Page 133

C.1 - Output 24V DC Source Module (32 or 16 points) Introduction

The output 24V DC module sources voltage for individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in the following configurations. 1. 32 point 24V DC output module 2. 16 point 24V DC output module

32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running. 32 point

OUTPUT 24 V DC

FB

DIAG

1

Figure C1-1. OUTPUT 24V DC source module 16 point

Name of module

OUTPUT 24 V DC

Diagnostic LED "Fuse blown" LED

FB

Name of module Diagnostic LED "Fuse blown" LED

DIAG

1 5

5

Indicator LEDs

9 13

Indicator LEDs

9 13

17 21 25 29

1

1

3

3

5

5

7

7 9 11 13

9

Screw terminal connector

11 13

Screw terminal connector

15 17

15 17

19

19

21

21

23

23

25

25 27 29 31 33 35 37 39

Door

Door

AA57-3290

AA30-0690

C.1 -3

Page 134

Output 24V DC Source Module (32 or 16 points)

Connections

A screw terminal connection is provided for each output and for each external power supply connection. The outputs are isolated in four groups of eight or four with two additional terminals per group for the DC HOT and COMMON. (See Figure C1-2.) The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the single point ground used for the system rack. Its power disconnect switch should be the same one used for the system rack. In the power distribution diagrams in Chapter 1, a 24V DC supply was set up according to these guidelines. The DC power supply for each group of eight or four devices may be different if required. In most cases one power supply is daisy-chained to all groups. IMPORTANT Do not connect the DC HOT and COMMON to a group unless you plan to use one or more of its outputs.

C.1 -4

Page 135

Output 24V DC Source Module (32 or 16 points)

Figure C1-2. Screw Terminal Connection Assignments

3 5

DCOUT4 DCOUT5

Group 1

DCOUT2 DCOUT3

7

DCOUT6 DCOUT7

9

#1 #2 #3 #4 #5 #6 #7 #8

DCOUT8 DCCOM2

11 13

17

Group 2

15

DCOUT12 DCOUT13 DCOUT14 DCOUT15

#9 # 10 # 11 # 12 # 13 # 14 # 15 # 16

19

DCOUT16 DCCOM3

DCOUT3

21

3 5

23 25

DCOUT20 DCOUT21

Group 3

DCOUT19

27

DCOUT22 DCOUT23

29

# 24

DCOUT24 DCCOM4

# 17 # 18 # 19 # 20 # 21 # 22 # 23

DC output 1 DC output 3

DCOUT4

DC output 4

DCCOM2

DC COMMON

7

DCL2 DCOUT5

9

DC output 5 DC output 6

11

DC output 7 DC output 8

DCCOM3

DC COMMON

13

DCL3

15

DC output 9 DC output 10

17

DC output 11 DC output 12

DCCOM4

DC COMMON

19 21

DC output 13 DC output 14

23

DCOUT16 DCCOM4A

#6 #7

#9 # 10 # 11 # 12

DC HOT

DCOUT14 DCOUT15

#5

#8

DCOUT12

DCOUT13

#3

DC HOT

DCOUT10 DCOUT11

#2 #4

DCOUT8

DCOUT9

#1

DC HOT

DCL4

DCOUT18

DC COMMON

DC output 2

DCL3 DCOUT17

LED

DC HOT

DCOUT2

DCOUT7

DCOUT10 DCOUT11

DCOUT1

DCOUT6

DCL2 DCOUT9

1

DCL1

FUNCTION

Group 1

DCCOM1

1

DCL1 DCOUT1

SCREW CONNECTIONS TERMINALS

Group 2

LEDS

Group 3

DCCOM1

GROUPS

DC output 15 DC output 16

25

Group 4

SCREW CONNECTIONS TERMINALS

# 13 # 14 # 15 # 16

Optional diode protection AA32-1690

31

DCL4 DCOUT25

33

DCOUT27

35

DCOUT28 DCOUT29

37

DCOUT30 DCOUT31

39

DCOUT32

Group 4

DCOUT26

# 25 # 26 # 27 # 28 # 29 # 30 # 31 # 32

AA79-4890

C.1 -5

Page 136

Output 24V DC Source Module (32 or 16 points)

Each group has its own fuse. The "fuse blown" LED circuit is active for all groups that have a power supply connected. Connections for one group of outputs are illustrated in Figure C1-3 and C1-4. The common side of each load must be connected to the 0V terminal of the supply. This 0V terminal is connected to the SPG used by the system rack. Figure C1-3. Connections for One Group of Outputs (32 pt module)

LOADS DC Supply

CONNECTIONS

DCCOM1

V+

SCREW TERMINALS

1

DCL1

HOT

0V

DCOUT1

3

DCOUT2 DCOUT3

5

DCOUT4 DCOUT5

7

DCOUT6 DCOUT7 COMMON

9

DCOUT8 AA78-4890

Figure C1-4. Connections for one group of outputs (16 pt module)

LOADS DC Supply V+ 0V

SCREW CONNECTIONS TERMINALS DCCOM1

HOT

1

DCL1 DCOUT1

3

DCOUT2 DCOUT3 COMMON

5

DCOUT4

AA31-0690

C.1 -6

Page 137

Output 24V DC Source Module (32 or 16 points)

Theory of Operation

Each output point is a solid state switch rated at .4 A for the 32 point module and .75A for the 16 point module. It turns on or off according to the logic state sent to it by the CPU. If the CPU sends it a logic 1, the switch closes and the device is powered. If the CPU sends a logic 0, the switch opens and power to the device is cut off. The CPU updates the logic state for each switch every time it scans the program. The logic side of the switch is optically isolated from the field side. An LED gives the logic state of each switch. If you need to know whether voltage is actually present at the field side, use a voltmeter on the terminal screws. Each group has its own protective fuse in series with the source to protect against current overload in case the outputs are shorted to ground. In addition, each output is protected with internal clamping diodes. Without clamping, high voltage transients (kickback) from inductive loads might damage the module. Protecting from an Inductive Load

Resistive loads can be connected to the module and controlled by the system with no precautions other than making sure they have a connection to the common of the DC power supply. When an output is energized, represented in Figure C1-4a by a closed switch, current passes through the load into the common line. When the output is de-energized, represented in C1-4b by an open switch, current stops. The state of the outputs is controlled by the CPU module. Inductive loads have an electrical "kickback" when current is stopped. This can damage or destroy the output switching device. Each output in the Output 24V DC module has a diode through which reverse current can be safely routed. Figure C1-5 shows how the internal diode works with an inductive load. When the output is turned off the inductive field collapses. This creates a reverse voltage across the load called "kickback" which tries to continue the current. The voltage is in series with the DC power supply. The combined voltage appears across the output switching device in the module. If this were the only path available, voltage across the device would peak at several hundred volts. The internal diode provides another path for current. This limits the peak reverse voltage across the load to less than 1 V. Every switch in the Output 24V DC module has this protection so you can connect an inductive load to any terminal.

C.1 -7

Page 138

Output 24V DC Source Module (32 or 16 points)

Figure C1-5. Diagram of Internal Protection for Inductive Loads

DC power supply 0V V+

DC power supply 0V V+

OUTPUT MODULE

OUTPUT MODULE DCL1

DCL1

DCCOM1

DCCOM1

Output switching device

INDUCTIVE LOAD

-

Output switching device

INDUCTIVE LOAD

+

+ DCOUT1

- DCOUT1 b) Output de-energized a) Output energized

AA33-0690

External Zener Diode on 16 Point Module

In some cases such as a fast-switching device, the energy from an inductive load may need to be discharged more quickly than the built-in diode allows. The fourth group of outputs on the 16 point module allows you to provide an optional path through an external zener diode. A zener diode gives a higher voltage return path than an ordinary diode does. This fourth group has the anode side of the clamping diodes brought out to allow for this quicker discharge. As shown in Figure C1-6 you can connect a zener diode (rated up to 30 V) externally, between the common of the fourth group of outputs and this extra terminal. That is, connect the cathode side of the zener to terminal 19, the common of the fourth group of outputs, and connect the anode to terminal 25. IMPORTANT You must use either a jumper or a zener diode between terminals #19 and #25 any time the fourth group of outputs is in use with inductive load(s).

C.1 -8

Page 139

Output 24V DC Source Module (32 or 16 points)

Figure C1-6. External Zener Diode for Fast-Switching Inductive Loads (Outputs 13 to 16 on the 16 point Module) LOADS

DC Supply V+ 0V

NAMES FOR TERMINALS

SCREW TERMINALS

DCCOM4 HOT

19

DCL4 DCOUT13

21

DCOUT14 DCOUT15 COMMON

Zener 23

DCOUT16 DCCOM4A

25

AA34-0690

Replacing a fuse

This module has four fuses, one for each group of outputs. Fuses are checked only for groups which have external power applied. If power is applied to a group in which the fuse is blown or missing, the FB LED on the module's upper segment lights up. The fuse is in series with the HOT line to the group, to protect the output switching device and the load. The fuse protects against a short circuit in an output device, but not against a sustained marginal overload current. See the specification table at the end of this section. Follow the procedure below to change a blown fuse. 1.

Turn off the main disconnect switch for the system rack and the external DC power supply to this module. Remove the screw terminal connector.

2.

Press down the latch at the top of the OUTPUT 24V DC module and pull it out of the rack. Lay it on a static-free surface, label side up. Ground yourself using an antistatic wrist strap before you open the module.

3.

Press the plastic tabs at the top and bottom of the module toward each other and lift off the module cover.

C.1 -9

Page 140

Output 24V DC Source Module (32 or 16 points)

Figure C1-7. Positions of Fuses

DIAG LED "Fuse blown" LED

LEDs for the outputs

Fuse for the second group of outputs

Screw terminal connector

64 pin connector to rack Spare fuse

AA836-1091

4.

Identify the fuse that has blown, and use an insulated screwdriver or fuse puller to remove it. Put a new fuse in its slot. The replacement must be a fast-acting 3A 250 VAC fuse. The following are recommended: Littlefuse 235-003 Bussman GMA-3 or an equivalent. For your convenience, there is an extra fuse in the lower front corner of the module.

C.1 -10

5.

Replace the module cover, making sure that the top and bottom tabs are fully engaged.

6.

Check the wiring to the devices to find why the fuse blew, and correct the situation before you continue running the program.

7.

Slide the module back in its slot, connect the screw terminal connector, and turn power back on. After the diagnostic tests run, the DIAG and the FB LEDs should both be off.

Page 141

Output 24V DC Source Module (32 or 16 points)

Specification Table

Characteristic

Output 24V DC module specifications

Function

Sources an external DC supply to 16/32 loads

Part number

32 point 16 point

DC source requirements

Nominal 24V DC; range 5 to 32 VDC

Field side connector

32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals

Protection of logic circuits

Optical isolation between the logic and field side

Grouping of outputs

Four groups of 8 or 4 solid-state switches. Each group may use its own DC supply, or one supply may be daisy-chained. UL 508 spacing

Fuse per group of 8 switches

Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm

Maximum current per group

2 A of continuous current for the group; 32-point - each switch is rated at .4 A continuous 16 point - each switch is rated at .75 A continuous

Indicator lights, output circuits

An LED for each output

Indicator light, module

A DIAG LED turns OFF when the module passes its diagnostic tests at power-on

Indicator light, fuses

A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse

Switch characteristics

Solid-state switches

Time delay on for resistive loads

30 µsec max

Time delay off for resistive loads

300 µsec max

Leakage current in off state

0.5 mA max

Switch voltage, maximum ON

32 point 16 point

Surge current, maximum

32 point 2.5 A for 40 msec., every 2 seconds 16 point 5 A for 40 msec, every 2 seconds; fuse blows if this is exceeded

Response to scan loss

All outputs are reset to the OFF state

502-03640-02 502-03549-02

1.8 VDC @ .4 A 1.6 VDC @ .75A

C.1 -11

Page 142

Output 24V DC Source Module (32 or 16 points)

Logic side power requirements (typical)

1 mA @ +5V

Field side power dissipation, worst case (at 32 VDC)

15.8 W

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards:

32 point 25 mA per energized output @ +5V 16 point 23 mA per energized output @ +5V

EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information. UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

C.1 -12