Page 335
E.1 - Input Analog Module (8 channel) Introduction
The analog input module is designed to interface the PiC with voltage or current output devices to monitor such things as pressure, flow, speed, position, or temperature. There are two versions of the analog input module available. One has 12bit resolution and the other has 14-bit resolution. The module has eight independent analog conversion channels. Each channel converts a unipolar or bipolar analog input voltage or current into a 12- or 14- bit digital value. This data is transmitted to the PiCs CPU for processing. There is an internal current sense resistor for each channel for use with 0 to 20 mA or 4 to 20 mA devices. This module contains no user adjustable potentiometers or hardware switches. All necessary gain adjustments are done in software. The analog module can be configured as a feedback module using the Servosetup software. The DIAG LED goes on briefly while the diagnostic tests are running. Figure E1-9. INPUT ANALOG Module (8 CH) INPUT ANALOG
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25 27 29 31 33 35 37 39
Door
AA60-3290
E.1 -1
Page 336
Input Analog Module (8 channel)
Connections
All signals to the input module must come to the screw terminal connectors through shielded twisted pair wires. See the discussion in the Hardware chapter on "Preventing electrical noise in data lines". Each input channel has three connection pins. (See Figure E1-2.) The signals are: +voltage input -voltage input 250 ohm current sense resistor for 0/20 mA and 4/20 mA applications There are five common connection pins. All five pins are interconnected within the module so that they are the same point electrically. These pins are internally connected to the Single Point Ground (SPG). In addition the module has nine screw connections for terminating the shields. All nine are interconnected within the module so they are the same point electrically. These pins are internally connected to SPG. The shield at the device end of the cable is not connected.
E.1 -2
Page 337
Input Analog Module (8 channel)
Figure E1-2 shows the assignments for all the screw terminal connections on the module. Figure E1-10. Connections for the Input Terminals SCREW TERMINALS CONNECTIONS
CONNECTIONS
2
1
Ch 1 +
3
Ch 1 -
5
Ch 1 250 ohm Resistor
7
Ch 3 +
9
Ch 3 -
11
Ch 3 250 ohm Resistor
13
Ch 5 +
15
Ch 5 -
17
Ch 5 250 ohm Resistor
19
Ch7 +
21
Ch 7 -
23
Ch 7 250 ohm Resistor
Ch 2 +
4 Channel 2
Channel 1
Ch 2 -
6 Ch 2 250 ohm Resistor
8 Ch 4 +
10 Channel 4
Channel 3
Ch 4 -
12 Ch 4 250 ohm Resistor
14 Ch 6 +
16 Channel 6
Channel 5
Ch 6 Ch 6 250 ohm Resistor
18 20
Ch 8 +
22 Channel 8
Channel 7
Ch 8 -
24 Ch 8 250 ohm Resistor
25
Not used Not used
26
Common Common
28
Common Common
30
Common Shield
32
Shield Shield Shield
34
Shield
36 38
Shield Shield
29
Common Pins 27 to 31 (No external connection)
31 33 35 Shield Pins 32 to 40
Shield Shield
27
40
37 39
E.1 -3
Page 338
Input Analog Module (8 channel)
When connecting an analog voltage output device to the module, the positive wire of the twisted pair goes to the + screw terminal and the negative wire goes to the - screw terminal. Figure E1-3 illustrates these connections for channel one. Notice that no connection is made to the screw terminal with the internal 250 Ω resistor when connecting a voltage source device. Figure E1-11. Voltage Input Connections
1
Ch 1 +
3
Ch 1 -
5
Ch 1 250 ohm Resistor
+ Voltage -
30 31 Common
32 33
Shield
34 35
Shield
Shield
36 37
Shield
Shield
38 39
Shield Shield
Shield
40
Shield
To SPG
E.1 -4 signal source
Page 339
Input Analog Module (8 channel)
When using a 0 to 20 mA or 4 to 20 mA current output device, the positive wire of the twisted pair is connected to the + input and the negative wire is connected to the 250 Ω resistor input. A jumper is placed between the - input and the 250 Ω resistor input as shown in Figure E1-4 (from pin 3 to pin 5 for channel 1). This connects a 250 Ω internal resistor across the input. Figure E1-12. Current Input Connections (0 to 20 or 4 to 20 mA)
1
Ch 1 +
3
Ch 1 -
+ -
Current signal source 0 to 20 or 4 to 20 mA
+ Power - supply
5 Ch 1 250 ohm Resistor
Common
30 31 Common
32 33
Shield
Shield
34 35
Shield
36
Shield
37
Shield
Shield
38 39
Shield Shield
40
Shield
To SPG
E.1 -5
Page 340
Input Analog Module (8 channel)
An alternative method of connecting a two wire 4 to 20 mA current device is shown in Figure E1-5. Place a jumper between the - input and the 250 Ω resistor input. Figure E1-13. Current Input Connections (4 to 20 mA)
Current Signal Source 4-20 mA +Input from power supply
Common
1
Ch 1+
3
Ch 1-
5
Ch 1 250 ohm Resistor
Output
+ Power - Supply
30 32
Shield
34
31 Common 33 Shield
Shield
36
35 Shield
38
37
Shield
39
Shield
Shield Shield Shield
40
To SPG
Figure E1-6 illustrates an example of wiring an external potentiometer to the module using twisted pair wire. For this example, set up the channel initialization function (A_INCHIT) in software for 5 V unipolar with a filter of 100 ms.
E.1 -6
Page 341
Input Analog Module (8 channel)
The 5 V power supply output voltage adjustment can be set for the maximum potentiometer output value. For example, the supply could be adjusted until the VALU output of the analog input channel read function (A_INCHRD) reads 4095 (12-bit) or 16383 (14-bit) with the pot at its maximum position. Figure E1-14. Adding an External Potentiometer
1K to 50K Pot
1 3 5
Common
Ch 1 -
5Volt
+ Adjustable Regulated
- Power supply
Ch 1 250 ohm Resistor
30 31 Common
32 33
Shield
Shield
34 35
Shield
36
Shield
37
Shield
Shield
38 39
Shield Shield
Ch 1 +
40
Shield
To SPG
Theory of Operation
A 12- or 14- bit A/D converter samples each channel in sequence at the input scan rate. These values are stored in memory on the module so that any channel value can be read while the A/D converter is processing another channel sample. Each channel can be set up for a maximum input sensitivity of .125 V to 10 V, bipolar or unipolar, or for 4 to 20 mA or 0 to 20 mA current input. To sense current the internal 250 Ω resistor must be connected as shown in Figures E1-4 or E15. All inputs are differential with the input signals electrically isolated from the logic side and filtered for a high degree of noise immunity. The default noise filter time constant is 1 ms. If more noise filtering is required, two longer time constants, 10 ms and 100 ms, are software selectable. The longer time constants will improve noise immunity but lengthen signal response time. Using the longer time constants may reduce closed position loop performance if the input is used for position feedback. E.1 -7
Page 342
Input Analog Module (8 channel)
Specification Table
Characteristic
Input Analog (8 ch) module specification
Function
Converts an analog input signal into a 12- or 14-bit digital word for each of eight channels.
Part number
12-bit 502-03642-03
Field side connector
40 pin card edge connector, screw terminals
Input channels
8
Resolution
12 bits, or 4096 steps over the full input range 14 bits, or 16384 steps over the full input range
14-bit 502-04050-00
Input sensitivity (software selectable) Voltage ranges
Current range
Unipolar
Bipolar
0 to 10 V 0 to 5V 0 to 2.5 V 0 to 1.25 V 0 to 1V 0 to .5 V 0 to .25 V 0 to .125 V
±10 V ±5 V ±2.5 V ±1.25V ±1 V ±.5 V ±.25 V ±.125 V
0 to 20 mA, 4 to 20 mA
Common mode maximum voltage ±40V (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.)
±11V
Internal current sense resistor
250 ohms
Maximum current sense resistor power .12 W Differential input resistance (each input to ground)
1 M Ohms
Filter time constant - software selection
1 ms, 10 ms, 100 ms
E.1 -8
Page 343
Input Analog Module (8 channel)
Accuracy of 4-20 mA range
12-bit - .2% of FSR at 25oC 14-bit - .15% of FSR at 25oC ± 100 PPM /oC
Accuracy of all other ranges
12-bit - .5% of FSR at 25oC 14-bit - .2% of FSR at 25oC ± 100 PPM /oC
0 Offset
12-bit-from ±2 counts @ 10V to ±8 counts @ .125V 14-bit-from ±5 counts @ 10V to ±40 counts @ .125V
Logic side power requirements (typical)
120 mA @ +5V 112 mA @ +15V
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
E.1 -9
Page 344
Input Analog Module (8 channel)
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
E.1 -10
Four shocks per axis (15g/11 msec)