Page 47
A.1- PiC900 CSM/RSM Central Service Module/Remote Service Module Introduction
The Central Service Module (CSM) and the Remote Service Module (RSM) convert incoming power to regulated DC power. Through the bus, the CSM supplies this power to the modules in the master rack and the RSM supplies this power to the modules in an expansion rack. The CSM has the following additional features: Scan control which includes a key switch to run/stop the scan when power is on. • A lithium battery to back up such items as non-volatile RAM in the CPU module and the time-of-day clock on the CSM module when power is turned off. • An internal clock to provide time of day and date when needed by the software. •
The CSM and the RSM must always be located in the first slot on the left in the master rack and expansion rack respectively. Figure A1-1. CSM/RSM RSM - the Remote Service Module CSM - the Central Service Module (for expansion rack)
(for master rack)
Name of modu
CSM
DIAG PWR SCAN BATT
DIAG PWR SCAN
LEDs
Key slot
Run
Name of module
RSM
Run
LEDs
(Key slot not used) Stop
Stop GIDDINGS & LEWIS Programmable industrial Controlle
Door
Door
ON
Power switch
L / LINE1
Power switch
OFF
OFF
N / LINE2
ON
L / LINE1
Power connec
E / GRND
N / LINE2
Power connector
E / GRND
AA21-489
AA1092-4892
A.1-1
Page 48
PiC900 CSM/RSM Central Service Module/Remote Service Module
Connections
The CSM and RSM modules receive power through a 3-pin power connector. Figure A1-2 illustrates the connections as listed below. Module
AC Power Source 110VAC
L / LINE 1 to Hot
AC Power Source 220VAC
DC Power Source 24VDC
Line1
+24V
N / LINE 2 to Common
Line2
-24V
E / GRND
Single Point Ground
Single Point Ground to Single Point Ground
Figure A1-2. Power to the System CSM/RSM Module
Power Source
ON OFF
110V AC 220V AC
24V DC
HOT Line 1 +24V DC COMMON Line 2 -24V DC GROUND GROUND GROUND
L / LINE 1 N / LINE 2 E / GRND SPG
(protective earthing connection)
Theory of Operation
The CSM (RSM) module converts incoming input power into DC power at voltages of + 5V, + 15 V, and - 15 V and supplies them to the logic side of the modules in the rack. External power supplies are used for the field side of the I/O modules. Such supplies are not routed through the CSM (RSM), but they should all have the same power cut-off switch as the PiC900. See the power distribution diagrams in Chapter 1. CAUTION The on/off rocker switch on the face of the CSM (RSM) does not control the I/O power supplies. Always shut off power at the main disconnect switch before you replace a module in the system rack. With the CSM, a key is supplied to protect the system from unauthorized start-ups. You can set up the PiC900 hardware, power up and run the diagnostic tests, and even load a software application program without the system key. However, the application program will not be scanned until you turn the Run/Stop key on the CSM to the Run position.
A.1-2
Page 49
PiC900 CSM/RSM Central Service Module/Remote Service Module
CSM Time-of-Day Clock
An internal clock IC maintains the current date and time. If power is off to the system, the battery maintains the clock. The application program and PiCPro can access this clock. Details are given in the Software Manual. LEDs
DIAG, diagnostic LED
The DIAG LED should turn on briefly whenever power is turned on to the system. The processor in the CPU module automatically runs diagnostic tests on all modules at power up. This LED goes on during testing, and then turns off when the module passes all the tests. Status LEDs
The CSM has four LEDs to indicate status. During normal operation the DIAG and BATT LEDs should be off, and the PWR and SCAN LEDs should be on. The RSM has three LEDs to indicate status. During normal operation the DIAG LED should be off, and PWR and SCAN LEDs should be on. PWR, power LED
The PWR light should be on all the time that power is on to the system. It indicates that the + 5V supply is within tolerance. See the specification sheet at the end of the section. SCAN, scan LED
The SCAN light indicates that the processor is executing the application program. If scan loss occurs the light will go off and there is an orderly shutdown procedure. CSM BATT, battery LED
The BATT light should turn on briefly while the battery is checked at power-on. After the battery passes its test, the LED goes off. If the BATT LED starts flashing either at start-up or during system operation, the lithium battery must be replaced. Each module that uses the battery to back up its data has circuitry that can maintain its data for approximately two hours if the CSM is not in the system rack. Power must be on for at least five minutes to ensure that modules that require backup power will retain their data while the CSM is out of the system rack.
A.1-3
Page 50
PiC900 CSM/RSM Central Service Module/Remote Service Module
Replacing the Battery on the CSM
Follow the procedure below to replace a battery. 1.
After AC power has been applied to the CSM for at least five minutes, turn off power at the control cabinet main disconnect switch and at the CSM power switch. Unplug the AC input power connector from the CSM.
2.
Remove the CSM module from the rack by pressing down the latch at the top and pulling it out.
3.
Use a static-free work surface if possible. Ground yourself using a properly grounded wrist strap before you open the case. These are standard precautions before handling any electronics component.
4.
Lay the CSM on the work surface with its label side up. Press the plastic tabs at the top and bottom of the module case toward each other and lift the side off.
WARNING DO NOT touch any of the capacitors. Do not touch the pins on any of the ICs; even with precautions against static you may destroy the circuitry. 5.
A.1-4
Use Figure A1-3 to locate the battery. Note how it is oriented.
Page 51
PiC900 CSM/RSM Central Service Module/Remote Service Module
Figure A1-3. Battery Location in CSM Module
BATTERY
DIAG LED PWR LED SCAN LED BATT LED
-
Battery Clip
+
CAP POWER
SUPPLY
6.
Use an insulated screwdriver to pry out one end of the battery clip. Remove the clip. Lift the battery out. Replace it with a 3V, 2/3A lithium battery. (See the specification sheet at the end of this section.) Replace the clip ensuring that it is latched.
7.
Close the case and insert the CSM in the rack. Connect the power cable. Turn on power and check the LEDs.
A.1-5
Page 52
PiC900 CSM/RSM Central Service Module/Remote Service Module
Specification Table
Characteristic
CSM/RSM specifications
Functions
Supplies regulated DC power to the hardware modules installed in the rack
AC power source
110-230 VAC, 47-63 Hz, 2A
Part numbers
502-03512-03 CSM-50 502-03732-03 RSM-50
DC power source
20 - 60 VDC, 5A
Part number
502-03973-00
Input connector
3-terminal plug connector, meets all specifications for touch safety in accordance with IEC 529 and DIN VDE 0470 part 1
Power output, total
CSM/RSM-50 50 W
502-03813-03 CSM-60 502-03817-03 RSM-60
CSM-50 (24VDC)
CSM/RSM-60 60 W
CSM 24VDC 50W
+ 5 V@8.5 A +15V@1.5 A -15V@1.5 A
5V @ 4.0 A +15V @ 1.0 A -15V @ 0.5 A
Individual outputs
+ 5 V @4.0 A + 15 V@2.0 A -15 V @0.5 A
Battery (CSM only)
1.2 Ah 3V, 2/3A lithium battery 401-52446-00
CAUTION for Lithium Batteries
Danger of explosion if battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batterries according to the manufacturers instructions. + 5 V supply monitor
Trip points ± 5% ± .5%: 4.725 to 4.775V and 5.225 to 5.275 V PWR LED goes off and PiC900 shuts down
± 15 V supply monitor
Trip points ± 8% ± 2%: 13.5 to 14.1 V and 15.9 to 16.5 V
Time-of-day clock (CSM only)
Access via PiCPro or application program.
Clock tolerance (CSM only)
At 25° C, ±1 second per day Over temperature, voltage and aging variation, +2/-12 seconds per day
Logic side power requirements (typical)
25 mA @ +5V 2 mA @ +15V 2 mA @ -15V 2 µA @ +3V
Operating temperature range
A.1-6
(from battery during power down on CSM)
7° C to 55° C (45° F to 131° F)
Page 53
PiC900 CSM/RSM Central Service Module/Remote Service Module
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed (CSM/RSM-50)
File No. E126417 NRAQ Programmable Controllers
Physical size
2.4" wide x 12" high x 8.4" deep (including latch) 61 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
A.1-7
Page 54
PiC900 CSM/RSM Central Service Module/Remote Service Module
NOTES
A.1-8