Page 101

RTD Module (6 channel)

RTD Module (6 channel) The input RTD (resistance temperature detector) module has 6 independent RTD conversion channels which receive signals from 50 ¾ or 100 ¾ RTDs. Each channel converts a resistance into a 12-bit digital word which is processed by the PiC. This module requires no hardware adjustments. All adjustments such as Fahrenheit or Celsius scaling and temperature ranges are software selectable. The DIAG LED turns on briefly while the diagnostic tests are running.

INPUT RTD Module (6 ch)

INPUT

Name of Module Diagnostic LED

RTD

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

97

Page 102

RTD Module (6 channel) Specification Table

Characteristic

RTD module specification

Function

Measures 50 ¾ and 100 ¾ RTD inputs

Part Number

(M.1016.9154) (old # 502-03679-02)

Field side connector

25-pin card edge connector, screw terminals

Input channels

6

Resolution

12 bits

RTD types

European curve (Alpha = .00385) for 50 ¾ and 100 ¾ two and three wire RTDs

50 ¾ temperature ranges

-200°C to 850°C -200°C to 266°C

(-328°F to 1562° F) (-328°F to 510.8° F)

100 ¾ temperature ranges

-200°C to 850°C -200°C to 266°C -200°C to 0°C

(-328°F to 1562° F) (-328°F to 510.8° F) (-328°F to 32° F)

Maximum RTD lead wire length 24 AWG or smaller

< 20 feet

20 AWG or larger

2-wire RTD - under 20 feet without lead compensation NOTE: Lead length can affect accuracy of 2-wire RTDs with lengths over 20 feet. 2-wire RTD - up to 5000 feet with lead compensation 3-wire RTD - up to 1000 feet without lead compensation 3-wire RTD - up to 5000 feet with lead compensation

Accuracy

.6% FSR @ 25°C Temperature coefficient of 75 PPM/°C

Time between samples (software selectable)

2000 to 65,535 µsec

Filter time constant

120 ms

Open RTD detection

Indicated by software

Logic side power requirements (typical)

80 mA @ +5 V 112 mA @ +15 V

Indicator light, module

DIAG LED goes off after the module passes its diagnostic tests

Operating temperature range

7°C to 55°C (45°F to 131°F)

98

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 103

RTD Module (6 channel)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

99

Page 104

RTD Module (6 channel)

NOTES

100

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 105

Output 4-20mA Module (6 channel)

Output 4-20mA Module (6 channel) The 4-20mA output module has six independent 4-20mA conversion channels. Each channel converts a 15-bit digital value into a single ended type 4-20mA analog current output signal. The full range of the output signal is 4mA to 20mA, with a 15-bit resolution of one part in 32,768. A typical use for this module is to supply a control signal to valves. This module contains no user adjusted potentiometers or hardware switches. All necessary adjustments are done in software. The DIAG LED goes on briefly while the diagnostic tests are running.

OUTPUT 4-20mA Module (6 CH)

OUTPUT

4-20mA

1 3 5 7 9 11 13 15 17 19 21 23 25

Name of Module Diagnostic LED

Screw terminal connector

Door

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

101

Page 106

Output 4-20mA Module (6 channel) Specification Table

Characteristic

Output 4-20mA (6 ch) specification

Function

Converts a 15-bit digital value into a 4-20mA analog current signal for each of six channels

New Part number

M.1016.9160 (old # 502-03681-02)

Field side connector

25-pin card edge connector, screw terminals

Output channels

6

Resolution

15 bits, or 32,768 steps over the full output range

Zero Offset

.1% FSR (Full Scale Range) over full temperature range

Accuracy

.1% FSR (Full Scale Range) over full temperature range

Output current, max.

20 mA

Output update time increment

100 µsec

Output voltage after power up

VOUT = IOUT * RLOAD

Response to scan loss

All outputs reset to 4mA

Short circuit protection

Current is limited to: IOUT = where IOUT = 4 to 20mA

Indicator light, module

DIAG LED goes off after module passes its diagnostic tests

External power supply +V and current Line and load regulation Maximum noise

+15 V to +24 V: Š 250 mA .5% 100 mV pk-pk

Isolation

Field side has differential isolation via Op Amp buffer between logic and field side The open alarm flag is optically isolated between field and logic side

Logic side power requirements (typical)

125 mA @ +5 V 30 mA @+15 V 18 mA @-15 V

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

102

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 107

Output 4-20mA Module (6 channel)

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

103

Page 108

Output 4-20mA Module (6 channel)

NOTES

104

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 109

MOTION SOLUTIONS PRODUCT GUIDE

PiC Family Miscellaneous Modules

Giddings & Lewis

Page 110

This page is a scan with no text; see it in the PDF.