Page 91

Analog Output ±10V DC Module (8, 4 channel)

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

87

Page 92

Analog Output ±10V DC Module (8, 4 channel)

NOTES

88

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 93

Analog Input ±10V Output (4 Channel)

Analog Input ±10V Output (4 Channel) The module provides: • Four analog input channels • Four analog output channels

The DIAG LED goes on briefly while the diagnostic tests are running.

Analog In/± 10V Out module INPUT

ANALOG

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

Giddings & Lewis

Name of Module Diagnostic LED

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

89

Page 94

Analog Input ±10V Output (4 Channel) Specification Table

Characteristic

Analog In/±10V Out module specifications

Function

Converts a 16-bit digital word into a ±11V analog output signal for each of four channels Converts an analog input signal into a 12-bit digital word for each of four channels.

New Part number

M.1016.9408 (old # 502-03907-03)

Logic side power requirements (typical)

192 mA @ +5V 70 mA @ +15V 53 mA @ -15V Analog Output 1 mA per energized output @ +5V 11 mA per energized output @ +15V 11 mA per energized output @ -15V

Field side connection

40 pin card edge connector, screw terminals

Indicator light, module

DIAG LED goes off after the module passes its diagnostic tests

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

Noise immunity

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

90

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 95

Analog Input ±10V Output (4 Channel)

Analog Output section (4 ch) Output channels

4

Resolution

16 bits, or 65536 steps over the full output range

Output voltage characteristics

Nominal voltage range

± 11V DC

Voltage accuracy @ 11 V

± 5%

Output current, max. @ ±10 V

± 10 mA

Output update time increment

32 µsec

Output voltage after power up

0 V ± 20 mV

Response to scan loss

All outputs reset to 0 V ± 20 mV

Output ripple

< 10 mVRMS at 30 KHz

Short circuit protection

Current limited outputs

Analog Input section (4 ch)

Input channels

4

Resolution

12 bits, or 4096 steps over the full input range

Input sensitivity (software selectable) Voltage ranges

Current range

Unipolar

Bipolar

0 to 10 V 0 to 5 V 0 to 2.5 V 0 to 1.25 V 0 to 1 V 0 to .5 V 0 to .25 V 0 to .125 V

±10V ±5V ±2.5V ±1.25V ±1V ±.5V ±.25V ±.125V

0 to 20 mA, 4 to 20 mA

Common mode maximum voltage ±40V (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage ±11V (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

91

Page 96

Analog Input ±10V Output (4 Channel)

Internal current sense resistor

250 ohms

Maximum current sense resistor power

.12 W

Differential input resistance (each input to ground)

1 M Ohms

Filter time constant - software selection

1 ms, 10 ms, 100 ms

Accuracy

.5% of FSR at 25oC ± 100 PPM /oC

0 Offset

From ±2 counts @ 10 V to ±8 counts @ .125 V

92

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 97

TEMP J-K Thermocouple Module (12 channel)

TEMP J-K Thermocouple Module (12 channel) The input temp J-K thermocouple modules (one for use with grounded thermocouples and one for use with ungrounded thermocouples) has 12 independent thermocouple or analog conversion channels which receive signals from J or K type thermocouples or from a voltage source. Each channel converts an analog signal into a 12-bit digital word which is processed by the PiC. This module requires no hardware adjustments. All adjustments such as Fahrenheit or Celsius scaling and thermocouple ranges are software selectable. The DIAG LED turns on briefly while the diagnostic tests are running.

INPUT TEMP J-K Module (12 CH)

INPUT

TEMP J-K

1 3 5 7 9 11 13 15 17 19 21 23 25

Name of Module Diagnostic LED

Screw terminal connector

Door

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

93

Page 98

TEMP J-K Thermocouple Module (12 channel) Specification Table

Characteristic

Thermocouple module specification

Function

Measure J or K type thermocouple wire inputs or ± 100 mV analog inputs

Part Number

Ungrounded M.1016.9108 (old # 502-03658-02) Grounded M.1016.9289 (old # 502-03809-02)

Field side connector

25-pin card edge connector, screw terminals

Input channels

12

Resolution

12 bits

Input voltage sensitivity (software selectable)

±100 mV

J type thermocouple temperature ranges (at 25°C)

-150°C to 1200°C (-238°F to 2192° F) -35°C to 620°C (-31°F to 1148° F) -10°C to 280°C (+14°F to 536° F)

K type thermocouple temperature ranges (at 25°C)

-200°C to 1300°C (-328°F to 2372° F) -80°C to 820°C (-112°F to 1508° F) -35°C to 415°C (-31°F to 779° F)

J or K type accuracy

J type .37% of the 1350°C span K type .36% of the 1500°C span

±100 mV accuracy

± (50 µV + 1 count + input x 1%)

Time between samples (software selectable)

5000 to 65,535 µsec

Filter time constant

120 ms

Cold junction compensation

0 to 80°C ± 1°C at the sensor

Open thermocouple detection

Indicated by software (No detection for grounded thermocouples)

Logic side power requirements (typi- 80 cal) 112 mA @ +5V mA @ +15V

Indicator light, module

DIAG LED goes off after the module passes its diagnostic tests

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

94

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 99

TEMP J-K Thermocouple Module (12 channel)

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

95

Page 100

TEMP J-K Thermocouple Module (12 channel)

NOTES

96

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis