Page 431

I.1 - A Wiring Jig Making a jig

The PiC was designed to get maximum controlling power in as small a footprint as possible. This can cause a problem because the screw terminal connectors are difficult to get at when the modules are installed in the rack. If you lay the module on the bench to make connections, the wires may be too short or too long when the system is set up. This puts stress on the connections, which may become disconnected and cause problems. An installation jig brings the connectors out where you can see what you are doing and still cut the wires to the correct length. Directions for making one are given here. Figure I-1. Jig for Wiring I/O Modules

PiC900 system rack CSM

CPU

2 pieces sheet metal 8.5" x 6.5" PiC

PiC

PiC

PiC

PiC

PiC

PiC

PiC

PiC

PiC

1" pine 16.8" x 6.5"

AA115-1390

1. This jig was designed for use with the 10-slot system rack. Cut 10 grooves in the pine board, 3/8" across and 1/2" deep. They will be about 1 1/2" apart. Adjust the length of the board and the number of grooves to fit different sized system racks. 2. The PiC900 system rack already has holes drilled in its sides, 5 1/2" apart. Drill two holes to match along one of the short sides of each metal plate, and three screw holes along the other side.

I.1 -3

Page 432

A Wiring Jig

Figure G1-2. Side plate of the jig pine board system rack

5.5"

6.5"

8.5" AA116-1390

3. Use 3 wood screws to fasten a metal side to one end of the grooved pine board, and repeat with the second metal piece at the other end of the board. The jig is now ready for use. Using a jig

1. Remove the hardware modules in the PiC900 system rack. 2. Unscrew the screw terminal connector from each I/O module and pull it off. 3. Push it into the corresponding groove in the jig, with the top of the screw terminal connector at the top of the jig. Keep the screw terminal connectors in the same order as their modules in the system rack, so you can replace each connector on the correct module. 4. Fit the jig over the rack. Insert 2 fasteners through the drill holes on each side of the jig, into the top and middle holes on the sides of the rack, to keep it in place during wiring. 5. Connect the wires to their assigned screw terminals starting from the bottom left terminal, as shown in the Hardware chapter. 6. When all the wiring is finished, pull each screw terminal connector from its slot in turn. 7. Unfasten the jig and store it. 8. Install hardware modules as specified and push the screw terminal connector on its respective module.

I.1 -4

Page 433

Appendix J - Power-on Circuitry

Page 434

This page is a scan with no text; see it in the PDF.