E.3 - Input RTD Module (6 channel) Introduction
The input resistance temperature detector (RTD) module has 6 independent RTD conversion channels which receive signals from 50 Ω or 100 Ω RTDs. Each channel converts a resistance into a 12-bit digital word which is processed by the PiC900. This module requires no hardware adjustments. All adjustments such as Fahrenheit or Celsius scaling and temperature ranges are software selectable. The DIAG LED turns on briefly while the diagnostic tests are running. Figure E3-1. INPUT RTD Module (6 CH)
INPUT
RTD
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25
Door
AA881-2591
E.3 -1
Page 354
Input RTD Module (6 channel)
Connections
RTD signal levels are very small (approximately 1.0 mA constant current source) and, consequently, sensitive to electrical noise. The module inputs are processed to reduce noise sensitivity. Always follow procedures to eliminate electrical noise from the system. Refer to the EMC Guidelines. Some additional guidelines for reducing noise are listed below. Route RTD wires separately from sources of noise such as motors, AC wiring, etc. • Keep RTD wires physically close to each other. • In severe noise environment, use twisted pair wire for two pin RTDs and use shielded wire (3 conductor w/ground recommended) for three pin RTDs. •
Figure E3-2 shows the assignments for all the screw terminal connections on the module.
E.3 -2
Page 355
Input RTD Module (6 channel)
Figure E3-2. Connection for Input Terminals SCREW TERMINALS 2
1
4
8
5
16
24
Ch 2 Pin 2
Channel 2
Ch 3 Common Ch 3 Pin 3
11
Ch 3 Pin 2
Channel 3
Ch 3 Pin 1
13
Ch 4 Common Ch 4 Pin 3
15
Ch 4 Pin 2
Channel 4
Ch 4 Pin 1
18
22
Ch 2 Common
Ch 2 Pin 1
17
20
Channel 1
Ch 2 Pin 3
7 9
14
Ch 1 Pin 2 Ch 1 Pin 1
10 12
Ch 1 Common Ch 1 Pin 3
3
6
CONNECTIONS
Ch 5 Common Ch 5 Pin 3
19
Ch 5 Pin 2
Channel 5
Ch 5 Pin 1
21
Ch 6 Common Ch 6 Pin 3
23
Ch 6 Pin 2
Channel 6
Ch 6 Pin 1
25
Common (No external connection)
RTDs may be 2- or 3-wire types. Inaccuracies in temperature will occur as the RTD wire (lead) length increases. Compensation for temperature inaccuracies must be taken into account when using RTDs. The RTD module provides internal lead compensation for 3-wire RTDs with lead lengths up to 1000 feet. No internal lead compensation is available for 2-wire RTDs. They are accurate without any lead compensation up to 20 feet. Adjustments for lead compensation can be made by you via the software for both 2- and 3-wire RTDs for up to 5000 feet of lead length. When connecting the 2-wire RTD to the module, the black wire and red wires may be connected to pins 1 and 2 for the channel. Pin 3 is connected to the channel common with a jumper. See Figure E3-3 below. NOTE: All the channel commons are connected internally to Pin 25 and to single point ground. No external connection to Pin 25 should be made.
E.3 -3
Page 356
Input RTD Module (6 channel)
Figure E3-3. RTD (2-wire) Connections
RTD Module 1
Ch 1 Common
3
Ch 1 Pin 2
Ch 1 Pin 3
RTD (2 Wire)
Ch 1 Pin 1
Black
Red
When connecting a 3-wire RTD to the module, the red wire and the black wires are connected to pins 1, 2, and 3 for the channel. Figure E3-4. RTD (3-wire) Connections
RTD (3 Wire)
RTD Module
Black Black
1
Ch 1 Common
3
Ch 1 Pin 2
Ch 1 Pin 3
Red Ch 1 Pin 1
Theory of Operation
The input RTD module receives analog signals from 50 Ω or 100 Ω RTDs and converts them to a 12 bit digital word for each channel in use. Each channel can be set up individually for up to three different RTD input ranges. The three temperature ranges for RTDs are. 50 Ω RTD
-200˚C to 350˚C (-328˚F to 1562˚F)
1
E.3 -4
100 Ω RTD
2
-200˚C to 850˚C (-328˚F to 1562˚F)
-200˚C to 266˚C (-328˚F to 510.8˚F)
3
-200˚C to 266˚C (-328˚F to 510.8˚F)
-200˚C to 0˚C (-328˚F to 32˚F)
Page 357
Input RTD Module (6 channel)
RTD Precautions
Certain precautions should be taken when working with RTDs to ensure the integrity of your system. Avoid any vibration, bending or other mechanical stress which may strain the RTD wire and change its characteristics. • Use 24 AWG solid or larger for runs less than 30 feet. Use 20 AWG or larger for runs greater than 30 feet. • Use shielded wire to protect from severe electrical noise. • Use the RTD wire well within its temperature rating. •
Specification Table
Characteristic
RTD module specification
Function
Measures 50 Ω and 100 Ω RTD inputs
Part number
502-03679-02
Field side connector
25-pin card edge connector, screw terminals
Input channels
6
Resolution
12 bits
RTD types
European curve (Alpha = .00385) for 50 Ω and 100 Ω two and three wire RTDs
50 Ω temperature ranges
-200˚C to -200˚C to
850˚C 266˚C
(-328˚F to 1562˚ F) (-328˚F to 510.8˚ F)
100 Ω temperature ranges
-200˚C to -200˚C to -200˚C to
850˚C 266˚C 0˚C
(-328˚F to 1562˚ F) (-328˚F to 510.8˚ F) (-328˚F to 32˚ F)
Maximum RTD lead wire length 24 AWG or smaller
< 20 feet
20 AWG or larger
2-wire RTD - under 20 feet without lead compensation NOTE: Lead length can affect accuracy of 2-wire RTDs with lengths over 20 feet. 2-wire RTD - up to 5000 feet with lead compensation 3-wire RTD - up to 1000 feet without lead compensation 3-wire RTD - up to 5000 feet with lead compensation
Accuracy
.6% FSR @ 25°C Temperature coefficient of 75 PPM/°C
E.3 -5
Page 358
Input RTD Module (6 channel)
Time between samples (software selectable)
2000 to 65,535 µsec
Filter time constant
120 ms
Open RTD detection
Indicated by software
Logic side power requirements (typical)
80 mA @ +5V 112 mA @ +15V
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
E.3 -6
Four shocks per axis (15g/11 msec)