Page 31
Place them near the top of the control cabinet so their heat output rises away from the PiC900 system. • Put them in another control cabinet above or to one side of the cabinet with the system rack. This protects the PiC900 system from both heat and electrical noise. •
The PiC900 system itself is a source of heat, though in most installations its heat dissipates without harmful effects. System heat is generated from power dissipated by: 1. the power supply 2. logic side components on each hardware module installed in the system 3. field side input/output components on each module If you need to calculate total heat generated by a particular setup, refer to Appendixes for the specifications of each hardware module you have installed.
CAUTION If the PiC900 system is operated outside the recommended limits, the rack or the modules installed in it may be damaged. This will void the warranty. 1.4
Hardware Modules
All modules except the CSM and CSM/CPU have identical dimensions so they can be physically placed in any slot in the system rack. The CSM and CSM/CPU are 2.4" wide instead of 1.6", but its length and depth, and the rack connector in the back, are the same as the other modules.
IMPORTANT The CSM or CSM/CPU must be placed in the first slot on the left of the system rack. • In the PiC900, the CPU module must be in the second slot. • All I/O modules may be assigned by the application program to any other slot. •
The face of each hardware module is in two segments. The upper segment identifies the type of module and gives LED status information. Every module has a DIAG LED which is discussed at the end of this section. LEDs that give status for specific modules are explained in Appendixes. Chapter 1 PiC900 Hardware Setup
1-17
Page 32
The lower segment contains a screw terminal connector that allows you to wire inputs or outputs of the PiC900 to specific parts of the application. A door swings shut to protect these connections. The bosses and vents on the side allow free circulation of air within the system (Figure 1-8). Figure 8. Front and Right Side of a Module
LATCH OUTPUT
AIR VENTS
10V DC DIAG
9.5" 241mm
DOOR
12.0" 305mm
64 PIN MALE CONNECTOR
AIR VENTS FOOT 8.4" 213mm
1.6" 41mm
AA112-0890
Handling a Module
The module's case protects its internal circuitry against mechanical damage in shipping and handling. However, like any electronics device, the circuitry can be destroyed by: • • • • •
1-18 temperatures over 55˚ C (131˚ F) moisture condensing inside the module static discharge exposure to a magnetic field strong enough to induce a current in the circuitry freezing temperatures, vibration, and other hazards
Chapter 1 PiC900 Hardware Setup
Page 33
Normally there is no need to open a module case. Occasionally you must replace a battery or a fuse. Modules with replaceable components have a diagram and detailed anti-static precautions in the appendixes. IMPORTANT It is good practice to keep the module in the system rack or in an antistatic bag at all times. Types of Modules
Each module has its name printed at the top of the front face, separated by colorcoded bands from the rest of the upper segment. The colors identify which of the four main categories the module belongs to. silver - CSM, CPU, CSM/CPU, I/O driver, relay output modules blue - DC I/O red - AC I/O green - servo/analog I/O Power comes through the AC input plug. It is then converted to DC power. There is an internal battery back-up. See diagrams and specifications in the appendixes. All the other modules are powered from the CSM (or CSM/CPU) which sends specific DC voltages through the system rack. In the PiC900, the CPU module contains a Central Processing Unit and several kinds of memory. It uses power from the CSM to control the application, integrating the hardware and software components of the PiC900 system. See the diagrams and specifications in Appendixes. The CPU module is always in the second slot, next to the CSM. In the PiC90, these two modules are combined into the CSM/CPU. Several models of the PiC9X have the capability to communicate between PiC900s and/or perform I/O expansion. With the PiC90, there is an optional peer-to-peer communications port on the CSM/CPU. The I/O Driver Module for connecting expansion racks to a master rack is covered in Appendix B2. Several types of I/O modules are available. Refer to the Table of Contents for a complete listing of all I/O modules available. An input module accepts signals that convey status information. An output module sends commands to the application. An I/O module has either 25 or 40 screw terminal connections. Each screw terminal is assigned to a specific function. This is illustrated in a wiring diagram in each module write-up in the appendixes. Some connections are used for the external power supply, and others for data signals. Modules that use differential signals have paired terminals for data and other terminals assigned as shield commons. Chapter 1 PiC900 Hardware Setup
1-19
Page 34
Installing a Module in the Rack
CAUTION ALWAYS turn off power at the main disconnect switch before installing, removing or wiring a module. To install a module in the system rack (Figure 1-9), follow these steps: 1. Loosen the thumbscrews on the metal retaining bar at the top of the rack. 2. Set the foot of the module in the J-Clip near the bottom of the rack (1) and rotate the module until the latch snaps into the slot near the top of the system rack (2). The connection between the male 64-pin connector on the module and the female one on the system rack is complete. 3. Tighten the thumbscrews on the retaining bar to hold modules securely in place (4).
1-20
Chapter 1 PiC900 Hardware Setup
Page 35
Figure 9. Steps in the procedure
RETAINING BAR with thumbscrew 4
MODULE
MODULE
SYSTEM RACK
2
SYSTEM RACK
3
1
AA113-0890
IMPORTANT Always loosen the thumbscrews on the retaining bar before attempting to install or remove modules from the system rack. Tighten the thumbscrews firmly after all modules are installed.
Chapter 1 PiC900 Hardware Setup
1-21
Page 36
1.5
Wiring the System to the Application
The screw terminal connectors on each I/O module allow you to connect the PiC900 system with the application. You need two kinds of information about the terminal assignments in order to wire a module correctly: 1. the screw assignment diagram for that module, found in the appendixes 2. the inputs and outputs assigned to run this specific application supplied by the software application program
Each signal to or from a module takes the form of a voltage which is powered by external AC or DC sources (that is, not from the system rack). Figures 1-6 and 1-7 illustrated AC and DC power distribution. Making a Wiring Worksheet
You can make a set of wiring worksheets for each application program. Appendix H has a wiring worksheet for each I/O module. Make a copy of the appropriate worksheet for each I/O slot in the system rack. • Copy the input or output connection wire numbers or signal names that came with the software program onto the worksheets. Check each one carefully. Note: power supply signals may be daisy-chained. • A label is supplied for the inside of the module door on which to enter the wire name of each screw terminal. Copy the wire name onto the worksheet for future reference. •
Making the I/O Connections
The acceptable range of wire sizes is 20 (.5 mm2) to 14 (2 mm2) gauge. Use copper wire. • The shield wire is not insulated. Do not leave bare wire exposed. Protect bare wiring with one of the following: • spaghetti tubing tape shrink tubing NOTE: All wires/cables connected to the PiC must be mechanically secured against undue stress and must be suitably rated and approved for the voltage and conditions of use. Install the modules in the system rack before you start the I/O wiring. Make sure the wires are the correct length. When the wiring is complete the connectors should not be stressed. You may find that a wiring jig makes the job easier; instructions for making one are given in Appendix I. • Strip 0.2" (5.1 mm) of insulation from the end of the wire. •
1-22
Chapter 1 PiC900 Hardware Setup
Page 37
•
Start wiring at the bottom left screw terminal. Work up the left (inner) column. Then continue with the lowest terminal in the column on the right, and work up. (See Figure 1-10.) Figure 10. How to Wire a Screw Terminal
Screw terminal connector (front) Retention Screw*
1
Screw terminal connections (left side)
3 5
7 9 11
13 15
17 19
21 23 25
Retention Screw*
*Do not overtighten retention screws on the screw terminal connectors. AA114-1093
Chapter 1 PiC900 Hardware Setup
1-23
Page 38
IMPORTANT Make sure all screws are tight when adding wires or when probing unwired terminals. If the screw head is not fully tightened, there is no electrical connection between the screw head and the circuitry on the module. 1.6
Preventing Electrical Noise in Data Lines
The PiC900 system relies on electrical signals to report what is going on in the application and to send commands to it. In addition, signals are constantly being exchanged within the system. The PiC900 is designed for use in industrial environments, but there are limits to how much noise it can tolerate. Some suggestions are given below to reduce electrical noise. 1. Keep electrically noisy devices away from the PiC900. 2. Reduce noise generated by the application itself. 3. Protect data signals from noise. 4. Use differential devices for analog and encoder signals.
CAUTION Errors in data transmission in a PiC900 system may cause malfunctions in the application. Any device or wire that generates or uses electricity can create electrical noise in nearby circuits or devices. 'Nearby' is a relative term: an arc welder can create noise problems for many feet in all directions - including the room above. When one device's currents affect another device, they are said to be coupled. Coupling between a pair of wires running parallel to each other is directly proportional to the length of the parallel portion and inversely proportional to the distance between them. Keep Noisy Devices Away from the PiC900.
Make sure that arc welding equipment, heavy duty motors, and other devices that use large amounts of current and their power lines are at least 10 feet away from the PiC900 and the devices connected to it.
1-24
Chapter 1 PiC900 Hardware Setup