The text of a manual · part 43 of 60
PiC900 Hardware Manual: E.5 - Output 4-20mA Module (6 channel)
Pages 365 to 370 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 365
E.5 - Output 4-20mA Module (6 channel) Introduction
The 4-20mA output module has six independent 4-20mA conversion channels. Each channel converts a 15-bit digital value into a single ended type 4-20mA analog current output signal. The full range of the output signal is 4mA to 20mA, with a 15-bit resolution of one part in 32,768. A typical use for this module is to supply a control signal to valves. This module contains no user adjusted potentiometers or hardware switches. All necessary adjustments are done in software. The DIAG LED goes on briefly while the diagnostic tests are running. Figure E5-1. OUTPUT 4-20mA Module (6 CH)
OUTPUT 4-20mA
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25
Door
AA1047-3991
E.5 -1
Page 366
Output 4-20mA Module (6 channel)
Connections
Two screw terminal connections are assigned to each channel to carry the signals. (See Figure E5-2.) The negative outputs of each channel (CHn) are connected internally to the +V Common. In addition, the module has six screw terminal connections for terminating the shields. All six are connected internally, so they are the same point electrically. Two connections are used to connect an external power supply. Figure E5-2. Screw Terminal Connector Assignments
SCREW TERMINALS CONNECTIONS CH2
CH2
CH4
CH4
1
CONNECTIONS CH1
3
CH1
5
CH3
7
CH3
9
CH5
11
CH5
13
NOT USED
15
+V EXTERNAL
17
+V COMMON
19
SHIELD
21
SHIELD
23
SHIELD
25
(No external connection)
2
4
6
8
10 CH6 12 CH6
NOT USED
NOT USED
14
16 18
NOT USED SHIELD
20
SHIELD
22
SHIELD
24
Each 4-20mA output channel is connected to a receiving device with twisted pair wires. (See Figure E5-3.) For extremely noisy environments, use shielded twisted pair wire. See the discussion on "Preventing electrical noise in data lines" in the Chapter 1 and the EMC Guidelines. E.5 -2
Page 367
Output 4-20mA Module (6 channel)
The shield connections are internally connected to the Single Point Ground (SPG) to which the system rack is connected. No external connection should be made. Figure E5-3. Receiving Devices and Power Supply Connections
SCREW TERMINALS
RECEIVING DEVICE
1
RECEIVING DEVICE CH1 CH1
2 CH2
3
CH2 CH2
CH2
CH1
CH1
4 5
CH3 CH3
6 CH3
CH4
CH4
CH4
CH3
7
CH4
8 9
CH5 CH5
10 CH5
CH6
CH6
CH5
11
CH6 CH6 12
13 Power Supply
14
(Pins 13, 14, 16, and 18 not used)
15
+V External
17
+V Common
19
SHIELD
21
SHIELD
23
SHIELD
+15 V
16 0V
18
SHIELD
20
SHIELD
22
SHIELD
24
TO SINGLEPOINT GROUND
25 (No external connection)
E.5 -3
Page 368
Output 4-20mA Module (6 channel)
Theory of Operation
The CPU module sends the output module a 16-bit digital word for each channel used. Each digital word is converted to a corresponding current within the range 420mA. The current is brought out to a pair of screw terminal connections as a single-ended type current output. You can adjust each channel in software for offset adjustments and gain scaling. For safety reasons, all outputs are automatically reset to 4mA when a scan loss condition occurs. All outputs have clamping diodes and a capacitor to permit the driving of nonresistive (i.e. inductive) loads. All outputs can drive loads whose impedance is less than or equal to: – 3.6V
V EXT -------------- = R LOAD 20mA Example: If VEXT = 24V, then the maximum impedance equals: – 3.6V
24V EXT --------------------= 1020Ω 20mA The load range in this example is from 0 to 1020 Ω. Anytime the load impedance is exceeded, the OPEN flag is set in software. Normally, it is an open circuit that causes this flag to be set.
E.5 -4
Page 369
Output 4-20mA Module (6 channel)
Specification Table
Characteristic
Output 4-20mA (6 ch) specification
Function
Converts a 15-bit digital value into a 4-20mA analog current signal for each of six channels
Part number
502-03681-02
Field side connector
25-pin card edge connector, screw terminals
Output channels
6
Resolution
15 bits, or 32,768 steps over the full output range
Zero Offset
.1% FSR (Full Scale Range)over full temperature range
Accuracy
.1% FSR (Full Scale Range)over full temperature range
Output current, max.
20 mA
Output update time increment
100 µsec
Output voltage after power up
VOUT = IOUT * RLOAD
Response to "scan loss"
All outputs reset to 4mA
Short circuit protection
Current is limited to: IOUT = where IOUT = 4 to 20mA
Indicator light, module
DIAG LED goes off after module passes its diagnostic tests
External power supply +V and current Line and load regulation Maximum noise
+15 V to +24 V: ≥ 250mA .5% 100mV pk-pk
Isolation
Field side has differential isolation via Op Amp buffer between logic and field side The open alarm flag is optically isolated between field and logic side
Logic side power requirements (typical)
125 mA @ +5V 30 mA @+15V 18 mA @ -15V
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
E.5 -5
Page 370
Output 4-20mA Module (6 channel)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/ EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
E.5 -6
Four shocks per axis (15g/11 msec)