The text of a manual · part 32 of 60
PiC900 Hardware Manual: D.4 - Servo Module Encoder with Analog Input, pages 263 to 271
Pages 263 to 271 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 263
D.4 - Servo Module Encoder with Analog Input Introduction
The servo encoder module provides: •
2 analog output channels
•
4 analog input channels
•
3 encoder input channels
•
3 fast inputs
An LED goes on when the fast input for each encoder channel is energized. The DIAG LED goes on briefly while the diagnostic tests are running. Figure D4-1. Servo Encoder Module
SERVO ENCODER
Name of module Diagnostic LED
DIAG
IN1
Fast input LEDs
IN2 IN3
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25 27 29 31 33 35 37 39
Door
AG11-0493
D.4 -1
Page 264
Servo Module Encoder with Analog Input
Connections
All signals to the module must come to the screw terminal connectors through shielded twisted pair wires. Shielded twisted pair wires are used to connect: •
Each analog output channel to a receiving device.
•
All analog input signals to the module.
•
All encoder signals to the module.
•
All fast input signals to the module.
These wires must be protected against electrical noise because of the speed and/or voltage levels of the signals transmitted through them. See the discussion on "Preventing electrical noise in data lines" in the Hardware chapter.
IMPORTANT One end of the shield from the twisted pair wire must be connected to chassis ground. Any power supplies used must be connected to the Single Point Ground. Figure D4-2 shows the assignments for all the screw terminal connections on the module.
D.4 -2
Page 265
Servo Module Encoder with Analog Input
Figure D4-2. Connections for the Servo I Encoder Module Terminals SCREW TERMINALS CONNECTIONS
CONNECTIONS
Analog Output
An Out Ch 1An Out Ch 2-
3
An Out Ch 2+
Analog Output
An Out Ch 1+ 1
An In Ch 1+ An In Ch 2+
5
An In Ch 2-
7 Ch 1 250 Ω resistor
Ch 2 250 Ω resistor
9 An In Ch 3+
An In Ch 4+
11
An In Ch 4-
13
Analog Input
Analog Input
An In Ch 1-
An In Ch 3Ch 3 250 Ω resistor Ch 4 250 Ω resistor
15
Enc Ch 1 A
17
Enc Ch 1 B
19
Enc Ch 1 Index
21
Enc Ch 2 A
23
Enc Ch 2 B
25
Enc Ch 2 Index
27
Enc Ch 3 A
29
Enc Ch 3 B
31
Enc Ch 3 Index
33
Ch 1- Fast Input
35
Ch 2- Fast Input
37
Ch 3- Fast Input
39
Enc Ch 1 A Enc Ch 1 B
Enc Ch 1 Index
Enc Ch 2 A
Encoder Input
Enc Ch 2 Index Enc Ch 3 A
Encoder Input
Enc Ch 2 B
Enc Ch 3 B
Enc Ch 3 Index
Ch 2+ Fast Input
Ch 3+ Fast Input
Fast Input
Fast Input
Ch 1+ Fast Input
AG09-0393
D.4 -3
Page 266
Servo Module Encoder with Analog Input
Analog Output Connections
You may connect the differential type output from this module to a single-ended or differential input device. Figure D4-3 shows the difference between the two types of connections. Note that one wire in the twisted pair is connected to the 0 V terminal on the single-ended receiving device. This 0V terminal must be referenced to the SPG through the device's ground connection. Figure D4-3. Differential and Single-Ended Receiving Devices Receiving Device
Analog Out Section
Differential input device
CH1
CH1
GND
To SPG
GND
CH1 CH2
CH2
0V
Single-ended input device
To SPG
D.4 -4
1
Channel 1
3
Channel 2
CH1
CH2
Page 267
Servo Module Encoder with Analog Input
Analog Input Connections
Each input channel has three connection pins. The signals are: + voltage input - voltage input 250 ohm current sense resistor for 0/20 mA and 4/20 mA applications When connecting an analog voltage output device to the module, the positive wire of the twisted pair goes to the + screw terminal and the negative wire goes to the screw terminal. Figure D4-4 illustrates these connections for channel one. Notice that no connection is made to the screw terminal with the internal 250 Ω resistor when connecting a voltage source device. Figure D4-4. Voltage Input Connections Analog Input Section Voltage + signal source
-
Ch 1 +
5
Ch 1 -
7
Ch 1 250 ohm Resistor
9
Channel 1
To SPG 11 13 15
D.4 -5
Page 268
Servo Module Encoder with Analog Input
When using a 0 to 20 mA or 4 to 20 mA current output device, the positive wire of the twisted pair is connected to the + input and the negative wire is connected to the 250 Ω resistor input. A jumper is placed between the - input and the 250 Ω resistor input as shown in Figure D4-5 (from pin 8 to pin 10 for channel 2). This connects a 250 Ω internal resistor across the input. Figure D4-5. Current Input Connections (0 to 20 or 4 to 20 mA)
Analog Input Section
Power + supply
-
5
Current signal + source
Ch 2 +
0 to 20 or 4 to 20 mA
Ch 2 -
7 9
To SPG
Ch 2 250 ohm Resistor
11 13 15
D.4 -6
Page 269
Servo Module Encoder with Analog Input
An alternative method of connecting a two wire 4 to 20 mA current device is shown in Figure D4-6. Place a jumper between the - input and the 250 Ω resistor input. Figure D4-6. Current Input Connections (4 to 20 mA) Current signal source
Output
+ Input from power supply
Analog Input Section 5 Ch 2 +
Power + supply
Ch 2 -
-
7 9
Ch 2 250 ohm Resistor
11
To SPG 13 15
D.4 -7
Page 270
Servo Module Encoder with Analog Input
Figure D4-7 illustrates an example of wiring an external potentiometer to the module using twisted pair wire. For this example, set up the channel initialization function (A_INCHIT) in software for 5 V unipolar with a filter of 100 ms. The 5 V power supply output voltage adjustment can be set for the maximum potentiometer output value. For example, the supply could be adjusted until the VALU output of the analog input channel read function (A_INCHRD) reads 4095 with the pot at its maximum position. Figure D4-7. Adding an External Potentiometer Analog Input Section 5Volt + Adjustable Regulated Power supply -
5
1K to 50K Pot
Ch 2 + Ch 2 -
7 9
To SPG
Ch 2 250 ohm Resistor
11 13 15
D.4 -8
Page 271
Servo Module Encoder with Analog Input
Encoder Connections
Each encoder channel has four signal pairs, each of which has two screw terminal connections. The signal pairs are: encoder input A encoder input B index input 24 VDC fast input Encoder Drivers
Information from the encoders is used to update three separate position counters and latches within the module. For each channel, a 24-bit counter is incremented or decremented based on signals it receives from the A and B outputs of an encoder. The counter value can be latched (stored) if the module receives either an "index" signal from the encoder or a 24 VDC "fast" input signal. Acceptable drivers provided by encoder manufacturers include: Differential voltage drivers
75183 8830 75114 9614 7513 26LS31
Single-ended open collector drivers
7406
339 type output devices will not work with the module because their output current level is too low.
NOTE Encoders with differential drivers are strongly recommended. They provide better noise immunity and capability for the module to detect "loss of feedback." See the section in the Hardware chapter on "Preventing electrical noise in data lines" for a comparison of signals from differential and single-ended drivers.
D.4 -9