Page 293
D.6 - Output Stepper Module (2, 4, or 8 channel) Introduction
The output stepper motor control module (SMCM) can control up to eight stepper drives. The maximum step rate is one million steps per second. An external power supply (4.5 VDC to 20 VDC) is required for operation. Commands and control data are sent to the module, and status and position information are received from the module, via software. The DIAG LED goes on briefly while the diagnostic tests are running. Figure D6-1. OUTPUT STEPPER Module (2, 4, 8 ch)
OUTPUTSTEPPER
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13
Screw terminal connector
15 17 19 21 23 25 27 29 31 33 35 37 39
Door
AA854-2491
D.6 -1
Page 294
Output Stepper Module (2, 4, or 8 channel)
Connections
A screw terminal connection is provided for each output and for the external power supply connection. (See Figure D6-2.) The outputs are optically isolated. (See Figure D6-3.) The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the rack's single point ground. The power disconnect switch should be the same one used for the Central Service Module. In the power distribution diagrams in the Hardware chapter, a DC supply was set up according to these guidelines. The external DC supply can be provided by any combination of the following: •
The stepper drive
An external DC supply daisy-chained to several channels • Separate external DC supplies for individual channels •
D.6 -2
Page 295
Output Stepper Module (2, 4, or 8 channel)
Figure D6-2. Screw terminal connection assignments
CONNECTIONS
SCREW TERMINALS
CONNECTIONS CH 1 +V INPUT
CH 2 +V INPUT
1
CH2 STEP/CW
3
CH 2 DIRECTION/CCW
5
CH 2 +V COMMON
7
CH 1 STEP/CW
CH 1 DIRECTION/CCW
Channel 2
Channel 1
CH 1 +V COMMON
SHIELD SHIELD
9 CH 3 +V INPUT
CH 4 +V INPUT
11
CH 4 STEP/CW
13
CH 4 DIRECTION/CCW
15
CH 4 +V COMMON
17
CH 3 STEP/CW
CH 3 DIRECTION/CCW
Channel 4
Channel 3
CH 3 +V COMMON
SHIELD SHIELD
19
CH 6 +V INPUT
21
CH 6 STEP/CW
23
CH 6 DIRECTION/CCW
25
CH 5 +V INPUT
CH 5 STEP/CW
CH 5 DIRECTION/CCW
Channel 6
Channel 5
CH 5 +V COMMON CH 6 +V COMMON
27
SHIELD
29
CH 8 +V INPUT
31
CH 8 STEP/CW
33
CH 8 DIRECTION/CCW
35
CH 8 +V COMMON
37
SHIELD
CH 7 +V INPUT
CH 7 STEP/CW
CH 7 DIRECTION/CCW
Channel 8
Channel 7
CH 7 +V COMMON
SHIELD SHIELD
39 AA855-2491
D.6 -3
Page 296
Output Stepper Module (2, 4, or 8 channel)
Connections for one channel are illustrated on the right in Figure D6-3. +V input to the +V terminal of the external power supply
Step/cw output to the step or clockwise input of the drive
Direction/ccw output to direction or counterclockwise input of the drive
Common to the 0V terminal of the external power supply NOTE: When the drive inputs are optically isolated, tie the 0V of the external power supply to SPG.
Shield
All shield pins on the module are connected to each other internally and AC coupled to SPG. Figure D6-3. Connections for One Channel
Stepper Module
Connections
External DC Supply
CH 1 +V INPUT
+V
Internal Circuitry
1
0V CH 1 STEP/CW
SPG
3 CH 1 DIRECTION/CCW
5 CH 1 +V COMMON
7 SHIELD
9
SPG
D.6 -4
Page 297
Output Stepper Module (2, 4, or 8 channel)
Connecting the SMCM to Stepper Drives
Consult your drive manual regarding the proper connection of an indexer such as the SMCM. Four types of drive inputs and the proper connection techniques are shown in Figures D6-4 to D6-7. When working with opto-coupler drive inputs, be sure the input diode is protected by a current-limiting resistor as stated in the following important note.
IMPORTANT There is a limit to the amount of current the input diode of the drive opto-coupler can withstand. If this current is exceeded, the device will be destroyed. The SMCM is capable of sinking considerably more current than the 15 mA specified. Most drives having opto-coupler inputs have a series current-limit resistor sized properly for a +5V external supply. If the drive being used has an opto-coupler input but does not have a current-limit resistor or if the current-limit resistor is too small, then one will have to be added externally. Consult your drive manual for information regarding this topic. Following the wiring guidelines listed below will increase the reliability of the SMCM/drive system. 1.
Route the wiring from the SMCM separately from any high current or electrically noisy wiring.
2.
Keep the wires connecting the SMCM to the drive less than 10 feet in length.
3.
Shield the wiring from the SMCM. Tie shields to the SMCM shield terminal screw and leave the other end of the shield unconnected.
D.6 -5
Page 298
Output Stepper Module (2, 4, or 8 channel)
Opto-Coupler Drive Inputs
The inputs for this type of drive will be: 1.
Step +
2.
Step -
3.
Direction +
4.
Direction -
Make the following connections as illustrated in Figure D6-4: External Power Supply
SMCM
Drive
Step/CW to
N/C to Step -
Direction/CCW to
N/C to Direction -
+V Input to
+V to Step + and Direction +
+V Common to
0V to N/C
Figure D6-4. SMCM Connections to Opto-Coupler Drive Inputs
+5VDC External Supply +V 0V
Stepper Module
Drive with opto-coupler inputs
SPG CH 1 +V INPUT
Step +
CH 1 STEP/CW
Step -
CH 1 DIRECTION/CCW
Dir +
1
220 Ohm Opto isolator
3 220 Ohm
5 CH 1 +V COMMON
7 SHIELD
9
D.6 -6
Dir Opto isolator
Page 299
Output Stepper Module (2, 4, or 8 channel)
Opto-Coupler with Common Source Drive Inputs
The inputs for this type of drive will be: 1.
Opto power input
2.
Step
3.
Direction
Make the following connections as illustrated in Figure D6-5: External Power Supply
SMCM
Drive
Step/CW to
N/C to Step
Direction/CCW to
N/C to Direction
+V Input to
+V to Opto power input
+V Common to
0V to N/C
Figure D6-5. SMCM Connections to Opto-Coupler Drive Inputs with Common Source
+15V DC External Supply
Drive with opto-coupler (common source) inputs
+V 0V
Stepper Module
SPG
Opto power
Opto isolator
CH 1 +V INPUT
1
680 Ohm CH 1 STEP/CW
3 CH 1 DIRECTION/CCW
5
220 Ohm Step
680 Ohm
220 Ohm Dir Opto isolator
CH 1 +V COMMON
7 SHIELD
9 External Resistors
D.6 -7
Page 300
Output Stepper Module (2, 4, or 8 channel)
Single-Ended Drive Inputs
The inputs for this type of drive will be: 1.
Step
2.
Direction
3.
Signal ground
Make the following connections as illustrated in Figure D6-6: SMCM
Power Supply
Drive
Step/CW to
N/C to Step
Direction/CCW to
N/C to Direction
+V Input to
+V to N/C
+V Common to
0V to Signal ground
Figure D6-6. SMCM Connections to Single-Ended Drive Inputs +5 VDC External Supply +V 0V
Stepper Module
Drive with single-ended inputs
CH 1 +V INPUT
1
+5V 1K
CH 1 STEP/CW
3
Step +5V
CH 1 DIRECTION/CCW
5
Dir
1K
CH 1 +V COMMON
7 SHIELD
Signal ground
9
AA859-2491
If the pull-up resistors internal to the drive are inadequate, you may need to add external pull-up resistors. Install them as close as possible to the drive.
D.6 -8
Page 301
Output Stepper Module (2, 4, or 8 channel)
Differential Drive Inputs
The inputs for this type of drive will be: 1. Step + 2. Step 3. Direction + 4. Direction 5. Signal ground
Make the following connections as illustrated in Figure D6-7: SMCM
Power Supply
Drive
Step/CW to
N/C to Step +
Direction/ CCW to
N/C to Direction +
+V Input to
+V to N/C
+V Common to
0V to Signal ground
Figure D6-7. SMCM Connections to Differential Drive Inputs
+5VDC External Supply +V 0V
Drive with differential inputs
Stepper Module
+5V CH 1 +V INPUT
1 CH 1 STEP/CW
+5V
Step + Step -
+5V
+ -
3 CH 1 DIRECTION/CCW
5
Dir + Dir -
CH 1 +V COMMON
7
+ -
Signal ground
SHIELD
9 AA860-2491
If the Step- and Direction- inputs are not biased to one half the external supply by the drive, external voltage dividers will be required. Install them as close to the drive as possible.
D.6 -9
Page 302
Output Stepper Module (2, 4, or 8 channel)
Theory of Operation
The stepper module is part of an open loop control system used to position from one to eight axes. The diagram in Figure D6-8 illustrates one axis being controlled by the SMCM. Digital signals from the SMCM are converted into fixed increments of motion via the stepper drive. This allows the stepper motor to move the load accurately and reliably by following the number of input steps. Figure D6-8. Open Loop Stepper System
PiC900 CPU
Data Transfer
SMCM Stepper Drive
L o a d
Stepper Motor
AA861-2491
The SMCM controls the position, velocity, and acceleration of the stepper motor. The number of pulses generated by the SMCM provides distance information (steps) and the rate of these pulses provides velocity information (steps/sec). The rate of change of the pulse rate provides acceleration/deceleration information (steps/sec/sec). Commands (acc/dec rates, maximum velocity, reference position, distance, position, and velocity moves) and control data (E-stop, C-stop, start, pause, continue, modes) are sent to the module and status and position information are received from the module via software. Each channel can have up to 500 commands queued up on the module. The step rate programmed by you for a velocity command (or calculated by the SMCM during acceleration or deceleration) versus the actual rate output from the SMCM is defined by the following equation: 10 × 10 6 ActualRate = -------------------X 10 × 10 6 where X is the integer quotient of ---------------------------------------------ProgrammedRate Refer to the Software Manual for information on controlling the SMCM via software.
D.6 -10
Page 303
Output Stepper Module (2, 4, or 8 channel)
Specification Table
Characteristic
Output stepper module (2, 4, 8 ch) specifications
Function
Controls up to eight stepper drives
Part number
502-03677-02 502-03677-22 502-03677-42
+V input (from external supply)
4.5 VDC to 20 VDC, 45 mA per connected channel
Step/CW output rating Direction/CCW output rating
Totem pole, 15 mA sink, 5 mA source
Field side connector
40-pin card edge connector, screw terminals
Protection of logic circuits
Optical isolation between the logic and field side
Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on
Position range
±2,147,352,575 steps
Step rate
0 to 1,000,000 steps/sec
Step rate accuracy
8 channel 2 channel 4 channel
10 × 10 6 ActualRate = -------------------X where X is the integer quotient of 10 × 10 6 ---------------------------------------------ProgrammedRate
Acceleration/deceleration rate
1 to 16,777,215 steps/sec/sec
Reference range
±2,147,352,575 steps
Response to scan loss
Pulse output halted
Logic side power requirements (typi- 404 mA @ +5V cal) 239 mA @ +5V 156 mA @ +5V
8 channel 4 channel 2 channel
6 mA per active channel @ +5V Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
D.6 -11
Page 304
Output Stepper Module (2, 4, or 8 channel)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
D.6 -12
Four shocks per axis (15g/11 msec)