Page 321

D.9 - Output Stepper Axis Module (2, 4, or 8 channel) Introduction

The output stepper axis module (SAM) can control up to eight stepper drives. The maximum step rate is ten million steps per second. An external power supply (4.75 VDC to 5.25 VDC) is required for operation. Commands and control data are sent to the module, and status information is received from the module, via the motion.lib software in PiCServoPro. The DIAG LED goes on briefly while the diagnostic tests are running. Figure D9-1. OUTPUT STEPPER Axis Module (2, 4, 8 ch)

OUTPUTSTEPPER

Name of module Diagnostic LED

DIAG

1 3 5 7 9 11 13

Screw terminal connector

15 17 19 21 23 25 27 29 31 33 35 37 39

Door

AA854-2491

D.9 -1

Page 322

Output Stepper Axis Module (2, 4, or 8 channel)

Connections

A screw terminal connection is provided for each output and for the external power supply connection. (See Figure D9-2.) The outputs are optically isolated. (See Figure D9-3.) The external DC supply that powers the output signals should have a wire connected from its 0V (COMMON) terminal directly to the rack's single point ground. The power disconnect switch should be the same one used for the Central Service Module. In the power distribution diagrams in the Hardware chapter, a DC supply was set up according to these guidelines. The external DC supply can be provided by any combination of the following: •

The stepper drive

An external DC supply daisy-chained to several channels • Separate external DC supplies for individual channels •

D.9 -2

Page 323

Output Stepper Axis Module (2, 4, or 8 channel)

Figure D9-2. Screw terminal connection assignments

CONNECTIONS

SCREW TERMINALS

CONNECTIONS CH 1 +V INPUT

CH 2 +V INPUT

1

CH2 STEP/CW

3

CH 2 DIRECTION/CCW

5

CH 2 +V COMMON

7

CH 1 STEP/CW

CH 1 DIRECTION/CCW

Channel 2

Channel 1

CH 1 +V COMMON

SHIELD SHIELD

9 CH 3 +V INPUT

CH 4 +V INPUT

11

CH 4 STEP/CW

13

CH 4 DIRECTION/CCW

15

CH 4 +V COMMON

17

CH 3 STEP/CW

CH 3 DIRECTION/CCW

Channel 4

Channel 3

CH 3 +V COMMON

SHIELD SHIELD

19

CH 6 +V INPUT

21

CH 6 STEP/CW

23

CH 6 DIRECTION/CCW

25

CH 5 +V INPUT

CH 5 STEP/CW

CH 5 DIRECTION/CCW

Channel 6

Channel 5

CH 5 +V COMMON CH 6 +V COMMON

27

SHIELD

29

CH 8 +V INPUT

31

CH 8 STEP/CW

33

CH 8 DIRECTION/CCW

35

CH 8 +V COMMON

37

SHIELD

CH 7 +V INPUT

CH 7 STEP/CW

CH 7 DIRECTION/CCW

Channel 8

Channel 7

CH 7 +V COMMON

SHIELD SHIELD

39 AA855-2491

D.9 -3

Page 324

Output Stepper Axis Module (2, 4, or 8 channel)

Connections for one channel are illustrated on the right in Figure D9-3. +V input to the +V terminal of the external power supply

Step/cw output to the step or clockwise input of the drive

Direction/ccw output to direction or counterclockwise input of the drive

Common to the 0V terminal of the external power supply NOTE: When the drive inputs are optically isolated, tie the 0V of the external power supply to SPG.

Shield

All shield pins on the module are connected to each other internally and AC coupled to SPG. Figure D9-3. Connections for One Channel

Stepper Module

Internal Circuitry Connections CH 1 +V INPUT

1

+5VDC External Supply +V 0V

CH 1 STEP/CW

SPG

3 CH 1 DIRECTION/CCW

5 CH 1 +V COMMON

7 SHIELD

9

SPG

D.9 -4

Page 325

Output Stepper Axis Module (2, 4, or 8 channel)

Connecting the SAM to Stepper Drives

Consult your drive manual regarding the proper connection of an indexer such as the SAM. Four types of drive inputs and the proper connection techniques are shown in Figures D9-4 to D9-7. When working with opto-coupler drive inputs, be sure the input diode is protected by a current-limiting resistor as stated in the following important note.

IMPORTANT There is a limit to the amount of current the input diode of the drive opto-coupler can withstand. If this current is exceeded, the device will be destroyed. The SAM is capable of sinking considerably more current than the 15 mA specified. Most drives having opto-coupler inputs have a series current-limit resistor sized properly for a +5V external supply. If the drive being used has an opto-coupler input but does not have a current-limit resistor or if the current-limit resistor is too small, then one will have to be added externally. Consult your drive manual for information regarding this topic. Following the wiring guidelines listed below will increase the reliability of the SAM/drive system. 1.

Route the wiring from the SAM separately from any high current or electrically noisy wiring.

2.

Keep the wires connecting the SAM to the drive less than 10 feet in length.

3.

Shield the wiring from the SAM. Tie shields to the SAM shield terminal screw and leave the other end of the shield unconnected.

D.9 -5

Page 326

Output Stepper Axis Module (2, 4, or 8 channel)

Opto-Coupler Drive Inputs

The inputs for this type of drive will be: 1.

Step +

2.

Step -

3.

Direction +

4.

Direction -

Make the following connections as illustrated in Figure D9-4: External Power Supply

SAM

Drive

Step/CW to

N/C to Step -

Direction/CCW to

N/C to Direction -

+V Input to

+V to Step + and Direction +

+V Common to

0V to N/C

Figure D9-4. SAM Connections to Opto-Coupler Drive Inputs

+5VDC External Supply +V 0V

Stepper Module

Drive with opto-coupler inputs

SPG CH 1 +V INPUT

Step +

CH 1 STEP/CW

Step -

CH 1 DIRECTION/CCW

Dir +

1

220 Ohm Opto isolator

3 220 Ohm

5 CH 1 +V COMMON

7 SHIELD

9

D.9 -6

Dir Opto isolator

Page 327

Output Stepper Axis Module (2, 4, or 8 channel)

Opto-Coupler with Common Source Drive Inputs

The inputs for this type of drive will be: 1.

Opto power input

2.

Step

3.

Direction

Make the following connections as illustrated in Figure D9-5: External Power Supply

SAM

Drive

Step/CW to

N/C to Step

Direction/CCW to

N/C to Direction

+V Input to

+V to Opto power input

+V Common to

0V to N/C

Figure D9-5. SAM Connections to Opto-Coupler Drive Inputs with Common Source +5V DC External Supply

Drive with opto-coupler (common source) inputs

+V 0V

Stepper Module

SPG

Opto power

Opto isolator

CH 1 +V INPUT

1

220 Ohm CH 1 STEP/CW

3

Step 220 Ohm

CH 1 DIRECTION/CCW

5

Dir CH 1 +V COMMON

Opto isolator

7 SHIELD

9

D.9 -7

Page 328

Output Stepper Axis Module (2, 4, or 8 channel)

Single-Ended Drive Inputs

The inputs for this type of drive will be: 1.

Step

2.

Direction

3.

Signal ground

Make the following connections as illustrated in Figure D9-6: SAM

Power Supply

Drive

Step/CW to

N/C to Step

Direction/CCW to

N/C to Direction

+V Input to

+V to N/C

+V Common to

0V to Signal ground

Figure D9-6. SAM Connections to Single-Ended Drive Inputs +5 VDC External Supply +V 0V

Stepper Module

Drive with single-ended inputs

CH 1 +V INPUT

1

+5V 1K

CH 1 STEP/CW

3

Step +5V

CH 1 DIRECTION/CCW

5

Dir

1K

CH 1 +V COMMON

7 SHIELD

Signal ground

9

AA859-2491

If the pull-up resistors internal to the drive are inadequate, you may need to add external pull-up resistors. Install them as close as possible to the drive.

D.9 -8

Page 329

Output Stepper Axis Module (2, 4, or 8 channel)

Differential Drive Inputs

The inputs for this type of drive will be: 1. Step + 2. Step 3. Direction + 4. Direction 5. Signal ground

Make the following connections as illustrated in Figure D9-7: SAM

Power Supply

Drive

Step/CW to

N/C to Step +

Direction/ CCW to

N/C to Direction +

+V Input to

+V to N/C

+V Common to

0V to Signal ground

Figure D9-7. SAM Connections to Differential Drive Inputs

+5VDC External Supply +V 0V

Drive with differential inputs

Stepper Module

+5V CH 1 +V INPUT

1 CH 1 STEP/CW

+5V

Step + Step -

+5V

+ -

3 CH 1 DIRECTION/CCW

5

Dir + Dir -

CH 1 +V COMMON

7

+ -

Signal ground

SHIELD

9 AA860-2491

If the Step- and Direction- inputs are not biased to one half the external supply by the drive, external voltage dividers will be required. Install them as close to the drive as possible.

D.9 -9

Page 330

Output Stepper Axis Module (2, 4, or 8 channel)

Theory of Operation

The stepper module is part of an open loop control system used to position from one to eight axes. The diagram in Figure D9-8 illustrates one axis being controlled by the SAM. Digital signals from the SAM are converted into fixed increments of motion via the stepper drive. This allows the stepper motor to move the load accurately and reliably by following the number of input steps. Figure D9-8. Open Loop Stepper System PiC900 CPU Data Transfer

SAM Stepper Drive

Stepper Motor

L o a d

The CPU, through the SAM controls the position, velocity, and acceleration of the stepper motor. The number of pulses generated by the SAM provides distance information (steps) and the rate of these pulses provides velocity information (steps/sec). The rate of change of the pulse rate provides acceleration/deceleration information (steps/sec/sec). For safety reasons, the SAM stops outputting pulses to the stepper drive when a scan loss occurs. Valid step rates sent by the CPU for a velocity command (or calculated by the CPU during acceleration or deceleration) are defined by the following equation: 10 × 10 6 ValidRate = -------------------X where X is any integer from 1 to 8,388,609. Refer to the Software Manual for information on controlling the SAM via software.

D.9 -10

Page 331

Output Stepper Axis Module (2, 4, or 8 channel)

Specification Table

Characteristic

Output stepper module (2, 4, 8 ch) specifications

Function

Controls up to eight stepper drives

Part number

502-04077-00 502-04077-20 502-04077-40

+V input (from external supply)

4.75 VDC to 5.25 VDC, 45 mA per connected channel

Step/CW output rating Direction/CCW output rating

Totem pole, 15 mA sink, 5 mA source

Field side connector

40-pin card edge connector, screw terminals

Protection of logic circuits

Optical isolation between the logic and field side

Indicator light, module

A DIAG LED turns OFF when the module passes its diagnostic tests at power-on

Step rate

0 to 10,000,000 steps/sec

Step rate accuracy

Response to scan loss

8 channel 2 channel 4 channel

10 × 10 6 ValidRate = -------------------X where X is any integer from 1 to 8,388,609 Pulse output halted

Logic side power requirements (typi- 140 mA cal) 80 mA 50 mA

8 channel 4 channel 2 channel

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

D.9 -11

Page 332

Output Stepper Axis Module (2, 4, or 8 channel)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

D.9 -12

Four shocks per axis (15g/11 msec)

Page 333