PiC900 Hardware Manual: J.1 - Power-on Circuitry

Pages 435 to 440 of 508, from PiC900 Hardware Manual

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 435

J.1 - Power-on Circuitry Wiring One Axis to Power-On Circuitry

This appendix presents an explanation of wiring one axis to power-on circuitry. In any application, it is important to provide for the safe starting and stopping of a machine. Variations to this recommended method are acceptable as long as they follow this intent. Figure J-1 on the next page illustrates the power-on circuitry for one axis. Additional axes needed for an application should be wired in a similar manner. 1.

There are three switches in series with the POWER-ON relay: 1. MACHINE ON switch 2. EMERGENCY STOP (E-stop) pushbutton 3. MACHINE START pushbutton The MACHINE ON switch and the EMERGENCY STOP pushbutton are normally closed. The MACHINE START pushbutton must be pressed to energize the POWER-ON relay. It is assumed that power is supplied to this circuit through an output module. This module must have its source power available at all times. A ladder diagram module (LDO) in the PiC900 is used to control the turning on and turning off of power through this module. When the LDO is not being scanned, there is no power supplied through the output module.

2.

When the POWER-ON relay is energized, the POWER-ON contact 2 is used to latch it on. POWER-ON contact 1 and contacts from the series switches are brought back through an input module to be monitored by the LDO.

3.

Since the POWER-ON relay does not typically have enough contacts or does not have contacts of high enough current rating, POWER-ON contact 3 is used to energize an AUXILIARY POWER-ON contactor.

4.

Power is supplied through AUXILIARY POWER ON contact 1 to the AXIS 1 POWER-ON contactor (M1). The plus and minus end-of-travel (EOT) limit switches are wired in series with this path. The END LIMIT OVERRIDE pushbutton is used to allow backing the machine off the limit switch if it is sitting on it. The status of the end limit switches is also brought back through an input module. This allows LDO control over the direction used for moving off an end limit.

J.1 -3

Page 436

Power-on Circuitry

J.1 -4

5.

Power is supplied to other output modules through AUXILIARY POWER-ON contact 2.

6.

When applicable, a contact from relay M1A is used to enable the servo drive for axis 1. This relay is controlled by the LDO. Typically, it is turned on two seconds after the POWER-ON contact 1 is detected as closed.

7.

Losing LDO scan, pressing of the E-STOP PB, or opening the MACHINE ON switch will remove power from machine operations.

Page 437

Power-on Circuitry

Figure J1-1. Recommended Power-On Circuitry

120V AC or 24V DC

PiC900 Output 120V AC (or 24V DC) Module

MACHINE START PB

MACHINE E-STOP ON PB OFF

POWER-ON Relay

ON

+24V

M1A

+24V

+24V

Relay

POWER-ON 2

Input 24V DC Module

AUXILIARY POWER-ON 2

Output 120V AC (or 24V DC) Module

POWER-ON 1

AUXILIARY POWER-ON Contactor

120V AC POWER-ON 3

AUXILIARY POWER-ON 1 AXIS 1 POWER-ON Contactor +EOT LS

-EOT LS M1

+24V

+24V

END LIMIT OVERRIDE PB AA1992890

J.1 -5

Page 438

Power-on Circuitry

J.1 -6

Page 439

Appendix K - Math Coprocessor Installation