Page 23
Figure 2. Diagram of the PiC900 system in operation
Computer Workstation using PiCPro / PiCServoPro and Application programs (optional)
PiC 900
1
CSM
CPU
INPUT
OUTPUT
ENCODER
OUTPUT +10 RESOLVER
2 5
6
8
9
0
+/-
.
G&L
PiC900™
3
4 7
EN
Operator Interface Devices (optional)
Motor Drive
Machine Inputs/Outputs
(POSITION LOOP)
Machine Servos/ Feedback Devices AA102-1890
3. A combination of hardware and software run an application. Hardware input modules accept data from the application. Data is processed as specified in the software application program. Commands generated by the program instructions are sent to the application by hardware output modules. Data sent to the workstation by the PiC allows an operator to monitor and modify the application using PiCPro commands.
Chapter 1 PiC900 Hardware Setup
1-9
Page 24
1.2
The System Rack
The system rack has four functions: 1. It provides physical support for the top and bottom of each hardware module. 2. It passes power from the CSM (or CSM/CPU)to each of the other modules. 3. It contains a data bus, address bus and control lines. These lines allow data to pass between the CPU (or CSM/CPU) module and each of the other modules. 4. It has a 64-pin female connector at each slot position which allows communication between modules. Dimensions of the Racks
PiC900 system racks differ only in length and the number of hardware modules they can contain. A dimensional diagram of each rack is shown on the following pages. Number of actual slots Number of modules PiC900
PiC90
Length
Height
Depth (with modules) Part Number
13
CSM, CPU, 11 I/O
21.6"
14.0"
9.0"
503-18011-03
10
CSM, CPU, 8 I/O
16.8"
14.0"
9.0"
503-18010-03
7
CSM, CPU, 5 I/O
12.0"
14.0"
9.0"
503-18009-03
5*
CSM/CPU, 4 I/O
8.8"
14.0"
9.0"
503-19184-02
3*
CSM/CPU, 2 I/O
5.6"
14.0"
9.0"
503-19185-02
*The PiC90 retaining bar labels the CSM/CPU module slot as 1/2, leaving 2 or 4 slots available for I/O modules. In Figure 1-3, racks with 3, 5, and 7 slots are shown with modules inserted. All racks are the same height and have the same profile. The other two rack sizes are shown empty (Figures 1-4 and 1-5).
1-10
Chapter 1 PiC900 Hardware Setup
Page 25
Figure 3. System racks with modules installed PiC90 Slots 3 and 4 available for hardware modules
PiC90 Slots 3, 4, 5, and 6 available for .365"/9.3 mm hardware modules
.365"/9.3 mm 2.8" 71 mm
3 I/O
1/2 CSM/CPU
I/O
14.0"/355mm
14.0"/355mm
13.375"/340mm
CSM/CPU
4
2.3" .265"/6.7mm
4 I/O
5
6
Servo Servo
6"/152mm .265"/6.7mm
58.4 mm
1.4"/35.6 mm
3 I/O
13.375"/340mm
1/2
1.4"/35.6 mm
5.6"/142mm
8.8"/224mm
PiC900 Slots 3, 4, 5, 6, and 7 available for hardware modules
.365"/9.3 mm
CPU
I/O
I/O
I/O
I/O
I/O
13.375"/340mm
14.0" / 355mm
CSM
Side View All racks
9.2" / 234mm .265"/6.7mm
1.4"/35.6 mm
9.0" / 229mm
12.0" / 305mm
Chapter 1 PiC900 Hardware Setup
1-11
Page 26
Figure 4. The 10-slot system rack
13.375"/340mm
14.0" / 355mm
.365"/9.3 mm
7.0" / 178mm .265"/6.7mm
14.0" / 356mm
1.4"/35.6 mm
16.8" / 427mm
Figure 5. The 13-slot system rack
13.375"/340mm
14.0" / 355mm
.365"/9.3 mm
9.4" / 239mm .265"/6.7mm
1.4"/35.6 mm
1-12
18.8" / 478mm 21.6" / 549mm
Chapter 1 PiC900 Hardware Setup
Page 27
1.3
System rack power and environment requirements
General Requirements
You are not required to install the system rack in a control cabinet. However a cabinet protects the system from dust and mechanical damage and is recommended. Two methods of power distribution are shown. The one in Figure 1-6 works in most situations. For installations where electrical noise is severe, Figure 1-7 illustrates a setup with filtered AC power. In both cases, Install the system rack away from all sources of strong electromagnetic noise. Such noise can interfere with PiC900 operation. • Protect the PiC900 system away from all the following: • conductive fluids and particles corrosive atmosphere explosive atmosphere The diagrams and recommendations may be modified if necessary so the wiring conforms to current NEC standards or government regulations. NOTE: All PiC modules are presently rated for operation between 7˚C and 55˚C. The PiC900/90 is suitable for operation in a pollution degree 2 environment (i.e., normally, only non-conductive pollution occurs). Control Cabinet Specifications
1. A control cabinet for the PiC900 should have a NEMA-12 rating or better. A cabinet with this rating protects its contents from dust and mechanical damage. 2. It must be large enough to provide adequate air circulation for the system rack, drives, and other components. You must have at least 2" free space within the cabinet on all sides of the system rack. 3. It must have a rigid vertical surface to mount the rack on. 4. The door should open fully for easy access.
IMPORTANT Post warnings according to National, State, or local codes for the voltage present in the control cabinet. Power Distribution Diagrams
The PiC900 system requires one AC power source for the system rack and its modules and one or more AC and/or DC sources for the connections to the I/O devices. Figures 1-6 and 1-7 show two ways to provide all necessary power in one setup.
Chapter 1 PiC900 Hardware Setup
1-13
Page 28
Figure 6. Example of 115V AC basic power distribution to a PiC900 system PiC900 module CUSTOMER'S 24 VDC POWER SUPPLY
+ - to DC I/O to AC I/O
115V AC
MAIN DISCONNECT
ON OFF L / LINE 1 N / LINE 2 E / GRND
Line1 (HOT) Line2 (COMMON) ground (protective earthing connection)
(Grounds from other devices)
AC outlet
PLANT GROUND
SINGLE-POINT GROUND (SPG) To COMPUTER WORKSTATION or other DEVICE
CHASSIS GROUND from another PiC900 GROUND CONTROL CABINET
The AC power source is connected to the PiC900 system through a 3-pin female connector. It plugs into the power connector of the CSM (or CSM/CPU). The ground from the power source and "GRND" (protective earthing ground) from the CSM (or CSM/CPU) module must be connected to the Single-Point Ground (SPG). Devices connected to the hardware modules must have their own power sources for input data or output control signals. Both versions of the power distribution setup provide properly grounded AC and DC sources that can be used for such devices. You can use other wiring setups, provided that each one is: at the correct voltage and current levels for the module and the device. • connected to the same Single-Point Ground that the system rack uses. •
It is recommended that the same main disconnect switch be used for the PiC900 system and for all devices in the application. NOTE: This main (primary) disconnect switch must have a minimum contact separation of 3 mm in all poles to meet requirements of the Low Voltage directive (73/23/EEC). IMPORTANT No matter how the system is installed, before you replace a module or connect it to the application, make sure that power is off to the system rack and to the devices the modules are wired to. 1-14
Chapter 1 PiC900 Hardware Setup
Page 29
The basic power distribution may be modified if the AC power source is subject to severe voltage spikes and surges. In many installations, a control transformer rated at a minimum of 0.5 KVA and a noise filter such as Islatrol model I-115/U may have been installed in series with the AC power source. Even though this model has worked successfully in the past, it is not CE approved. To meet the requirement of the Low Voltage Directive (73/23/EEC), a CE approved filter must be used. Control Concepts has an "Elite" series of Islatrol filters that have this CE approval. Filtered power distribution is recommended for most applications. It will prolong the life of the control. It should always be used when using communication and/or analog hardware. Figure 7. Example of 115V AC filtered power distribution to a PiC900 system PiC900 module CUSTOMER'S 24 VDC POWER SUPPLY
+ to DC I/O
-
ON OFF L / LINE 1 N / LINE 2 E / GRND to AC I/O
115V AC
MAIN DISCONNECT
1:1 TRANSFORMER
ISLATROL FILTER
Line1 (HOT) Line2 (COMMON)
(Grounds from other devices)
Ground
AC outlet PLANT GROUND SINGLE-POINT GROUND (SPG) 12" maximum
GROUND from another PiC900 CONTROL CABINET
CHASSIS GROUND
To WORKSTATION or other DEVICE AA105-1093
Grounding the System
The ground of the PiC900 system power source must be connected directly to a Single Point Ground (SPG) tie block. The tie block should be made of brass or copper, bolted or brazed to the control cabinet. If the tie block is bolted rather than brazed, scrape away paint or grease at the point of contact. Put star washers between the tie block and the cabinet to ensure good electrical contact. Metal enclosures of power supplies, drives, etc., should also have good electrical contact with the SPG.
Chapter 1 PiC900 Hardware Setup
1-15
Page 30
CAUTION The Single Point Ground should be the only common point for all the ground lines. If not, ground loops may cause current flow between components of the system which can interfere with proper operation of the PiC900. Devices to be connected directly to the Single Point Ground include:
1. Plant safety ground. 2. Ground (GRND - protective earthing connection) from CSM: the green/yellow wire. 3. "Common" or "0 V" lines from power supplies that provide external power to the I/O modules and the devices to which they are connected. 4. Chassis grounds from the devices themselves, such as device drivers, machinery, and operator interface devices. 5. AC common line from the noise filter, if any. 6. The ground of the power source of the computer workstation, if any, from which you monitor the system operation. An AC outlet in the control cabinet is recommended. See Figure 1-6 or 1-7. 7. Single point grounds from other control cabinets, if any, in the PiC900 system. 8. Shielded I/O wires. Shielded I/O wiring is recommended for use with analog output, encoder interface, and resolver interface modules. Controlling Heat Within the System
The hardware module cases and the system rack are designed to promote air circulation and dissipate heat. The rack must be mounted vertically to take advantage of this design. Normally no fans or air conditioners are needed. However, if the environment outside the control cabinet is hot or humid, you may need to use a fan, heat exchanger, dehumidifier or air conditioner to provide the correct operating environment. Table 1-1. Operating Limits for the System Rack Temperature
7 to 55˚ C (45 to 131˚ F)
Relative humidity
0 to 95%, non-condensing
Make sure that components installed in the cabinet with the rack do not raise the temperature above system limits and that any hot spots do not exceed specifications. For instance, when heat-generating components such as transformers, drives or motor controls are installed, separate them from the system by one of the following: 1-16
Chapter 1 PiC900 Hardware Setup