Page 39

Shield all cables that carry heavy current near the system, using continuous foil wrap or conduit grounded at both ends. Such cables include power leads for highfrequency welders and for pulse-width-modulation motor drives. Reduce Noise Generated by the Application Itself.

Equip inductive devices that are not directly connected to PiC900 modules with arc suppression circuits. These devices include contactors, solenoids and motors. Wires in the system which carry high current should be routed away from data lines that are sensitive to noise. AC, DC, communications, and analog cables must not be bundled together inside or outside the control cabinet. See Figure 1-11. Protect Data Wires from Noise

Install the system rack as close to the application as you can. Short communications lines are less affected by noise than long ones. Make all connections to the Single-Point Ground as short as possible, and use 14 gauge or larger wire for these connections. Route data lines 6" or more away from power lines or run them through separate conduit. Communications lines, for example those that use RS232, RS422 or biphase transformer mode signals, should also be shielded. In Figure 1-11 the communications data lines and the encoder/resolver/analog data lines are each in a separate conduit, grounded at the SPG. Figure 11. Power and signal cables from the system

COMMUNICATIONS

PiC900

ENCODER, ANALOG

SYSTEM AC INPUT/OUTPUT and MODULES

DC INPUT/OUTPUT to AC I/O to DC I/O

+ AC INPUT POWER

-

DC POWER SUPPLY

GND SINGLE-POINT GROUND

AA107-0890

Chapter 1 PiC900 Hardware Setup

1-25

Page 40

Use Differential Devices for Analog and Encoder Signals

A differential device receives or sends one signal over two wires (typically a shielded twisted pair). The input/output voltage at the second terminal is the inverse of the first. Information is received/sent as the difference between the two voltages. A single-ended device effectively receives or sends data over only one line. Information is received/sent as the difference between the signal voltage and the device's ground potential. Figure 12. Differential vs. Single-Ended Digital Pulse Train

SIGNAL AT A

SIGNAL AT A

INVERTED SIGNAL AT A

INPUT AT A TIED TO +

DIFFERENTIAL

SINGLE-ENDED

The advantages of using differential signals are: 1. A differential signal is less susceptible to electromagnetic noise. Static or other interference affects both of the twisted-pair wires equally, so the difference between the normal and inverted voltage remains unchanged. A differential signal can be transmitted over a much longer distance or in a much noisier environment than a single-ended one. A single-ended device's signal can be affected by noise while the ground to which it is compared is not. The receiver cannot tell the difference between a pulse from the sending device that carries information and a pulse created by noise on the line. 2. PiC900 hardware circuitry can detect signal loss from an encoder if the signal is differential, but not if it is single-ended. The application program can be set to shut down the application if such an error is detected.

IMPORTANT Use differential drivers or differential inputs if possible. If singleended devices must be used, keep the distance between the device and the PiC900 less than 10 feet.

1-26

Chapter 1 PiC900 Hardware Setup

Page 41

1.7

Starting an Operation

Good procedure suggests that the system should be tested each time a new application is powered up. Each module in the PiC900 rack is tested automatically every time power is applied. The DIAG LED on each module should be off indicating that the module passed the diagnostic tests. Installing and Testing the Hardware Modules

1. Insert the CSM (or CSM/CPU) into the first slot at the left end of the system rack. 2. With the PiC900, insert the CPU module into the second slot next to the CSM. 3. Turn off the main disconnect switch and plug the AC connector into the power connector. Turn on input power and the power switch (see the power distribution diagrams). The DIAG LED turns on and then turns off when the module passes its diagnostic tests. With the PiC900, the DIAG LED on the CPU module repeats these steps. Turn off the power switch and the main disconnect switch. 4. Slide the I/O modules into the appropriate slots designated in the software program. Connecting the PiC900 System to the Application

1. Turn off the main disconnect switch in the control cabinet. If some devices are not powered from the control cabinet, turn them off also. 2. Connect the screw terminal connectors according to your diagrams. 3. Turn on power to the system and the power switch. The PWR light goes on and stays on. The DIAG light on each module goes on, then goes off in turn. Turn the key clockwise. The SCAN light goes on. The application starts to work under control of the system. 4. If an application program is not in system memory, the Software manual describes a number of procedures that may be used to put it there. 1.8

Troubleshooting

Table 1-2 summarizes how to proceed when performing certain maintenance and/ or setup functions.

Chapter 1 PiC900 Hardware Setup

1-27

Page 42

Table 1-2. Summary In order to: Turn off the entire application.

Turn off main disconnect in the AC input line (which should also turn off all external power supplies to the application), and the power switch; unplug the AC power.

Wire the I/O modules to the application.

Turn off main disconnect in the AC input line and the power switch; unplug the AC power.

Replace a module in the rack.

Turn off main disconnect in the AC input line.

Change a fuse in an output module. Change the battery.

Turn off main disconnect in the AC input line.

Connect/disconnect the PiC900 with the Turn off the power switch. computer workstation through the PiCPro port. Connect/disconnect the PiC900 with an operator interface through the User port.

Turn off the power switch.

Download an application program into the Make sure power is on (check the PWR CPU module memory. LED). The Run key may be off or on. Stop the scan.

From the workstation - use PiCPro commands. From the PiC900 - turn off the RUN/STOP switch.

This section covers two types of diagnostics; power-on and run-time. Power-On Diagnostics

When the system is powered up, it tests itself and reports the results of the tests in the form of LED signals. Power LED If the PWR light does not go on, or goes off during operation of the system, check that power is still connected to the CSM (or CSM/CPU). If it is, turn off the main disconnect switch and replace the CSM (or CSM/CPU) Scan LED If the SCAN LED does not go on: Check that the PWR light is ON. • Check that the DIAG lights on all modules are OFF. • Check that the key switch is in the Run position. •

1-28

Chapter 1 PiC900 Hardware Setup

Page 43

If the application program is in RAM, turn off the Run key, download the program again from the workstation, and turn on the key. • If the program is in an EPROM, make sure the it is correctly installed. See Appendix A2 for the PiC900 and A4 for the PiC90. •

Diagnostic LEDs Each module has an LED marked DIAG which lights up briefly while its diagnostic tests are running and then goes off. If the DIAG LED on any module remains on, the module has failed one of its tests. Follow these steps: 1. Turn off power to the system and to the application. 2. If the I/O wiring is connected, remove the screw terminal connector from the module, but leave its wiring attached. 3. Pull the defective module from the rack. 4. Insert a replacement module of the same type in the rack. Replace the screw terminal connector on the new module. 5. Turn on power to check diagnostics again.

NOTE Diagnostics are run only when the system is powered up. It is possible that a module might fail during operation. If so, its DIAG light remains off. If you suspect that a module might be defective, cycle power to run diagnostics again. If the diagnostic LEDs remain lit on one or more of the modules, there may be something wrong with the CSM or CPU module (or the CSM/CPU). Follow these steps in tracing the problem: 1. Turn off the main disconnect switch in the control cabinet and any other power to the application. 2. Remove all modules except the CPU and CSM (or the CSM/CPU). 3. Turn on the power to run diagnostics again. 4. With the PiC900, if both LEDs stay lit, turn off power, replace either the CSM or the CPU module and turn on power. If LEDs remain lit, put original module back in and replace the other module. With the PiC90, replace the CSM/CPU module. 5. If the problem is not the CSM or CPU (or the CSM/CPU) module, turn off power, replace one of the I/O modules, and turn on power to run its diagnostics. Repeat until you find the defective module.

Chapter 1 PiC900 Hardware Setup

1-29

Page 44

6. If the problem can not be traced to a module, check the I/O wiring and the devices the system is connected to. There may be a short or other problem outside the system rack. Run-Time Diagnostics

While the PiC900 is running, other tests are performed on a regular basis with their results also reported to you through LEDs. •If the BATT LED on the CSM or CSM/CPU starts flashing, the battery must be replaced. See Appendix A1 for the PiC900 and A4 for the PiC90. •If the FB LED on one of the output modules goes on, a fuse must be replaced. See the section on the specific module in Appendixes for details. •While the PiC900 is running, the DIAG LED on the CPU or the CSM/CPU will flash a three digit code signal if there is an error. For example, if there is a long pause-flash-pause-flash-flash-pause-flash-flash-flash-long pause, the code is 123. The errors are described in Appendix M.

1-30