Page 365

E.5 - Output 4-20mA Module (6 channel) Introduction

The 4-20mA output module has six independent 4-20mA conversion channels. Each channel converts a 15-bit digital value into a single ended type 4-20mA analog current output signal. The full range of the output signal is 4mA to 20mA, with a 15-bit resolution of one part in 32,768. A typical use for this module is to supply a control signal to valves. This module contains no user adjusted potentiometers or hardware switches. All necessary adjustments are done in software. The DIAG LED goes on briefly while the diagnostic tests are running. Figure E5-1. OUTPUT 4-20mA Module (6 CH)

OUTPUT 4-20mA

Name of module Diagnostic LED

DIAG

1 3 5 7 9 11 13 15

Screw terminal connector

17 19 21 23 25

Door

AA1047-3991

E.5 -1

Page 366

Output 4-20mA Module (6 channel)

Connections

Two screw terminal connections are assigned to each channel to carry the signals. (See Figure E5-2.) The negative outputs of each channel (CHn) are connected internally to the +V Common. In addition, the module has six screw terminal connections for terminating the shields. All six are connected internally, so they are the same point electrically. Two connections are used to connect an external power supply. Figure E5-2. Screw Terminal Connector Assignments

SCREW TERMINALS CONNECTIONS CH2

CH2

CH4

CH4

1

CONNECTIONS CH1

3

CH1

5

CH3

7

CH3

9

CH5

11

CH5

13

NOT USED

15

+V EXTERNAL

17

+V COMMON

19

SHIELD

21

SHIELD

23

SHIELD

25

(No external connection)

2

4

6

8

10 CH6 12 CH6

NOT USED

NOT USED

14

16 18

NOT USED SHIELD

20

SHIELD

22

SHIELD

24

Each 4-20mA output channel is connected to a receiving device with twisted pair wires. (See Figure E5-3.) For extremely noisy environments, use shielded twisted pair wire. See the discussion on "Preventing electrical noise in data lines" in the Chapter 1 and the EMC Guidelines. E.5 -2

Page 367

Output 4-20mA Module (6 channel)

The shield connections are internally connected to the Single Point Ground (SPG) to which the system rack is connected. No external connection should be made. Figure E5-3. Receiving Devices and Power Supply Connections

SCREW TERMINALS

RECEIVING DEVICE

1

RECEIVING DEVICE CH1 CH1

2 CH2

3

CH2 CH2

CH2

CH1

CH1

4 5

CH3 CH3

6 CH3

CH4

CH4

CH4

CH3

7

CH4

8 9

CH5 CH5

10 CH5

CH6

CH6

CH5

11

CH6 CH6 12

13 Power Supply

14

(Pins 13, 14, 16, and 18 not used)

15

+V External

17

+V Common

19

SHIELD

21

SHIELD

23

SHIELD

+15 V

16 0V

18

SHIELD

20

SHIELD

22

SHIELD

24

TO SINGLEPOINT GROUND

25 (No external connection)

E.5 -3

Page 368

Output 4-20mA Module (6 channel)

Theory of Operation

The CPU module sends the output module a 16-bit digital word for each channel used. Each digital word is converted to a corresponding current within the range 420mA. The current is brought out to a pair of screw terminal connections as a single-ended type current output. You can adjust each channel in software for offset adjustments and gain scaling. For safety reasons, all outputs are automatically reset to 4mA when a scan loss condition occurs. All outputs have clamping diodes and a capacitor to permit the driving of nonresistive (i.e. inductive) loads. All outputs can drive loads whose impedance is less than or equal to: – 3.6V

V EXT -------------- = R LOAD 20mA Example: If VEXT = 24V, then the maximum impedance equals: – 3.6V

24V EXT --------------------= 1020Ω 20mA The load range in this example is from 0 to 1020 Ω. Anytime the load impedance is exceeded, the OPEN flag is set in software. Normally, it is an open circuit that causes this flag to be set.

E.5 -4

Page 369

Output 4-20mA Module (6 channel)

Specification Table

Characteristic

Output 4-20mA (6 ch) specification

Function

Converts a 15-bit digital value into a 4-20mA analog current signal for each of six channels

Part number

502-03681-02

Field side connector

25-pin card edge connector, screw terminals

Output channels

6

Resolution

15 bits, or 32,768 steps over the full output range

Zero Offset

.1% FSR (Full Scale Range)over full temperature range

Accuracy

.1% FSR (Full Scale Range)over full temperature range

Output current, max.

20 mA

Output update time increment

100 µsec

Output voltage after power up

VOUT = IOUT * RLOAD

Response to "scan loss"

All outputs reset to 4mA

Short circuit protection

Current is limited to: IOUT = where IOUT = 4 to 20mA

Indicator light, module

DIAG LED goes off after module passes its diagnostic tests

External power supply +V and current Line and load regulation Maximum noise

+15 V to +24 V: ≥ 250mA .5% 100mV pk-pk

Isolation

Field side has differential isolation via Op Amp buffer between logic and field side The open alarm flag is optically isolated between field and logic side

Logic side power requirements (typical)

125 mA @ +5V 30 mA @+15V 18 mA @ -15V

Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

E.5 -5

Page 370

Output 4-20mA Module (6 channel)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

E.5 -6

Four shocks per axis (15g/11 msec)