PiC900 Hardware Manual: D.2 - Input Resolver Module (2, 4 channel)

Pages 247 to 254 of 508, from PiC900 Hardware Manual

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 247

D.2 - Input Resolver Module (2, 4 channel) Introduction

The input resolver module can interface to two or four independent resolvers (or equivalent transducers). Information from the resolvers is used to update two or four separate position counters and latches within the module. For each channel, the module sends out two sine waves 90° out of phase with each other and receives a signal whose phase represents the angular position of the resolver. This input signal is used to update a 24-bit counter. This module can be programmed to "latch" (store) the counter value when a signal is received by the fast input for that channel. An LED in the upper section of the module goes on when the fast input for each channel is energized. The DIAG LED goes on briefly while the diagnostic tests are running. Figure D2-1. INPUT RESOLVER module (4 CH)

INPUT RESOLVER

Name of module Diagnostic LED

DIAG

IN1

Indicator LEDs for fast inputs

IN2 IN3 IN4

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25 27 29 31 33 35 37 39

Door

AA83-1790

D.2 -1

Page 248

Input Resolver Module (2, 4 channel)

Connections

All signals to the resolver module must come to its screw terminal connector through shielded twisted pair wires. These wires must be protected against electrical noise because of the speed and/or voltage levels of the signals transmitted through them. See the discussion in the Hardware chapter on "Preventing electrical noise in data lines". Each input resolver channel has four signal pairs, each of which has two screw terminal connections. The signals are: RPO output QPO output FDBK input 24 VDC fast input In addition the module has eight screw connections for terminating the shields. All eight are connected inside the module so they are the same point electrically.

IMPORTANT If the 24 VDC fast input is used, its power supply common must be connected to the SPG. Figure D2-2 shows the assignments for all the screw terminal connections on the module. To make the diagram more readable, The shielded twisted pair wires are shown with transparent shields. • Channel 3 shows how a potentiometer can be wired to the module. • The shielded twisted pair wires are shown grounded only for channel 4. In an actual application, every cable shield must be grounded. • The fast inputs for channels 1 and 2 are shown in source configuration; that for channel 4 is shown in sink configuration. •

D.2 -2

Page 249

Input Resolver Module (2, 4 channel)

Figure D2-2. Connections for the Input Resolver Terminals

FDBK

1

FDBK (R1) FDBK (R2) FDBK (S1) RPO RESOLVER (S3) RPO (S2) QPO (S4) QPO

RPO

QPO

COLOR KEY R1 RED/WHITE R2 YELLOW/WHITE S1 RED S3 BLACK S2 YELLOW S4 BLUE

3

RPO

CHANNEL

1 5

QPO FDBK

7

FDBK

(R1) FDBK (R2) FDBK (S1) RPO RESOLVER (S3) RPO (S2) QPO

RPO

9

RPO

(S4) QPO

QPO

CHANNEL

2 11

QPO FDBK

13

RPO

15

QPO

17

FDBK

19

POTENTIOMETER MIN

CHANNEL

3

MAX

FDBK (R1) FDBK (R2) FDBK (S1) RPO RESOLVER (S3) RPO (S2) QPO (S4) QPO

RPO

21

RPO QPO

CHANNEL

4 23

QPO SHIELD

25

SHIELD SHIELD

27

SHIELD

24 VDC POWER SUPPLY 0V TO SPG

24 V

SHIELD

29

SHIELD FAST INPUT SWITCHES

SHIELD

31

SHIELD FAST INPUT

33

CHANNEL

35

CHANNEL

FAST INPUT FAST INPUT

1 2

FAST INPUT

37

CHANNEL

3 FAST INPUT FAST INPUT

39

CHANNEL

4

D.2 -3

Page 250

Input Resolver Module (2, 4 channel)

IMPORTANT If a channel is not being used, tie its FDBK input to its RPO output to ensure proper operation. See Figure D2-3. Figure D2-3. Unused Channel Connection

FDBK (R1) FDBK (R2) FDBK (S1) RPO RESOLVER (S3) RPO (S2) QPO (S4) QPO

1

FDBK RPO

3

RPO QPO

1 5

QPO FDBK

CHANNEL

7

Connect FDBK to RPO on any unused channel.

FDBK RPO

9

RPO QPO

11

CHANNEL

2

QPO

AA1118-3292

Resolvers

A resolver (Figure D2-4) is a servo feedback device which provides absolute position over one electrical revolution. It receives RPO (reference phase output) and QPO (quadrature phase output) signals from the interface module. RPO and QPO signals are sine waves 90° out of phase with each other. They energize two stator coils positioned at 90° to each other. The stator coils induce a sine wave signal called FDBK (feedback) in the rotor coil. The phase of this signal, with respect to RPO, depends on the rotor coil's position.

D.2 -4

Page 251

Input Resolver Module (2, 4 channel)

R2

R1

Figure D2-4. Diagram of a Resolver

QPO ck ba ed Fe

S2 S4

RPO

S1

S3 AA85-1790

The recommended resolver has a part number in the specification sheet at the end of this section. Other resolvers may be used, if they conform to the interface module specifications. Theory of Operation

The module sends out two sine wave signals, RPO and QPO. These signals have the same voltage amplitude and frequency but are 90° out of phase. The module then receives a FDBK sine wave signal whose phase is a measure of the angular rotation of the resolver. The phase information is used to increment or decrement an internal 24-bit up/ down counter. A phase shift of 360° corresponds to 4,000 counts of resolution, so one count represents 5.4 arc-minutes of rotation of the resolver. The value in the counter thus represents the current position of the resolver. In addition to the counter, there is a 24-bit latch associated with each resolver interface. This module can be programmed so that the counter value is latched or stored when a fast 24 VDC input pulse is received for that channel. Each of the four 24-bit latches has a fast 24 VDC input associated with it. Each input is optically isolated. This input is typically used for referencing or synchronization purposes. Fast input characteristics include: The detection of a signal occurs faster than it does for the DC inputs in other modules, due to less filtering. Because of this there is also less noise immunity. • The response to a fast input signal is independent of ladder scan time. The module can be programmed to latch a position count as soon as this input is detected. •

D.2 -5

Page 252

Input Resolver Module (2, 4 channel)

Specification Table

Characteristic

Input Resolver module specifications

Function

Measures the position of a transducer that accepts a 2phase quadrature excitation, such as a resolver or potentiometer

Part number

4 ch 502-03552-02

Field side connector

40 pin card edge connector, screw terminals

Excitation method

2-phase quadrature for control transformer type of resolver

Excitation frequency

2 ch 502-03552-22

2 KHz

RPO and QPO outputs Output voltage Current per output channel, max. Resolver transformer ratio

16 VP-P (5.7 VRMS) 4ch 5 mA RMS (14 mA p-p) 2ch 10mARMS (20 mA p-p)

.5 to 1.0

Resolution, resolver

4000 Feedback Units (FUs) per electrical revolution

Resolution, potentiometer

1000 Feedback Units (FUs) per electrical revolution

Accuracy at constant temperature

± 20 arc minutes

Accuracy over temperature range ± 45 arc minutes Electrical velocity, max.

15000 RPM (1M FU/Sec.)

Cable length, max.

200 ft.

Stored position value range

24-bit up/down counter 24-bit latch

Fast input

Nominal 24 VDC

Reverse polarity protection

YES

Voltage max.

30 VDC

Guaranteed on

15 VDC

Guaranteed off

5 VDC

Input impedance

2.7 K

On/off time, max.

50 µs

Indicator lights, fast inputs

LED is lit when current flows into the input.

Indicator light, module

D.2 -6

DIAG LED goes off when the module passes its diagnostic tests

Page 253

Input Resolver Module (2, 4 channel)

Logic side power requirements (typical for 4 ch)

473 mA @ 5V 133 mA @+15V 20 mA @-15V 14 mA per energized input @ +15V 14 mA per energized input @ -15V 12 mA per fast input

Logic side power requirements (typical for 2 ch)

296 mA @ 5V 105 mA @ +15V 16 mA @ -15V 14 mA per energized input @ +15V 14 mA per energized input @ -15V 13 mA per fast input

Field side power dissipation, worst case

4 ch

1.4 W

2 ch

.7W

Recommended resolver

Giddings & Lewis part number 501-98409-00 Harowe 11BRW 300-F-1/10

Other suggested resolvers

Clifton 11BHW-0IE/A004 Kearfott CR41095050

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information. D.2 -7

Page 254

Input Resolver Module (2, 4 channel)

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

D.2 -8

Four shocks per axis (15g/11 msec)