Page 281

D.5 - Servo Module Encoder Introduction

Depending on the model you have, the Servo encoder module provides: •

4, 3, or 2 analog output channels

•

3, 2, or 1 encoder input channels

•

3, 2, or 1 fast input

An LED goes on when the fast input for each encoder channel is energized. The DIAG LED goes on briefly while the diagnostic tests are running. Figure D5-1. Servo Encoder Module

SERVO ENCODER

Name of module Diagnostic LED

DIAG

IN1

Fast input LEDs

IN2 IN3

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25 27 29 31 33 35 37 39

Door

AG11-0493

D.5 -1

Page 282

Servo Module Encoder

Connections

All signals to the module must come to the screw terminal connectors through shielded twisted pair wires. Shielded twisted pair wire is used to connect: •

Each analog output channel to a receiving device

•

All encoder signals to the module

•

All fast input signals to the module

These wires must be protected against electrical noise because of the speed and/or voltage levels of the signals transmitted through them. See the discussion on "Preventing electrical noise in data lines" in the Hardware chapter. The module has eight screw terminal connections for terminating the shields. All eight are connected internally to SPG. The shield at the device end of the cable is not connected. Figure D5-2 shows the assignments for all the screw terminal connections on the module.

D.5 -2

Page 283

Servo Module Encoder

Figure D5-2. Connections for the Servo Encoder Module Terminals SCREW TERMINALS CONNECTIONS

CONNECTIONS

An Out Ch 1-

1

An Out Ch 2-

3

An Out Ch 3-

5

An Out Ch 4-

7

Shield

9

An Out Ch 2+ An Out Ch 3+

An Out Ch 4+

Analog Output

Analog Output

An Out Ch 1+

Shield Shield Shield

11 Shield

Shield

13

Shield

15

Enc Ch 1 A

17

Enc Ch 1 B

19

Shield Enc Ch 1 A Enc Ch 1 B

Enc Ch 1 Index Enc Ch 1 Index

21 Enc Ch 2 A 23

Enc Ch 2 B

25

Enc Ch 2 Index

27

Enc Ch 3 A

29

Enc Ch 3 B

31

Enc Ch 3 Index

33

Ch 1- Fast Input

35

Ch 2- Fast Input

37

Ch 3- Fast Input

39

Encoder Input

Enc Ch 2 B Enc Ch 2 Index Enc Ch 3 A

Encoder Input

Enc Ch 2 A

Enc Ch 3 B Enc Ch 3 Index

Ch 2+ Fast Input

Fast Input

Fast Input

Ch 1+ Fast Input

Ch 3+ Fast Input

AG08-0393

D.5 -3

Page 284

Servo Module Encoder

Analog Output Connections

You may connect the differential type output from the analog output section to a single-ended or differential input device. Figure D5-3 shows the two types of connections. Note that one wire in the twisted pair is connected to the 0 V terminal on the single-ended receiving device. This 0 V terminal must be referenced to the SPG through the device's ground connection. Figure D5-3. Differential and Single-Ended Receiving Devices

Receiving Device

Analog Out Section

Differential input device

CH1

CH1

GND

To SPG

CH1 CH2

GND

1

Channel 1

3

Channel 2

CH1

CH2

0V

Single-ended input device

CH2

5

7

To SPG

9 11 13

Shields

15

Encoder Connections

Each encoder channel has four signal pairs, each of which has two screw terminal connections. The signal pairs are: encoder input A encoder input B index input 24 VDC fast input

D.5 -4

Page 285

Servo Module Encoder

IMPORTANT The power supply to the encoder (or signal source device) must have its common connected to the Single Point Ground. If the 24 VDC "fast" input is used, its power supply common must also be connected to the Single Point Ground. Encoder Drivers

Information from the encoders is used to update four separate position counters and latches within the module. For each channel, a 24-bit counter is incremented or decremented based on signals it receives from the A and B outputs of an encoder. The counter value can be latched (stored) if the module receives either an "index" signal from the encoder or a 24 VDC "fast" input signal. Acceptable drivers provided by encoder manufacturers include: Differential voltage drivers

75183 8830 75114 9614 7513 26LS31

Single-ended open collector drivers

7406

339 type output devices will not work with the Input encoder module (4 ch) because their output current level is too low.

NOTE Encoders with differential drivers are strongly recommended. They provide better noise immunity and capability for the module to detect "loss of feedback." See the section in the Hardware chapter on "Preventing electrical noise in data lines" for a comparison of signals from differential and single-ended drivers. If the encoder has differential output drivers as shown in Figure D5-4, the three encoder outputs are paired: A and A B and B index and index

D.5 -5

Page 286

Servo Module Encoder

Figure D5-4. Wiring from an Encoder with Differential Drivers

9 VDC 55VDC ENCODER ENCODER POWER POWER SUPPLY SUPPLY

11

0V +V

13

Encoder Input Section TO SPG

15 17

A

-- ++ AA AA B B B index

ENCODER index

Shields

A

19

B B INDEX

Channel 1

21

INDEX

If an encoder has single-ended drivers, there are three single outputs: A, B, and index. Each output is referenced to the + V terminal of the encoder power supply. See Figure D5-5. Figure D5-5. Wiring from an Encoder with Single-Ended Drivers Encoder Input Section 9 5 VDC ENCODER POWER SUPPLY

11

0V +V

13

Shields

15 To SPG

A

-- ++

17

A AA A B B

ENCODER

B

19

B index INDEX INDEX

D.5 -6

21

Channel 1

Page 287

Servo Module Encoder

IMPORTANT The minimum width signal that can be accepted by the encoder section is 0.6 µ seconds. The signal at output A or B from the encoder has a frequency that is the product of the resolution of the encoder in pulses (lines) per revolution and the speed of the encoder in revolutions per second. Thus an encoder that generates 2,000 pulses (lines) per revolution and rotates at 10 revolutions per second generates 20,000 pulses (lines) per second. In a quadrature type encoder, the interface module would supply 80,000 Feedback Units per second. The fast input is connected as shown in Figure D5-6. Figure D5-6. Fast Input Connections

9 11 Shields 13 24 VDC POWER SUPPLY

15

Fast Input Switches

0V 24 V

Source

Fast Input Section FAST INPUT

35

FAST INPUT FAST INPUT

TO SPG

37 FAST INPUT

Sink

Channel 1 Channel 2

39

Incremental encoders

An incremental encoder is a position transducer. It transmits quadrature or pulse type signals through its "A" and "B" outputs with a frequency proportional to the rotational velocity of its shaft. It transmits a pulse through its index output once per revolution of the device. There are two types of incremental encoders, quadrature and pulse. Giddings & Lewis recommends quadrature type encoders, which are the most commonly used. D.5 -7

Page 288

Servo Module Encoder

A quadrature encoder sends square wave type signals. When the shaft rotates at a constant velocity, the A and B outputs are square waves and are at the same frequency. However they are out of phase with each other by 90°. When the encoder shaft rotates in one direction, each A pulse leads the corresponding B pulse by 90°. When it rotates the other direction each A pulse lags its B pulse by 90°. The signals illustrated in Figure D5-7 indicate that the encoder shaft rotates in one direction at first. Its speed of rotation decreases to 0 and then it starts rotating the other direction. The signals are shown as differential. A is the inverse of the signal A and B is the inverse of signal B. Figure D5-7. Signals Transmitted by a Quadrature Encoder with Differential Outputs ROTATION SPEED

OUTPUT

0 A A

B B AA71-2290

A pulse encoder sends pulses through output A for one direction of its shaft rotation, and output B for the other direction. When the shaft is not rotating, no pulse is generated. The signals illustrated in Figure D5-8 indicate that the encoder shaft rotates in one direction at first. Its speed of rotation decreases to 0 and then it starts rotating the other way. The signals are shown as differential, with the inverse of signal A and the inverse of signal B. A pulse encoder may alternate signals at its two outputs, but it cannot send signals from both outputs at the same time. Figure D5-8. Signals transmitted by a pulse encoder with differential outputs

OUTPUT

ROTATION SPEED 0

A A

B B AA70-1690

Analog Output Theory of Operation

The CPU sends the analog output section a 16-bit digital word for each analog output channel used. Each digital word is converted to a corresponding voltage within the range of ±11 V. The voltage is buffered and brought out to a pair of screw terminal connections as a differential type voltage output. This output is less subject to interference from electrical noise than a single-ended output would be. D.5 -8

Page 289

Servo Module Encoder

You can adjust each analog output channel in software for offset adjustments, gain scaling, and unipolar outputs. For safety reasons, all outputs are automatically reset to 0 V when a scan loss condition occurs. Encoder Theory of Operation

The encoder section uses differential type inputs to interface with up to three independent incremental encoders. These inputs are optically isolated and current limited. •

From a quadrature type, the maximum input frequency is 250,000 lines per second, which results in 1,000,000 Feedback Units (FUs) per second in the encoder module. Figure D5-9. Counting Quadrature Pulses

A B

•

The module counts positive and negative transitions at both channel A and channel B. One quadrature cycle in this case gives 4 Feedback Units.

From a pulse type, the module can accept up to 500,000 pulses per second at either input.

There is a 24-bit up/down counter on the module. It is incremented or decremented in accordance with the counting mode selected. There is also a 24-bit latch associated with each encoder channel. The module can be programmed so that the counter value is "latched" or stored under one of these conditions: an index pulse from the encoder • a positive or negative transition of the fast input • the next index pulse after the required transition of the fast input •

Each of the four 24-bit latches has a fast 24 VDC input associated with it. Each input is optically isolated. This input is intended to receive a signal from a device other than an encoder. It is typically used for referencing or synchronization purposes. Fast input characteristics include: the detection of a signal occurs faster than it does for the DC inputs in other modules, due to less filtering. Because of this there is also less noise immunity. • the response to a fast input signal is independent of ladder scan time. The module can be programmed to latch a position count as soon as this input is detected. •

D.5 -9

Page 290

Servo Module Encoder

Specification Table

Characteristic

Servo module encoder specifications

Function

Converts a 16-bit digital word into a ±11V analog output signal for each of two channels Counts pulses from up to three encoders Latches the counter value at an index or 24 VDC input event

Part number

Logic side power requirements (typical)

502-03840-04 502-03840-24 502-03840-44

4 Analog Outputs/3 Encoder Inputs 3 Analog Outputs/2 Encoder Inputs 2 Analog Outputs/1 Encoder Input

413 mA @ +5V 55 mA @ +15V 51 mA @ -15V Analog Output 1 mA per energized output 11 mA per energized output 11 mA per energized output

@ +5V @ +15V @ -15V

Encoder 21 mA per energized input 12 mA per fast input

@ +5V @ +5V

Field side connection

40 pin card edge connector, screw terminals

Field side power dissipation, worst case

7.4 W

Indicator light, module

DIAG LED goes off after the module passes its diagnostic tests

Indicator light, fast inputs

LED is lit when current flows into the fast input

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

D.5 -10

Page 291

Servo Module Encoder

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Analog Output section (4, 3, or 2 ch)

Resolution

16 bits, or 65536 steps over the full output range

Output voltage characteristics Nominal voltage range

± 11 VDC

Voltage accuracy @ 11 V

± 5%

Output current, max. @ ±10V

± 10 mA

Output update time increment

32 µsec

Output voltage after power up

0 V ± 20 mV

Response to "scan loss"

All outputs reset to 0 V ± 20 mV

Output ripple

< 10 mVRMS at 30 KHz

Short circuit protection

Current limited outputs

Response to scan loss

All outputs are reset to the OFF state

D.5 -11

Page 292

Servo Module Encoder

Encoder Input section (3, 2, or 1 ch)

Input Encoder (A, B, and index)

Differential or single ended; differential recommended

Guaranteed on, min

2.5 VDC @ 2.5 mA

Input voltage, max

7 VDC

Input current, max

22 mA @ 7 VDC

Signal pulse width, min

.6 µs(600 ns)

Quadrature signal frequency, max 250 KHz for A or B input (1 M FU count rate) Pulse encoder signal frequency, max

500 KHz for A or B input (500 KFU count rate)

Encoder device

1. Quadrature type incremental encoder (recommended) 2. Pulse type incremental encoder

Stored position value range

24-bit up/down counter 24-bit latch

Fast input

Nominal 24 VDC, switched externally to the module Active high or low Reverse polarity protected

Voltage max

30 VDC

Guaranteed on

15 VDC

Guaranteed off

5 VDC

Input impedance

2.7 K

On/off time, max

50 µs

Cable length, max

200 ft. @ 250 KHz and 45° quad error (with differential driver)

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

D.5 -12

Four shocks per axis (15g/11 msec)