N.2 - I/O Expansion Connections Expansion Racks
I/O expansion racks can be added to a PiC900 system. There are three methods of connecting an I/O expansion system. 1.
Local - up to seven expansion racks linked to the master rack, with a maximum segment length between racks of 40 feet (12 m), using twisted pair wire. IMPORTANT The twisted pair interface should only be used for racks within the same enclosure and supplied by the same AC power source. Otherwise electrical noise problems may occur. Noise related problems can be eliminated by using the fiber optic interface in remote expansion.
2.
Remote - up to seven expansion racks linked to a master rack, with a maximum segment length between racks of 2000 feet (610 m), using fiber optic cable.
The expansion rack must have either a CSM or a RSM module in slot 1 and an I/O driver module in slot 2. If a PiC90 is used as an expansion rack, it must have the RSM/IO driver module in slot 1/2. The following can be used in the master rack of an I/O expansion system. CPU Module in Master Rack
Number of Expansion Racks Supported
PiC9XX CPU with communication capabilities
1 to 7 racks
The following expansion racks can be used in an I/O expansion system. Expansion Rack
Number of Slots Available
PiC90 with RSM I/O driver
3 or 5 slots
PiC900 with RSM or CSM and I/O driver
7, 10, or 13 slots
It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are up to 40 feet apart and use fiber optic cable to connect racks that are up to 2000 feet apart. Ring, or loop, topology is used for the layout of an expansion system. The ‘out’ of the last expansion rack is connected to the ‘in’ of the master rack. Rack numbers are assigned in the order each expansion rack is wired in the loop.
N.2 -1
Page 468
I/O Expansion Connections
IMPORTANT Because of the ring configuration, all expansion racks must be present and have power applied in order for I/O expansion to function properly. 3.
Block I/O - up to 77 block I/O modules in an expansion system. Maximum distance between block modules is 200 feet using shielded twisted pair wire.
Local I/O Expansion
Whenever the wire segments from rack to rack are less than 40 feet (12 m), twisted pair wiring can be used. 18 to 20 AWG stranded twisted pair wire is typically used. Local I/O expansion is intended for connecting expansion racks mounted in the same control cabinet as the master rack. One PiC9XX layout possibility is illustrated in Figure N2-1. Notice that the expansion system forms a loop with expansion rack eight connected to the master rack. A loop configuration is required for all expansion systems. Figure N2-1. Local Expansion Layout for a PiC9XX Master Rack
PiC9XX Master Out Rack In
PiC9XX Expansion In Rack Out 1
PiC9XX ExpansionIn Rack Out 2 Each twisted pair segment length 40' maximum PiC9XX Expansion In Rack Out 3
PiC9XX Expansion In Rack Out 4
N.2 -2
PiC9XX Expansion In Rack Out 5
PiC9XX ExpansionIn Rack Out 6
PiC9XX Expansion In Rack Out 7
Page 469
I/O Expansion Connections
Local Expansion with a PiC9XX
The connections made from the PiC9XX communications connector on the CPU module in the master rack to the twisted pair connector on the I/O driver in an expansion rack is shown in Figure N2-2. This represents a system with only one expansion rack in the loop. If more racks were included in the system, they would be wired similarly running the twisted pair out of expansion rack 1 to the twisted pair in of expansion rack 2, and so on until the final expansion rack is wired. The twisted pair out of the final rack is run to the twisted pair in of the master rack so that a loop is created. Figure N2-2. Twisted Pair Connections for Local I/O Expansion (PiC9XX to PiC9XX)
Master Rack PiC9XX CPU
Expansion Rack I/O driver
CPU
I/O Driver
DIAG
DIAG
CONFIG
CONFIG
INOUT
DATA IN
DATA TX ACT
DATA OUT
ARCNET IN OUT
RS232
PiC900 ™
In
Out
In
Out
N.2 -3
Page 470
I/O Expansion Connections
Local Expansion with a PiC9XX and a PiC90
The connections made from the PiC9XX communications connector on the CPU module in the master rack to the twisted pair connector on the PiC90 RSM I/O driver in an expansion rack is shown in Figure N2-3. This represents a system with only one expansion rack in the loop. If more racks were included in the system, they would be wired similarly running the twisted pair out of expansion rack 1 to the twisted pair in of expansion rack 2, and so on until the final expansion rack is wired. The twisted pair out of the final rack is run to the twisted pair in of the master rack so that a loop is created. Figure N2-3. Twisted Pair Connections for Local I/O Expansion (PiC9XX to PiC90)
Master Rack PiC9XX CPU CPU
Expansion Rack RSM I/O driver RSM I/O
DIAG CONFIG IN OUT
DATA TX ACT
ARCNET
DIAG PWR/SCAN CONFIG DATA IN/OUT
IN OUT
RS232 Run Stop
PiC900 ™
I/O local expansion twisted pair out
ON OFF
I/O local expansion twisted pair in
L / LINE1 N / LINE2 E / GRND
I/O local expansion twisted pair out I/O local expansion twisted pair in
In
N.2 -4
Out In
Out
Page 471
I/O Expansion Connections
Remote I/O Expansion
When isolation is required or the segments from rack to rack are more than 40 feet (12 m), fiber optic cable is used. The fiber optic connectors are found on the bottom of the PiC900 modules. Fiber optic segments can be up to 2,000 feet (610 m) in length. The total loop length should be less than 4,000 feet (1,210 m). One layout possibility is illustrated in Figure N2-4. Notice that the expansion system forms a loop with the expansion rack seven connected to the master rack. A loop configuration is required for all expansion systems. Figure N2-4. Remote I/O layout for a PiC900 master rack
Master Rack
PiC9XX Expansion Rack 1
PiC9XX Expansion Rack 2
In Out
In Out
In Out
PiC9XX
PiC9XX Expansion Rack 5 Out
In
Expansion Rack 3
Out In
Out
PiC9XX Expansion Rack 7 Out
PiC9XX
PiC9XX Expansion Rack 4
In
PiC9XX Expansion Rack 6 Out
In
In
A fiber optic segment can be up to 2000' maximum. However, the total loop length should be less than 4000'.
N.2 -5
Page 472
I/O Expansion Connections
Fiber Optic Cables
Fiber optic cables for remote I/O expansion are available in various lengths with connectors attached. It is also possible to order the cable and connectors separately. Item
Part number
Cable with connectors 502-037XY-YY* Cable
401-54631-00
Connector
401-54652-00
*The XY-YY part of the part number allows you to enter the length of the cable you are ordering. Cable can be ordered any length from 4 feet to 2,000 feet. The X may be a 0, 1, or 2. The Ys may be any digit from 0 to 9. For example, to order a 4 foot cable, the part number would be: 502-03700-04 To order a 1,234 foot cable, the part number would be: 502-03712-34 If fabricating your own cable, it must have the characteristics shown in the fiber optic cable specification table. Handling Precautions
When working with fiber optic cable, the following precautions should be followed. 1.
Keep the slip covers on the ends of the connectors until ready to hook up.
2.
When routing cable through difficult runs, use a simplex pulling grip.
3.
Do not exceed the recommended tensile strength. (Tensile strength is the ability of a fiber to be stretched or pulled without breaking.)
4.
Do not exceed the recommended bend radius. (Bend radius is a limit on how much the fiber should be bent. Bends increase attenuation slightly and decrease tensile strength.) Bends tighter than a 2 inch radius may cause permanent damage to the cable
See the fiber optic cable specification table at the end of this appendix. Connecting ST Style Fiber Optic Connector to the Module Connector
The procedure for connecting the ST style connector to the module connector is as follows:
N.2 -6
1.
Remove the protective cap from the ceramic tip of the ST style connector.
2.
Find the slot on the module connector and line up the notch on the ST style connector with it.
Page 473
I/O Expansion Connections
3.
Push the spring-loaded latch section of the ST connector up to the notch on the module connector and twist to lock in place. Figure N2-5. Connecting Fiber Optic Cable to Module
Slot Ceramic end of fiber optic cable Notch to slide into slot above
Connector on module Notch to lock latch onto Latch
ST style connector on fiber optic cable
AA842-1191
N.2 -7
Page 474
I/O Expansion Connections
For remote I/O expansion, the I/O expansion fiber optic in and out cables are connected to the connectors located on the bottom of the module as shown in Figure N2-6. Figure N2-6. Fiber Optic Connections for PiC9XX Remote I/O Expansion
Master Rack PiC9XX CPU
Expansion Rack I/O driver I/O Driver
CPU DIAG
DIAG
CONFIG
CONFIG
DATA IN
IN OUT DATA OUT
DATA TX ACT
ARCNET IN OUT
RS232
PiC900 ™
In In
N.2 -8
Out
Out
Page 475
I/O Expansion Connections
Peer-to-Peer and Remote I/O Expansion
Figure N2-7 illustrates both peer-to-peer and I/O expansion with the PiC9XX with communication capabilities. Figure N2-7. Peer-to-Peer (between two PiC9XXs) and I/O Expansion Connections
PiC9XX 2
CPU
PiC9XX 1
Expansion Rack I/O driver
CPU
Master Rack DIAG
DIAG
CONFIG
CONFIG
IN OUT
DATA
DATA TX ACT
TX ACT
DATA IN
IN OUT
DATA OUT
ARCNET OUT
RS232
Peer-to-peer twisted pair interface
DIAG CONFIG
IN OUT
ARCNET IN
RS232
PiC900 ™
PiC900 ™ Peer-to-peer communications
100 ohm resistor
Peer-to-peer twisted pair interface
100 ohm resistor
In In
I/O Driver
Out
In
Out
Out
I/O remote expansion
N.2 -9