C.1 - Output 24V DC Source Module (32 or 16 points) Introduction
The output 24V DC module sources voltage for individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in the following configurations. 1. 32 point 24V DC output module 2. 16 point 24V DC output module
32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. 32 point
OUTPUT 24 V DC
FB
DIAG
1
Figure C1-1. OUTPUT 24V DC source module 16 point
Name of module
OUTPUT 24 V DC
Diagnostic LED "Fuse blown" LED
FB
Name of module Diagnostic LED "Fuse blown" LED
DIAG
1 5
5
Indicator LEDs
9 13
Indicator LEDs
9 13
17 21 25 29
1
1
3
3
5
5
7
7 9 11 13
9
Screw terminal connector
11 13
Screw terminal connector
15 17
15 17
19
19
21
21
23
23
25
25 27 29 31 33 35 37 39
Door
Door
AA57-3290
AA30-0690
C.1 -3
Page 134
Output 24V DC Source Module (32 or 16 points)
Connections
A screw terminal connection is provided for each output and for each external power supply connection. The outputs are isolated in four groups of eight or four with two additional terminals per group for the DC HOT and COMMON. (See Figure C1-2.) The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in Chapter 1, a 24V DC supply was set up according to these guidelines. The DC power supply for each group of eight or four devices may be different if required. In most cases one power supply is daisy-chained to all groups. IMPORTANT Do not connect the DC HOT and COMMON to a group unless you plan to use one or more of its outputs.
C.1 -4
Page 135
Output 24V DC Source Module (32 or 16 points)
Figure C1-2. Screw Terminal Connection Assignments
3 5
DCOUT4 DCOUT5
Group 1
DCOUT2 DCOUT3
7
DCOUT6 DCOUT7
9
#1 #2 #3 #4 #5 #6 #7 #8
DCOUT8 DCCOM2
11 13
17
Group 2
15
DCOUT12 DCOUT13 DCOUT14 DCOUT15
#9 # 10 # 11 # 12 # 13 # 14 # 15 # 16
19
DCOUT16 DCCOM3
DCOUT3
21
3 5
23 25
DCOUT20 DCOUT21
Group 3
DCOUT19
27
DCOUT22 DCOUT23
29
# 24
DCOUT24 DCCOM4
# 17 # 18 # 19 # 20 # 21 # 22 # 23
DC output 1 DC output 3
DCOUT4
DC output 4
DCCOM2
DC COMMON
7
DCL2 DCOUT5
9
DC output 5 DC output 6
11
DC output 7 DC output 8
DCCOM3
DC COMMON
13
DCL3
15
DC output 9 DC output 10
17
DC output 11 DC output 12
DCCOM4
DC COMMON
19 21
DC output 13 DC output 14
23
DCOUT16 DCCOM4A
#6 #7
#9 # 10 # 11 # 12
DC HOT
DCOUT14 DCOUT15
#5
#8
DCOUT12
DCOUT13
#3
DC HOT
DCOUT10 DCOUT11
#2 #4
DCOUT8
DCOUT9
#1
DC HOT
DCL4
DCOUT18
DC COMMON
DC output 2
DCL3 DCOUT17
LED
DC HOT
DCOUT2
DCOUT7
DCOUT10 DCOUT11
DCOUT1
DCOUT6
DCL2 DCOUT9
1
DCL1
FUNCTION
Group 1
DCCOM1
1
DCL1 DCOUT1
SCREW CONNECTIONS TERMINALS
Group 2
LEDS
Group 3
DCCOM1
GROUPS
DC output 15 DC output 16
25
Group 4
SCREW CONNECTIONS TERMINALS
# 13 # 14 # 15 # 16
Optional diode protection AA32-1690
31
DCL4 DCOUT25
33
DCOUT27
35
DCOUT28 DCOUT29
37
DCOUT30 DCOUT31
39
DCOUT32
Group 4
DCOUT26
# 25 # 26 # 27 # 28 # 29 # 30 # 31 # 32
AA79-4890
C.1 -5
Page 136
Output 24V DC Source Module (32 or 16 points)
Each group has its own fuse. The "fuse blown" LED circuit is active for all groups that have a power supply connected. Connections for one group of outputs are illustrated in Figure C1-3 and C1-4. The common side of each load must be connected to the 0V terminal of the supply. This 0V terminal is connected to the SPG used by the system rack. Figure C1-3. Connections for One Group of Outputs (32 pt module)
LOADS DC Supply
CONNECTIONS
DCCOM1
V+
SCREW TERMINALS
1
DCL1
HOT
0V
DCOUT1
3
DCOUT2 DCOUT3
5
DCOUT4 DCOUT5
7
DCOUT6 DCOUT7 COMMON
9
DCOUT8 AA78-4890
Figure C1-4. Connections for one group of outputs (16 pt module)
LOADS DC Supply V+ 0V
SCREW CONNECTIONS TERMINALS DCCOM1
HOT
1
DCL1 DCOUT1
3
DCOUT2 DCOUT3 COMMON
5
DCOUT4
AA31-0690
C.1 -6
Page 137
Output 24V DC Source Module (32 or 16 points)
Theory of Operation
Each output point is a solid state switch rated at .4 A for the 32 point module and .75A for the 16 point module. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the device is powered. If the CPU sends a logic 0, the switch opens and power to the device is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. In addition, each output is protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. Protecting from an Inductive Load
Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the common of the DC power supply. When an output is energized, represented in Figure C1-4a by a closed switch, current passes through the load into the common line. When the output is de-energized, represented in C1-4b by an open switch, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. Each output in the Output 24V DC module has a diode through which reverse current can be safely routed. Figure C1-5 shows how the internal diode works with an inductive load. When the output is turned off the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts. The internal diode provides another path for current. This limits the peak reverse voltage across the load to less than 1 V. Every switch in the Output 24V DC module has this protection so you can connect an inductive load to any terminal.
C.1 -7
Page 138
Output 24V DC Source Module (32 or 16 points)
Figure C1-5. Diagram of Internal Protection for Inductive Loads
DC power supply 0V V+
DC power supply 0V V+
OUTPUT MODULE
OUTPUT MODULE DCL1
DCL1
DCCOM1
DCCOM1
Output switching device
INDUCTIVE LOAD
-
Output switching device
INDUCTIVE LOAD
+
+ DCOUT1
- DCOUT1 b) Output de-energized a) Output energized
AA33-0690
External Zener Diode on 16 Point Module
In some cases such as a fast-switching device, the energy from an inductive load may need to be discharged more quickly than the built-in diode allows. The fourth group of outputs on the 16 point module allows you to provide an optional path through an external zener diode. A zener diode gives a higher voltage return path than an ordinary diode does. This fourth group has the anode side of the clamping diodes brought out to allow for this quicker discharge. As shown in Figure C1-6 you can connect a zener diode (rated up to 30 V) externally, between the common of the fourth group of outputs and this extra terminal. That is, connect the cathode side of the zener to terminal 19, the common of the fourth group of outputs, and connect the anode to terminal 25. IMPORTANT You must use either a jumper or a zener diode between terminals #19 and #25 any time the fourth group of outputs is in use with inductive load(s).
C.1 -8
Page 139
Output 24V DC Source Module (32 or 16 points)
Figure C1-6. External Zener Diode for Fast-Switching Inductive Loads (Outputs 13 to 16 on the 16 point Module) LOADS
DC Supply V+ 0V
NAMES FOR TERMINALS
SCREW TERMINALS
DCCOM4 HOT
19
DCL4 DCOUT13
21
DCOUT14 DCOUT15 COMMON
Zener 23
DCOUT16 DCCOM4A
25
AA34-0690
Replacing a fuse
This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. Follow the procedure below to change a blown fuse. 1.
Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.
2.
Press down the latch at the top of the OUTPUT 24V DC module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.
3.
Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover.
C.1 -9
Page 140
Output 24V DC Source Module (32 or 16 points)
Figure C1-7. Positions of Fuses
DIAG LED "Fuse blown" LED
LEDs for the outputs
Fuse for the second group of outputs
Screw terminal connector
64 pin connector to rack Spare fuse
AA836-1091
4.
Identify the fuse that has blown, and use an insulated screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.
C.1 -10
5.
Replace the module cover, making sure that the top and bottom tabs are fully engaged.
6.
Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.
7.
Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and the FB LEDs should both be off.
Page 141
Output 24V DC Source Module (32 or 16 points)
Specification Table
Characteristic
Output 24V DC module specifications
Function
Sources an external DC supply to 16/32 loads
Part number
32 point 16 point
DC source requirements
Nominal 24V DC; range 5 to 32 VDC
Field side connector
32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of outputs
Four groups of 8 or 4 solid-state switches. Each group may use its own DC supply, or one supply may be daisy-chained. UL 508 spacing
Fuse per group of 8 switches
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; 32-point - each switch is rated at .4 A continuous 16 point - each switch is rated at .75 A continuous
Indicator lights, output circuits
An LED for each output
Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maximum ON
32 point 16 point
Surge current, maximum
32 point 2.5 A for 40 msec., every 2 seconds 16 point 5 A for 40 msec, every 2 seconds; fuse blows if this is exceeded
Response to scan loss
All outputs are reset to the OFF state
502-03640-02 502-03549-02
1.8 VDC @ .4 A 1.6 VDC @ .75A
C.1 -11
Page 142
Output 24V DC Source Module (32 or 16 points)
Logic side power requirements (typical)
1 mA @ +5V
Field side power dissipation, worst case (at 32 VDC)
15.8 W
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards:
32 point 25 mA per energized output @ +5V 16 point 23 mA per energized output @ +5V
EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information. UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
C.1 -12