)
7.5 mA
UL Min
Polarity independent
Guaranteed on
14 VDC
IH Min (min. current @ UH Min)
2.8 mA
Guaranteed off
5 VDC
IT Min (current allowed when off)
.75 mA
Time delay on
1 ms max.
Time delay off
1 ms max.
Protection of logic circuits
Optical isolation between the logic and field sides, 4000V peak
Indicator lights, input circuits
An LED indicates the logic state of each input
Indicator light, module
The DIAG LED goes OFF when the module passes power-on diagnostic tests
Logic side power requirements (typical)
32 point 29 mA @+5V 7 mA per energized input @+5V 16 point 2mA @+5V 7mA per energized input @+5V
Field side power dissipation, worst case
32 point 7.2W 16 point 3.6W
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
C.2 -8
Page 151
Input 24V DC Module (32 or 16 points)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.2 -9
Page 152
Input 24V DC Module (32 or 16 points)
NOTES
C.2 -10