For the Giddings & Lewis 502-03550-02
Page 345
E.2 - Input J-K Thermocouple Module (12 channel) Introduction
The input temp J-K thermocouple modules (one for use with grounded thermocouples and one for use with ungrounded thermocouples) has 12 independent thermocouple or analog conversion channels which receive signals from J or K type thermocouples or from a voltage source. Each channel converts an analog signal into a 12-bit digital word which is processed by the PiC900. This module requires no hardware adjustments. All adjustments such as Fahrenheit or Celsius scaling and thermocouple ranges are software selectable. The DIAG LED turns on briefly while the diagnostic tests are running. Figure E2-1. INPUT TEMP J-K Module (12 CH)
INPUT TEMP J-K
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25
Door
AA82-0391
E.2 -1
Page 346
Input J-K Thermocouple Module (12 channel)
Connections
Thermocouple signal levels are very small (1˚C is approximately 50 µV) and, consequently, sensitive to electrical noise. The module inputs are processed to reduce noise sensitivity. Always follow procedures to eliminate electrical noise from the system. Some guidelines for reducing noise are listed below. Route thermocouple wires separately from sources of noise such as motors, AC wiring, etc. • Keep both wires of the thermocouple physically close. • If the point being measured is a noisy source, use shielded wire and electrically isolate the thermocouple junction from the point of measurement. • Use shielded thermocouple wire in severe noise environments. •
For ±100 mV input signals, do the following to protect from noise: Use shielded twisted pair wire. • Connect the shield to the cabinet or to the metal enclosure at the cable entrance. Figure E2-2 shows the assignments for all the screw terminal connections on the module. •
E.2 -2
Page 347
Input J-K Thermocouple Module (12 channel)
Figure E2-2. Connection for Input Terminals
CONNECTION S Ch 2 +
Channel 2 Ch 2 -
SCREW TERMINALS
2
1
Ch 1 +
3
Ch 1 -
5
Ch 3 +
7
Ch 3 -
9
Ch 5 +
11
Ch 5 -
13
Ch 7 +
15
Ch 7 -
17
Ch 9 +
19
Ch 9 -
21
Ch 11 +
23
Ch 11 -
25
Common (No external connection)
4 6
CONNECTION S
Channel 1
Ch 4 +
Channel 4
8
Channel 3
Ch 4 -
10 Ch 6 +
Channel 6 Ch 6 -
Ch 8 +
Channel 8 Ch 8 Ch 10 +
Channel 10
Ch 10 -
12 14 16 18 20 22
Ch 12 -
Channel 7
Channel 9
Ch 12 +
Channel 12
Channel 5
Channel 11 24
E.2 -3
Page 348
Input J-K Thermocouple Module (12 channel)
When connecting thermocouples to the module, the white wire of J type (the yellow wire of K type) is connected to the + input and the red wire of J or K type is connected to the - input as shown on the left in Figure E2-3. On the right is a shielded thermocouple connection. Figure E2-3. Thermocouple Connections
Thermocouple connections to Channel 1
1
Ch 1 +
3
Ch 1 -
White (J), Yellow (K) +
Red (J or K)
Thermocouple connections with shield
1
Ch 1 +
3
Ch 1 -
5
White (J), Yellow (K) +
Red (J or K) To metal enclosure at cable entrance
When making an analog input connection to a ±100 mV type signal, shielded twisted pair wire should be used with the shield connected to SPG close to the module as shown in Figure E2-4. Figure E2-4. Analog Input Connections
1
Ch 1 +
+ 3
Ch 1 -
To metal enclosure at cable entrance
E.2 -4
To SPG
Voltage signal source
Page 349
Input J-K Thermocouple Module (12 channel)
If the ±100 mV range will be exceeded, external resistors must be added. The resistors should be positioned as close to the PiC900 as possible. NOTE: Units are Vin in volts and R1 and R2 in K Ωs. Select a R1 value from .5K Ω to 2K Ω. Use the following formula to calculate the R 1 × 260 value of R2: R 2 = ( V in × 10 ) --------------------- R 1 + 260 For example, if the input range will be ±10 V and R1 = 1K Ω , then the value of R2 1 × 260 would be: R 2 = ( 10V × 10 ) ----------------- 1 + 260 R 2 = 99.6K A 100K Ω resistor could be used for R2 in this example. It is the closest standard 1% value. Figure E2-5. Analog Input Connections with External Resistors R2
1
Ch 1 +
3
Ch 1 -
+ Voltage
R1
To metal enclosure at cable entrance signal source
To SPG
E.2 -5
Page 350
Input J-K Thermocouple Module (12 channel)
Theory of Operation
The input thermocouple module receives analog signals from thermocouples or analog inputs and converts them to a 12 bit digital word for each channel in use. Each channel can be set up individually for three different thermocouple input ranges (see specification table) or for ±100 mV. The module provides cold junction compensation. Cold junction compensation corrects for error voltages which occur at the point where the thermocouple wire terminates into the PiC900 module connector. Always make the connection into the module with the thermocouple wire to ensure that cold junction compensation is effective. All inputs are differential with input signals electrically isolated from the logic side. The inputs are filtered with a 120 ms time constant for a higher degree of noise immunity. The ±100 mV input can be used only in applications which do not require a response time faster than 120 ms. Thermocouple Precautions
Certain precautions should be taken when working with thermocouples to ensure the integrity of your system. Avoid any vibration, bending or other mechanical stress which may strain the thermocouple wire and change its characteristics. • Use 24 AWG solid or larger for runs less than 30 feet. Use 20 AWG or larger for runs greater than 30 feet. (The maximum thermocouple wire length is 1,000 feet.) • Use shielded wire to protect from severe electrical noise. • Use the thermocouple wire well within its temperature rating. •
E.2 -6
Page 351
Input J-K Thermocouple Module (12 channel)
Specification Table
Characteristic
Thermocouple module specification
Function
Measure J or K type thermocouple wire inputs or ± 100 mV analog inputs
Part numbers
Ungrounded 502-03658-02
Field side connector
25-pin card edge connector, screw terminals
Input channels
12
Resolution
12 bits
Input voltage sensitivity (software selectable)
±100 mV
J type thermocouple temperature ranges (at 25˚C)
Grounded 502-03809-02
-150˚C to 1200˚C (-238˚F to 2192˚ F) -35˚C to 620˚C (-31˚F to 1148˚ F) -10˚C to 280˚C (+14˚F to 536˚ F)
K type thermocouple temperature ranges (at 25˚C)
-200˚C to 1300˚C (-328˚F to 2372˚ F) -80˚C to 820˚C (-112˚F to 1508˚ F) -35˚C to 415˚C (-31˚F to 779˚ F)
J or K type accuracy
J type .37% of the 1350˚C span K type .36% of the 1500˚C span
±100 mV accuracy
± (50 µV + 1 count + input x 1%)
Time between samples (software selectable)
5000 to 65,535 µsec
Filter time constant
120 ms
Cold junction compensation
0 to 80°C ± 1°C at the sensor
Open thermocouple detection
Indicated by software (No detection for grounded thermocouples)
Logic side power requirements (typi- 80 cal) 112 mA @ +5V mA @ +15V
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
E.2 -7
Page 352
Input J-K Thermocouple Module (12 channel)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
E.2 -8
Four shocks per axis (15g/11 msec)