The text of a manual · part 17 of 60
PiC900 Hardware Manual: B.5 - Profibus Module
Pages 125 to 132 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 125
B.5 - Profibus Module Introduction
The PiC900 Profibus scanner module is an interface between the PiC and a Profibus network. The module contains an on-board processor, a Profibus compliant interface, and firmware that makes it act as the master to all nodes assigned to it on the network. Prior to initial operation, a file is generated with specific configuration information in an external PC. This file must be downloaded via the RS232 configuration port to the Profibus scannerProfibus module prior to initial operation. Two indicator LEDs (IN/OUT) are connected to this configuration port. Directly above the Profibus port are two LEDs that provide operation information; Network Status and Profibus Scanner Status. The DIAG LED goes on briefly while the diagnostic tests are running. Figure B5-1. Profibus Module Diagnostic LED Profibus DIAG IN OUT
Configuration Port LEDs
CNFG PORT
Network Status LED
Profibus Scanner Status LED
Profibus Port 9-pin D-sub Connector Open Door
Configuration Port RS232 Port 9-pin D Connector
B.5 -1
Page 126
Profibus Module
Connections
Profibus connections are illustrated in Figure B5-2. Up to 31 Profibus nodes, without repeaters, may be attached to the Profibus scanner. Up to 125 other Profibus nodes, using repeaters, may be attached to the Profibus scanner module. Figure B5-2. Profibus Connections
PiC CSM CPU
DEVIC
Profibus Node
Profibus Node
To Profibus Segment
Profibus Node
PC connected to RS232 port for downloading file generated with Giddings & Lewis Profibus configuration software.
To Profibus Segment
The Profibus Port
The Profibus port is on the front of the module near the center as shown in Figure B5-1. The pinout for the Profibus port is shown below:
B.5 -2
Pin #
Signal Name
1
Chassis ground
2 reserved
3 data +
4
Tx enable
5
Isolated ground
6 voltage plus
7 reserved
8 data -
9 reserved
Note: It is strongly recommended that you use Profibus Sub-D connectors wiht switchable (ON/OFF) termination, such as Siemans 6ES7 972-0BA11-0XA0 or 6ES7 972-0BB11-0XA0. Only use Profibus type A cable, such as Belden 3079A or Siemens 6XV1 830-0AH10.
Page 127
Profibus Module
The Configuration (RS232) Port
There is an RS232 port on the lower front of the module as shown in Figure B5-1. This is used to connect to a PC in order to download a file representing your Profibus network. Pin #
Signal Name
In/Out
2
Receive Data
In
3
Transmit Data
Out
5
Ground
In/Out
LEDs
The two configuration port LEDs and the two Profibus port LEDs are described below. Port
LED
Color
State
Definition
Profibus
Network status Green
OFF
Off-line
ON
On-line and connected to at least one node
ON
On-line but bus error present (baud rate or wiring problem)
OFF
No power or else reset asserted, interface closed
ON
Scanner OK and active (interface open)
Red
ON
Interface open, at least one slave faulted
Orange
ON
Configuration (download) mode
Red
Flickering
Data is being passed to the module
OFF
No data to the module
Flickering
Data is being passed from the module
OFF
No data from the module
Red Scanner status Green
Configuration IN
OUT
Red
B.5 -3
Page 128
Profibus Module
Theory of operation
The Profibus scanner module provides a memory image of the nodes (slaves) connected to a Profibus network. It is this memory image that is controlled by your LDO created in PiCPro. The module’s on-board processor continually transfers data between this memory image and the actual Profibus nodes. Communication between the Profibus module and the nodes can be set between 9600 baud (1200m max.) and 12M baud (100m max.) The baud rate, the relationship between the memory image and specific data in each node, and other parameters are established with configuration software run in an external PC. This configuration software generates two files. One file is downloaded to the Profibus module through its RS232 serial port. The other file is used by PiCPro to establish the relationship between the memory image and the declared variables in the LDO. To ensure that a given location in the memory image is connected to a variable in the LDO and to the corresponding data in the Profibus node, the same tag name or label must be used. For example, when running the configuration software, PROX_SW1 could be used as the name for the boolean bit representing a Profibus proximity switch’s logic state. The name PROX_SW1 must also be used for the corresponding variable in your LDO.
IMPORTANT Additional information about Profibus can be obtained from www.profibus.com.
NOTE The G&L Prorfibus configuration software (G&L Part No. M.1300.7794) is required to configure the Profibus scanner (within the Profibus module) for the devices on the associated network.
B.5 -4
Page 129
Profibus Module
Specification Table
Characteristics
Profibus Module Specifications
Function
Interfaces( acts as DP Master - Class 1), to a Profibus network with up to 125 other nodes, using repeaters
Part number
M.1300.7050
Profibus Port
Phoenix style 5-pin male connector
Configuration Port
RS232 interface
Logic side power requirements (typical)
275 mA @ 5 V
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
B.5 -5
Page 130
Profibus Module
NOTES
B.5 -6
Page 131
Appendix C - Discrete I/O Modules