PiC900 Hardware Manual: N.2 - I/O Expansion Connections, pages 467 to 475

Pages 467 to 475 of 508, from PiC900 Hardware Manual

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Giddings & Lewis 502-03550-02

Page 467

N.2 - I/O Expansion Connections Expansion Racks

I/O expansion racks can be added to a PiC900 system. There are three methods of connecting an I/O expansion system. 1.

Local - up to seven expansion racks linked to the master rack, with a maximum segment length between racks of 40 feet (12 m), using twisted pair wire. IMPORTANT The twisted pair interface should only be used for racks within the same enclosure and supplied by the same AC power source. Otherwise electrical noise problems may occur. Noise related problems can be eliminated by using the fiber optic interface in remote expansion.

2.

Remote - up to seven expansion racks linked to a master rack, with a maximum segment length between racks of 2000 feet (610 m), using fiber optic cable.

The expansion rack must have either a CSM or a RSM module in slot 1 and an I/O driver module in slot 2. If a PiC90 is used as an expansion rack, it must have the RSM/IO driver module in slot 1/2. The following can be used in the master rack of an I/O expansion system. CPU Module in Master Rack

Number of Expansion Racks Supported

PiC9XX CPU with communication capabilities

1 to 7 racks

The following expansion racks can be used in an I/O expansion system. Expansion Rack

Number of Slots Available

PiC90 with RSM I/O driver

3 or 5 slots

PiC900 with RSM or CSM and I/O driver

7, 10, or 13 slots

It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are up to 40 feet apart and use fiber optic cable to connect racks that are up to 2000 feet apart. Ring, or loop, topology is used for the layout of an expansion system. The ‘out’ of the last expansion rack is connected to the ‘in’ of the master rack. Rack numbers are assigned in the order each expansion rack is wired in the loop.

N.2 -1

Page 468

I/O Expansion Connections

IMPORTANT Because of the ring configuration, all expansion racks must be present and have power applied in order for I/O expansion to function properly. 3.

Block I/O - up to 77 block I/O modules in an expansion system. Maximum distance between block modules is 200 feet using shielded twisted pair wire.

Local I/O Expansion

Whenever the wire segments from rack to rack are less than 40 feet (12 m), twisted pair wiring can be used. 18 to 20 AWG stranded twisted pair wire is typically used. Local I/O expansion is intended for connecting expansion racks mounted in the same control cabinet as the master rack. One PiC9XX layout possibility is illustrated in Figure N2-1. Notice that the expansion system forms a loop with expansion rack eight connected to the master rack. A loop configuration is required for all expansion systems. Figure N2-1. Local Expansion Layout for a PiC9XX Master Rack

PiC9XX Master Out Rack In

PiC9XX Expansion In Rack Out 1

PiC9XX ExpansionIn Rack Out 2 Each twisted pair segment length 40' maximum PiC9XX Expansion In Rack Out 3

PiC9XX Expansion In Rack Out 4

N.2 -2

PiC9XX Expansion In Rack Out 5

PiC9XX ExpansionIn Rack Out 6

PiC9XX Expansion In Rack Out 7

Page 469

I/O Expansion Connections

Local Expansion with a PiC9XX

The connections made from the PiC9XX communications connector on the CPU module in the master rack to the twisted pair connector on the I/O driver in an expansion rack is shown in Figure N2-2. This represents a system with only one expansion rack in the loop. If more racks were included in the system, they would be wired similarly running the twisted pair out of expansion rack 1 to the twisted pair in of expansion rack 2, and so on until the final expansion rack is wired. The twisted pair out of the final rack is run to the twisted pair in of the master rack so that a loop is created. Figure N2-2. Twisted Pair Connections for Local I/O Expansion (PiC9XX to PiC9XX)

Master Rack PiC9XX CPU

Expansion Rack I/O driver

CPU

I/O Driver

DIAG

DIAG

CONFIG

CONFIG

INOUT

DATA IN

DATA TX ACT

DATA OUT

ARCNET IN OUT

RS232

PiC900 ™

In

Out

In

Out

N.2 -3

Page 470

I/O Expansion Connections

Local Expansion with a PiC9XX and a PiC90

The connections made from the PiC9XX communications connector on the CPU module in the master rack to the twisted pair connector on the PiC90 RSM I/O driver in an expansion rack is shown in Figure N2-3. This represents a system with only one expansion rack in the loop. If more racks were included in the system, they would be wired similarly running the twisted pair out of expansion rack 1 to the twisted pair in of expansion rack 2, and so on until the final expansion rack is wired. The twisted pair out of the final rack is run to the twisted pair in of the master rack so that a loop is created. Figure N2-3. Twisted Pair Connections for Local I/O Expansion (PiC9XX to PiC90)

Master Rack PiC9XX CPU CPU

Expansion Rack RSM I/O driver RSM I/O

DIAG CONFIG IN OUT

DATA TX ACT

ARCNET

DIAG PWR/SCAN CONFIG DATA IN/OUT

IN OUT

RS232 Run Stop

PiC900 ™

I/O local expansion twisted pair out

ON OFF

I/O local expansion twisted pair in

L / LINE1 N / LINE2 E / GRND

I/O local expansion twisted pair out I/O local expansion twisted pair in

In

N.2 -4

Out In

Out

Page 471

I/O Expansion Connections

Remote I/O Expansion

When isolation is required or the segments from rack to rack are more than 40 feet (12 m), fiber optic cable is used. The fiber optic connectors are found on the bottom of the PiC900 modules. Fiber optic segments can be up to 2,000 feet (610 m) in length. The total loop length should be less than 4,000 feet (1,210 m). One layout possibility is illustrated in Figure N2-4. Notice that the expansion system forms a loop with the expansion rack seven connected to the master rack. A loop configuration is required for all expansion systems. Figure N2-4. Remote I/O layout for a PiC900 master rack

Master Rack

PiC9XX Expansion Rack 1

PiC9XX Expansion Rack 2

In Out

In Out

In Out

PiC9XX

PiC9XX Expansion Rack 5 Out

In

Expansion Rack 3

Out In

Out

PiC9XX Expansion Rack 7 Out

PiC9XX

PiC9XX Expansion Rack 4

In

PiC9XX Expansion Rack 6 Out

In

In

A fiber optic segment can be up to 2000' maximum. However, the total loop length should be less than 4000'.

N.2 -5

Page 472

I/O Expansion Connections

Fiber Optic Cables

Fiber optic cables for remote I/O expansion are available in various lengths with connectors attached. It is also possible to order the cable and connectors separately. Item

Part number

Cable with connectors 502-037XY-YY* Cable

401-54631-00

Connector

401-54652-00

*The XY-YY part of the part number allows you to enter the length of the cable you are ordering. Cable can be ordered any length from 4 feet to 2,000 feet. The X may be a 0, 1, or 2. The Ys may be any digit from 0 to 9. For example, to order a 4 foot cable, the part number would be: 502-03700-04 To order a 1,234 foot cable, the part number would be: 502-03712-34 If fabricating your own cable, it must have the characteristics shown in the fiber optic cable specification table. Handling Precautions

When working with fiber optic cable, the following precautions should be followed. 1.

Keep the slip covers on the ends of the connectors until ready to hook up.

2.

When routing cable through difficult runs, use a simplex pulling grip.

3.

Do not exceed the recommended tensile strength. (Tensile strength is the ability of a fiber to be stretched or pulled without breaking.)

4.

Do not exceed the recommended bend radius. (Bend radius is a limit on how much the fiber should be bent. Bends increase attenuation slightly and decrease tensile strength.) Bends tighter than a 2 inch radius may cause permanent damage to the cable

See the fiber optic cable specification table at the end of this appendix. Connecting ST Style Fiber Optic Connector to the Module Connector

The procedure for connecting the ST style connector to the module connector is as follows:

N.2 -6

1.

Remove the protective cap from the ceramic tip of the ST style connector.

2.

Find the slot on the module connector and line up the notch on the ST style connector with it.

Page 473

I/O Expansion Connections

3.

Push the spring-loaded latch section of the ST connector up to the notch on the module connector and twist to lock in place. Figure N2-5. Connecting Fiber Optic Cable to Module

Slot Ceramic end of fiber optic cable Notch to slide into slot above

Connector on module Notch to lock latch onto Latch

ST style connector on fiber optic cable

AA842-1191

N.2 -7

Page 474

I/O Expansion Connections

For remote I/O expansion, the I/O expansion fiber optic in and out cables are connected to the connectors located on the bottom of the module as shown in Figure N2-6. Figure N2-6. Fiber Optic Connections for PiC9XX Remote I/O Expansion

Master Rack PiC9XX CPU

Expansion Rack I/O driver I/O Driver

CPU DIAG

DIAG

CONFIG

CONFIG

DATA IN

IN OUT DATA OUT

DATA TX ACT

ARCNET IN OUT

RS232

PiC900 ™

In In

N.2 -8

Out

Out

Page 475

I/O Expansion Connections

Peer-to-Peer and Remote I/O Expansion

Figure N2-7 illustrates both peer-to-peer and I/O expansion with the PiC9XX with communication capabilities. Figure N2-7. Peer-to-Peer (between two PiC9XXs) and I/O Expansion Connections

PiC9XX 2

CPU

PiC9XX 1

Expansion Rack I/O driver

CPU

Master Rack DIAG

DIAG

CONFIG

CONFIG

IN OUT

DATA

DATA TX ACT

TX ACT

DATA IN

IN OUT

DATA OUT

ARCNET OUT

RS232

Peer-to-peer twisted pair interface

DIAG CONFIG

IN OUT

ARCNET IN

RS232

PiC900 ™

PiC900 ™ Peer-to-peer communications

100 ohm resistor

Peer-to-peer twisted pair interface

100 ohm resistor

In In

I/O Driver

Out

In

Out

Out

I/O remote expansion

N.2 -9