Page 371
E.6 - Analog Input\±10V Output (4 Channel) Introduction
The analog in/out module provides: 4 analog input channels • 4 analog output channels •
The DIAG LED goes on briefly while the diagnostic tests are running. Figure E6-1. Analog In/± 10V Out Module
IN/OUT ANALOG
Name of module Diagnostic LED
DIAG
1 3 5 7 9 11 13 15
Screw terminal connector
17 19 21 23 25 27 29 31 33 35 37 39
Door
E.6 -1
Page 372
Analog Input\±10V Output (4 Channel)
Connections
All signals to the module must come to the screw terminal connectors through shielded twisted pair wires. Shielded twisted pair wires are used to connect: Each analog output channel to a receiving device. • All analog input signals to the module. •
These wires must be protected against electrical noise because of the speed and/or voltage levels of the signals transmitted through them. See the discussion on "Preventing electrical noise in data lines" in the Hardware chapter and the EMC guidelines. Shields are provided for the analog input section and for the analog output section. Any power supplies used must be connected to SPG. Figure E6-2 shows the assignments for all the screw terminal connections on the module.
E.6 -2
Page 373
Analog Input\±10V Output (4 Channel)
Figure E6-2. Connections for the Analog In/± 10V Out Module Terminals
SCREW TERMINALS
1 CONNECTIONS
CONNECTIONS 3 An In Ch 1+
An In Ch 2+
5 An In Ch 17
Ch 2 250 Ω resistor
9
Analog Input
Ch 1 250 Ω resistor An In Ch 3+ An In Ch 4+
11
Analog Input
An In Ch 2-
An In Ch 3An In Ch 4-
13
Ch 4 250 Ω resistor
15
Shield
17
Shield
19
Ch 3 250 Ω resistor
Analog Input Shields
Shield
Shield
Analog Input Shields
Shield
21
23 An Out Ch 2+
25
An Out Ch 2-
27
An Out Ch 4+
29
An Out Ch 1An Out Ch 3+ An Out Ch 3An Out Ch 4-
31
Shield
33
Shield
35
Shield Shield 37
Analog Output Shields
Shield
Analog Output Shields
Analog Output
Analog Output
An Out Ch 1+
39
E.6 -3
Page 374
Analog Input\±10V Output (4 Channel)
Analog Output Connections
You may connect the differential type output from this module to a single-ended or differential input device. Figure E6-3 shows the difference between the two types of connections. Note that one wire in the twisted pair is connected to the 0 V terminal on the single-ended receiving device. This 0V terminal must be referenced to the SPG through the device's ground connection. Figure E6-3. Differential and single-ended receiving devices
Receiving Device
Analog Out Section
Differential input device
CH1
CH1
GND
To SPG
GND
CH1 CH2
25
Channel 1
27
Channel 2
CH1
CH2
0V
Single-ended input device
To SPG
CH2
33 35 37
Analog Input Connections
Each input channel has three connection pins. The signals are: + voltage input - voltage input 250 ohm current sense resistor for 0/20 mA and 4/20 mA applications When connecting an analog voltage output device to the module, the positive wire of the twisted pair goes to the + screw terminal and the negative wire goes to the screw terminal. Figure E6-4 illustrates these connections for channel one. Notice that no connection is made to the screw terminal with the internal 250 Ω resistor when connecting a voltage source device.
E.6 -4
Page 375
Analog Input\±10V Output (4 Channel)
Figure E6-4. Voltage Input Connections Analog Input Section Voltage + signal source
-
Ch 1 +
5
Ch 1 -
7
Ch 1 250 ohm Resistor
Channel 1
9
To SPG 11 13 15 Shield
17
When using a 0 to 20 mA or 4 to 20 mA current output device, the positive wire of the twisted pair is connected to the + input and the negative wire is connected to the 250 Ω resistor input. A jumper is placed between the - input and the 250 Ω resistor input as shown in Figure E6-5 (from pin 8 to pin 10 for channel 2). This connects a 250 Ω internal resistor across the input. Figure E6-5. Current Input Connections (0 to 20 or 4 to 20 mA) Analog Input Section
Power + supply
-
5
Current signal + source
Ch 2 +
0 to 20 or 4 to 20 mA
Ch 2 Ch 2 250 ohm Resistor
To SPG
7 9 11 13 15
Shield
17
An alternative method of connecting a two wire 4 to 20 mA current device is shown in Figure E6-6. Place a jumper between the - input and the 250 Ω resistor input.
E.6 -5
Page 376
Analog Input\±10V Output (4 Channel)
Figure E6-6. Current Input Connections (4 to 20 mA) Current signal source
Output
+ Input from power supply
Analog Input Section 5 Ch 2 +
Power + supply
Ch 2 -
-
7 9
Ch 2 250 ohm Resistor
11
To SPG 13 15 Shield
17
Figure E6-7 illustrates an example of wiring an external potentiometer to the module using twisted pair wire. For this example, set up the channel initialization function (A_INCHIT) in software for 5 V unipolar with a filter of 100 ms. The 5 V power supply output voltage adjustment can be set for the maximum potentiometer output value. For example, the supply could be adjusted until the VALU output of the analog input channel read function (A_INCHRD) reads 4095 with the pot at its maximum position.
E.6 -6
Page 377
Analog Input\±10V Output (4 Channel)
Figure E6-7. Adding an External Potentiometer Analog Input Section 5Volt + Adjustable Regulated Power supply -
5
1K to 50K Pot
Ch 2 + Ch 2 -
7 9
To SPG
Ch 2 250 ohm Resistor
11 13 15 Shield
17
Analog Output Theory of Operation
The CPU sends the analog output section a 16-bit digital word for each analog output channel used. Each digital word is converted to a corresponding voltage within the range of ±11 V. The voltage is buffered and brought out to a pair of screw terminal connections as a differential type voltage output. This output is less subject to interference from electrical noise than a single-ended output would be. You can adjust each analog output channel in software for offset adjustments, gain scaling, and unipolar outputs. For safety reasons, all outputs are automatically reset to 0 V when a scan loss condition occurs. Analog Input Theory of Operation
A 12 bit A/D converter samples each analog input channel in sequence at the input scan rate. These values are stored in memory on the module so that any channel value can be read while the A/D converter is processing another channel sample. Each channel can be set up for a maximum input sensitivity of .125 V to 10 V, bipolar or unipolar, or for 4 to 20 mA or 0 to 20 mA current input. To sense current the internal 250 Ω resistor must be connected as shown in Figures E6-5 or E6-6. All inputs are differential and filtered for a high degree of noise immunity. The default noise filter time constant is 1 ms. If more noise filtering is required, two longer time constants, 10 ms and 100 ms, are software selectable. The longer time constants will improve noise immunity but lengthen signal response time. E.6 -7
Page 378
Analog Input\±10V Output (4 Channel)
Using the longer time constants may reduce closed position loop performance if the input is used for position feedback. Specification Table
Characteristic
Analog In/±10V Out module specifications
Function
Converts a 16-bit digital word into a ±11V analog output signal for each of four channels Converts an analog input signal into a 12-bit digital word for each of four channels.
Part number
502-03907-03
Logic side power requirements (typical)
192 mA @ +5V 70 mA @ +15V 53 mA @ -15V Analog Output 1 mA per energized output @ +5V 11 mA per energized output @ +15V 11 mA per energized output @ -15V
Field side connection
40 pin card edge connector, screw terminals
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
E.6 -8
Page 379
Analog Input\±10V Output (4 Channel)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204 • Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8 Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
E.6 -9
Page 380
Analog Input\±10V Output (4 Channel)
Analog Output section (4 ch)
Output channels
4
Resolution
16 bits, or 65536 steps over the full output range
Output voltage characteristics Nominal voltage range
± 11 VDC
Voltage accuracy @ 11 V
± 5%
Output current, max. @ ±10V
± 10 mA
Output update time increment
32 µsec
Output voltage after power up
0 V ± 20 mV
Response to "scan loss"
All outputs reset to 0 V ± 20 mV
Output ripple
< 10 mVRMS at 30 KHz
Short circuit protection
Current limited outputs
Response to scan loss
All outputs are reset to the OFF state
Analog Input section (4 ch)
Input channels
4
Resolution
12 bits, or 4096 steps over the full input range
Input sensitivity (software selectable) Voltage ranges
Current range
Unipolar
Bipolar
0 to 10 V 0 to 5V 0 to 2.5V 0 to 1.25V 0 to 1V 0 to .5 V 0 to .25V 0 to .125V
±10 V ±5 V ±2.5 V ±1.25V ±1 V ±.5 V ±.25 V ±.125 V
0 to 20 mA, 4 to 20 mA
Common mode maximum voltage ±40V (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage ±11V (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.) E.6 -10
Page 381
Analog Input\±10V Output (4 Channel)
Internal current sense resistor
250 ohms
Maximum current sense resistor power
.12 W
Differential input resistance (each input to ground)
1 M Ohms
Filter time constant - software selection
1 ms, 10 ms, 100 ms
Accuracy
.5% of FSR at 25oC ± 100 PPM /oC
0 Offset
From ±2 counts @ 10V to ±8 counts @ .125V
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
E.6 -11
Page 382
Analog Input\±10V Output (4 Channel)
E.6 -12
Page 383