E.1 - Input Analog Module (8 channel) Introduction

The analog input module is designed to interface the PiC with voltage or current output devices to monitor such things as pressure, flow, speed, position, or temperature. There are two versions of the analog input module available. One has 12bit resolution and the other has 14-bit resolution. The module has eight independent analog conversion channels. Each channel converts a unipolar or bipolar analog input voltage or current into a 12- or 14- bit digital value. This data is transmitted to the PiCs CPU for processing. There is an internal current sense resistor for each channel for use with 0 to 20 mA or 4 to 20 mA devices. This module contains no user adjustable potentiometers or hardware switches. All necessary gain adjustments are done in software. The analog module can be configured as a feedback module using the Servosetup software. The DIAG LED goes on briefly while the diagnostic tests are running. Figure E1-9. INPUT ANALOG Module (8 CH) INPUT ANALOG

Name of module Diagnostic LED

DIAG

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25 27 29 31 33 35 37 39

Door

AA60-3290

E.1 -1

Page 336

Input Analog Module (8 channel)

Connections

All signals to the input module must come to the screw terminal connectors through shielded twisted pair wires. See the discussion in the Hardware chapter on "Preventing electrical noise in data lines". Each input channel has three connection pins. (See Figure E1-2.) The signals are: +voltage input -voltage input 250 ohm current sense resistor for 0/20 mA and 4/20 mA applications There are five common connection pins. All five pins are interconnected within the module so that they are the same point electrically. These pins are internally connected to the Single Point Ground (SPG). In addition the module has nine screw connections for terminating the shields. All nine are interconnected within the module so they are the same point electrically. These pins are internally connected to SPG. The shield at the device end of the cable is not connected.

E.1 -2

Page 337

Input Analog Module (8 channel)

Figure E1-2 shows the assignments for all the screw terminal connections on the module. Figure E1-10. Connections for the Input Terminals SCREW TERMINALS CONNECTIONS

CONNECTIONS

2

1

Ch 1 +

3

Ch 1 -

5

Ch 1 250 ohm Resistor

7

Ch 3 +

9

Ch 3 -

11

Ch 3 250 ohm Resistor

13

Ch 5 +

15

Ch 5 -

17

Ch 5 250 ohm Resistor

19

Ch7 +

21

Ch 7 -

23

Ch 7 250 ohm Resistor

Ch 2 +

4 Channel 2

Channel 1

Ch 2 -

6 Ch 2 250 ohm Resistor

8 Ch 4 +

10 Channel 4

Channel 3

Ch 4 -

12 Ch 4 250 ohm Resistor

14 Ch 6 +

16 Channel 6

Channel 5

Ch 6 Ch 6 250 ohm Resistor

18 20

Ch 8 +

22 Channel 8

Channel 7

Ch 8 -

24 Ch 8 250 ohm Resistor

25

Not used Not used

26

Common Common

28

Common Common

30

Common Shield

32

Shield Shield Shield

34

Shield

36 38

Shield Shield

29

Common Pins 27 to 31 (No external connection)

31 33 35 Shield Pins 32 to 40

Shield Shield

27

40

37 39

E.1 -3

Page 338

Input Analog Module (8 channel)

When connecting an analog voltage output device to the module, the positive wire of the twisted pair goes to the + screw terminal and the negative wire goes to the - screw terminal. Figure E1-3 illustrates these connections for channel one. Notice that no connection is made to the screw terminal with the internal 250 Ω resistor when connecting a voltage source device. Figure E1-11. Voltage Input Connections

1

Ch 1 +

3

Ch 1 -

5

Ch 1 250 ohm Resistor

+ Voltage -

30 31 Common

32 33

Shield

34 35

Shield

Shield

36 37

Shield

Shield

38 39

Shield Shield

Shield

40

Shield

To SPG

E.1 -4 signal source

Page 339

Input Analog Module (8 channel)

When using a 0 to 20 mA or 4 to 20 mA current output device, the positive wire of the twisted pair is connected to the + input and the negative wire is connected to the 250 Ω resistor input. A jumper is placed between the - input and the 250 Ω resistor input as shown in Figure E1-4 (from pin 3 to pin 5 for channel 1). This connects a 250 Ω internal resistor across the input. Figure E1-12. Current Input Connections (0 to 20 or 4 to 20 mA)

1

Ch 1 +

3

Ch 1 -

+ -

Current signal source 0 to 20 or 4 to 20 mA

+ Power - supply

5 Ch 1 250 ohm Resistor

Common

30 31 Common

32 33

Shield

Shield

34 35

Shield

36

Shield

37

Shield

Shield

38 39

Shield Shield

40

Shield

To SPG

E.1 -5

Page 340

Input Analog Module (8 channel)

An alternative method of connecting a two wire 4 to 20 mA current device is shown in Figure E1-5. Place a jumper between the - input and the 250 Ω resistor input. Figure E1-13. Current Input Connections (4 to 20 mA)

Current Signal Source 4-20 mA +Input from power supply

Common

1

Ch 1+

3

Ch 1-

5

Ch 1 250 ohm Resistor

Output

+ Power - Supply

30 32

Shield

34

31 Common 33 Shield

Shield

36

35 Shield

38

37

Shield

39

Shield

Shield Shield Shield

40

To SPG

Figure E1-6 illustrates an example of wiring an external potentiometer to the module using twisted pair wire. For this example, set up the channel initialization function (A_INCHIT) in software for 5 V unipolar with a filter of 100 ms.

E.1 -6

Page 341

Input Analog Module (8 channel)

The 5 V power supply output voltage adjustment can be set for the maximum potentiometer output value. For example, the supply could be adjusted until the VALU output of the analog input channel read function (A_INCHRD) reads 4095 (12-bit) or 16383 (14-bit) with the pot at its maximum position. Figure E1-14. Adding an External Potentiometer

1K to 50K Pot

1 3 5

Common

Ch 1 -

5Volt

+ Adjustable Regulated

- Power supply

Ch 1 250 ohm Resistor

30 31 Common

32 33

Shield

Shield

34 35

Shield

36

Shield

37

Shield

Shield

38 39

Shield Shield

Ch 1 +

40

Shield

To SPG

Theory of Operation

A 12- or 14- bit A/D converter samples each channel in sequence at the input scan rate. These values are stored in memory on the module so that any channel value can be read while the A/D converter is processing another channel sample. Each channel can be set up for a maximum input sensitivity of .125 V to 10 V, bipolar or unipolar, or for 4 to 20 mA or 0 to 20 mA current input. To sense current the internal 250 Ω resistor must be connected as shown in Figures E1-4 or E15. All inputs are differential with the input signals electrically isolated from the logic side and filtered for a high degree of noise immunity. The default noise filter time constant is 1 ms. If more noise filtering is required, two longer time constants, 10 ms and 100 ms, are software selectable. The longer time constants will improve noise immunity but lengthen signal response time. Using the longer time constants may reduce closed position loop performance if the input is used for position feedback. E.1 -7

Page 342

Input Analog Module (8 channel)

Specification Table

Characteristic

Input Analog (8 ch) module specification

Function

Converts an analog input signal into a 12- or 14-bit digital word for each of eight channels.

Part number

12-bit 502-03642-03

Field side connector

40 pin card edge connector, screw terminals

Input channels

8

Resolution

12 bits, or 4096 steps over the full input range 14 bits, or 16384 steps over the full input range

14-bit 502-04050-00

Input sensitivity (software selectable) Voltage ranges

Current range

Unipolar

Bipolar

0 to 10 V 0 to 5V 0 to 2.5 V 0 to 1.25 V 0 to 1V 0 to .5 V 0 to .25 V 0 to .125 V

±10 V ±5 V ±2.5 V ±1.25V ±1 V ±.5 V ±.25 V ±.125 V

0 to 20 mA, 4 to 20 mA

Common mode maximum voltage ±40V (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.)

±11V

Internal current sense resistor

250 ohms

Maximum current sense resistor power .12 W Differential input resistance (each input to ground)

1 M Ohms

Filter time constant - software selection

1 ms, 10 ms, 100 ms

E.1 -8

Page 343

Input Analog Module (8 channel)

Accuracy of 4-20 mA range

12-bit - .2% of FSR at 25oC 14-bit - .15% of FSR at 25oC ± 100 PPM /oC

Accuracy of all other ranges

12-bit - .5% of FSR at 25oC 14-bit - .2% of FSR at 25oC ± 100 PPM /oC

0 Offset

12-bit-from ±2 counts @ 10V to ±8 counts @ .125V 14-bit-from ±5 counts @ 10V to ±40 counts @ .125V

Logic side power requirements (typical)

120 mA @ +5V 112 mA @ +15V

Indicator light, module

DIAG LED goes off after the module passes its diagnostic tests

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

E.1 -9

Page 344

Input Analog Module (8 channel)

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

E.1 -10

Four shocks per axis (15g/11 msec)