The text of a manual · part 58 of 60
PiC900 Hardware Manual: N.2 - I/O Expansion Connections, pages 476 to 484
Pages 476 to 484 of 508, from PiC900 Hardware Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 476
I/O Expansion Connections
Figure N2-8 illustrates both peer-to-peer and I/O expansion when the I/O expansion rack is a PiC90. Figure N2-8. Peer-to-Peer (between two PiC900s) and I/O Expansion Connections PiC9XX 2
CPU
PiC9XX 1
CPU
Expansion Rack RSM I/O RSM I/O Driver
Master Rack DIAG
DIAG
CONFIG
CONFIG
IN OUT
IN OUT
DATA
DATA IN/OUT
DATA TX ACT
TX ACT
ARCNET
ARCNET IN
OUT
IN OUT
RS232
Peer-to-peer twisted pair interface
DIAG PWR/SCAN CONFIG
PiC900
Run
RS232
PiC900
™
™
Stop
Peer-to-peer twisted pair interface
Peer-to-peer communications ON 100 ohm resistor
OFF
100 ohm resistor
L / LINE1 N / LINE2 E / GRND
In
Out
In
Out
In
I/O remote expansion
N.2 -10
Out
Page 477
I/O Expansion Connections
Specification Table for Fiber Optic Cable Characteristics
Fiber optic cable specifications
Function
For use with I/O expansion from 4 to 2,000 feet.
Part number
Cable with connectors 502-037XY-YY Cable only 401-54631-00 Connector only 401-54652-00
Type
Glass plenum or non-plenum
Size
62.5/125 µm
Operating temperature
0˚ C to 55˚ C (32˚ F to 131˚ F)
Bend radius
Greater than 2 inches during installation and operation
Tensile strength
110 # during installation and operation
Connectors
ST style which accommodates 62.5/125 µm size cable
N.2 -11
Page 478
I/O Expansion Connections
Block I/O Expansion
Block I/O is a self-contained I/O interface with its own logic power supply derived from an external 24V DC source. Each block has a communication interface that includes two transmitters (RS485) and two receivers (optically isolated). Blocks differ as to the type of I/O interface (analog or digital) provided. Block I/O is an alternative to PiC900 rack I/O expansion. It is used to distribute small groups of interface logic close to the actual location of I/O devices. It allows you to replace long runs of I/O cables with twisted pairs of communication wires. The Block I/O footprint has been minimized for easy installation into small enclosures or junction boxes. Block I/O cannot be intermixed within a rack I/O expansion loop. Block I/O uses a slower data rate and optical isolation to accommodate longer distances between modules. It requires the latest version of the PiC9XX CPU with the block I/O interface option. Block I/O modules can be mounted directly to a panel or to a DIN rail. The package contains a metal piece that is used to make contact with the module when used with a Din rail. For an alternate connection to chassis or for panel mounting, a terminal pin is provided. Chassis connection is required for conformance to EMC standards. There are two 5-pin communications connectors and four logic LEDs on the top of the block I/O module as shown in Figure N2-9 below.
N.2 -12
Page 479
I/O Expansion Connections
Figure N2-9. Pinouts for Communication Connectors
1 Driver +
2
(twisted pair output)
3
Driver -
Receiver +
(twisted pair input)
Receiver -
4
(twisted pair output)
Pin # 5 (twisted pair input)
Receiver +
1 (twisted pair input)
Receiver -
2
Shield
Out (to next block I/O module
(twisted pair input)
3 Shield
Driver +
(twisted pair output)
4
(twisted pair output)
Pin # 5 Driver -
In (from CPU)
Communications Receive/Transmit
In Out
ConfPwr
Logic LEDs GIDDINGS & LEWIS® OUTPUT 24VDC SOURCE
LEDs
The four LEDs are described below. LED
Color
State
Definition
DATA IN
Yellow
DATA OUT
Yellow
CONFG
Green
ON OFF ON OFF ON
Indicates the line is active No activity Indicates the line is active No activity Communication established with this block I/O module Communication not established Internal +5V logic power supply OK No external 24V applied or internal 5V logic supply not OK
PWR
Green
OFF ON OFF
More information about using the LEDs for troubleshooting is available in Appendix P.
N.2 -13
Page 480
I/O Expansion Connections
One possible layout for PiC900 expansion using block I/O modules is shown in Figure N2-10. There can be up to 200 feet between block I/O modules. The recommended wire is Belden 9729, 24 AWG stranded conductors, twisted pair (100Ω characteristic impedance) with shield. Figure N2-10. Block I/O Layout for PiC900 Expansion PiC900/90 Master Rack T R
Block I/O Modules T
R
T
R
T
R
T
R
R
T
R
T
R
T
R
T
T R
R
T
T
R
R
T
T
R
The distance between block I/O modules can be up to 200 feet.
R
T
R
T
R
T
Up to 77 modules T
R
R
T
NOTE: Unlike wiring for I/O expansion racks, it is not necessary to return the last block I/O module back to the PiC900. The interconnecting cable between block I/O modules contains both a forward and a return communication path.
N.2 -14
Page 481
I/O Expansion Connections
Figure N2-11 shows the connections between a PiC9XX master rack and a block I/O module. To add the next block I/O module, twisted pair wire would be connected to the 5-pin connector on the upper right side of the block I/O module. Figure N2-11. PiC9XX CPU to Block I/O Module Connections
Master Rack PiC9XX CPU CPU DIAG CONFIG INOUT
DATA TX ACT
ARCNET INOUT
RS232
PiC900
I/O Expansion twisted pair out I/O Expansion twisted pair in Shield
1 2 3 4 5 6 7
Twisted pair in
™
Shields 5 4 3 2 1 GIDDINGS & LEWIS ® Twisted pair out
BLOCK I/O
Shield
In
Out
N.2 -15
Page 482
I/O Expansion Connections
NOTES
N.2 -16
Page 483
Appendix O - EMC Guidelines