Page 81
Input/Output 24V DC Source Module (16/8 points)
Input section(16 pt) Input signals (exceed IEC standards) Nominal 24 VDC on, 0 VDC off UH Max (max. allowed voltage)
30V DC
IH Max (max. current @ 30 VDC)
7.5 mA
UL Min
Polarity independent
Guaranteed on
14V DC
IH Min (min. current @ UH Min) 2.8 mA Guaranteed off
5V DC
IT Min (current allowed when off)
.75 mA
Time delay on
1 ms max.
Time delay off
1 ms max.
Protection of logic circuits
Optical isolation between the logic and field sides, 4000 V peak
Input groups
Two groups of 8 IEC Type 1 inputs per NEMA Standard, ICS 3-1983, Table 3-304-2. UL 508 spacing
Output section (8 pt source) DC source requirements
Nominal 24V DC; range 5 to 32 VDC
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of outputs
Two groups of four solid-state switches. UL 508 spacing
Fuse per group of 8 switches
Fast-acting, UL rated 3A 250 VAC metric fuse, 5 x 20 mm
Maximum current per group
2 A of continuous current for the group; each switch is rated at .75 A continuous
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maximum ON
1.8V DC @ .4 A
Surge current, maximum
2.5 A for 40 msec., every 2 seconds
Response to scan loss (present)
Giddings & Lewis
All outputs are reset to the OFF state
PiC900 Controls Motion Solutions Product Guide
77
Page 82
Input/Output 24V DC Source Module (16/8 points)
78
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 83
PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE
PiC 900 Analog Modules
Giddings & Lewis
Page 84
Page 85
Analog Input Module (8 channel)
Analog Input Module (8 channel) The analog input module is designed to interface the PiC with voltage or current output devices to monitor such things as pressure, flow, speed, position, or temperature. There are two versions of the analog input module available. One has 12-bit resolution and the other has 14-bit resolution. The module has eight independent analog conversion channels. Each channel converts a unipolar or bipolar analog input voltage or current into a 12- or 14- bit digital value. This data is transmitted to the PiCs CPU for processing. There is an internal current sense resistor for each channel for use with 0 to 20 mA or 4 to 20 mA devices. This module contains no user adjustable potentiometers or hardware switches. All necessary gain adjustments are done in software. The analog module can be configured as a feedback module using the Servosetup software. The DIAG LED goes on briefly while the diagnostics tests are running. INPUT ANALOG Module (8 CH)
INPUT
ANALOG
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
Giddings & Lewis
Name of Module Diagnostic LED
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
81
Page 86
Analog Input Module (8 channel) Specification Table
Characteristic
Input Analog (8 ch) module specification
Function
Converts an analog input signal into a 12- or 14-bit digital word for each of eight channels.
Part number
12-bit M.1016.9081 (old # 502-03642-03) 14-bit M.1016.9544 (old # 502-04050-00)
Field side connector
40 pin card edge connector, screw terminals
Input channels
8
Resolution
12 bits, or 4096 steps over the full input range 14 bits, or 16384 steps over the full input range
Input sensitivity (software selectable) Voltage ranges
Current range
Unipolar
Bipolar
0 to 10V 0 to 5V 0 to 2.5V 0 to 1.25V 0 to 1V 0 to .5V 0 to .25V 0 to .125V
±10V ±5V ±2.5V ±1.25V ±1V ±.5V ±.25V ±.125V
0 to 20 mA, 4 to 20 mA
Common mode maximum voltage ±40V (The maximum voltage that can safely be applied between either input terminal and circuit common.) Common mode operating voltage (The maximum voltage that can be applied between either input terminal and circuit common with inputs still operating properly.)
±11V
Internal current sense resistor
250 ohms
Maximum current sense resistor power .12 W Differential input resistance (each input to ground)
1 M Ohms
Filter time constant - software selection
1 ms, 10 ms, 100 ms
82
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 87
Analog Input Module (8 channel)
Accuracy of 4-20 mA range
12-bit - .2% of FSR at 25oC 14-bit - .15% of FSR at 25oC ± 100 PPM /oC
Accuracy of all other ranges
12-bit - .5% of FSR at 25oC 14-bit - .2% of FSR at 25oC ± 100 PPM /oC
0 Offset
12-bit-from ±2 counts @ 10 V to ±8 counts @ .125 14-bit-from ±5 counts @ 10 V to ±40 counts @ .125
Logic side power requirements (typical)
120 mA @ +5 V 112 mA @ +15 V
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
83
Page 88
Analog Input Module (8 channel)
NOTES
84
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 89
Analog Output ±10V DC Module (8, 4 channel)
Analog Output ±10V DC Module (8, 4 channel) The ±10V DC output module has eight or four independent D/A conversion channels. It is also called a D/A or Analog Output module. Each channel converts a 16-bit digital word into a differential type analog output signal. The full range of the output signal is -11 V to +11 V, with a resolution of 1 part in 65,536. A typical use for this module is to supply the velocity command to a servo drive. This module contains no potentiometers or hardware switches. All necessary adjustments are done using PiCServoPro/PiCPro commands. The DIAG LED goes on briefly while the diagnostics tests are running.
OUTPUT ±10V DC Module (8, 4 CH) OUTPUT + 10 V DC
1 3 5 7 9 11 13 15 17 19 21 23 25
Name of Module Diagnostic LED
Screw terminal connector
Door
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
85
Page 90
Analog Output ±10V DC Module (8, 4 channel) Specification Table
Characteristic
Output ±10 VDC module specification
Function
Converts a 16-bit digital word into a +/- 11 V analog signal for each of eight or four channels.
Part number
8 ch M.1016.8892 (old # 502-03518-03) 4 ch M.1016.8897 (old # 502-03518-23)
Field side connector
25 pin card edge connector, screw terminals
Output channels
8 4
Resolution
16 bits, or 65536 steps over the full output range
Output voltage characteristics Nominal voltage range
± 11V DC
Voltage accuracy @ 11 V
± 5%
Output current, max. @ ±10V
± 10 mA
Output update time increment
32 µs
Output voltage after power up
0 V ± 20 mV
Response to scan loss
All outputs reset to 0V ± 20 mV
Output ripple
< 10 mVRMS at 30 KHz
Short circuit protection
Current limited outputs
Indicator light, module
DIAG LED goes off after the module passes its diagnostic tests
Logic side power requirements (typical)
For 8 channel module; 43 mA @ +5V 11 mA @ +15V 6 mA @ -15V 2 mA per energized output @ +5 V 12 mA per energized output @ +15V 12 mA per energized output @ -15V For 4 channel module; 37 mA 5 mA 3 mA
@ +5V @ +15V @ -15V
1 mA per energized output @ +5V 11 mA per energized output @+15V
86
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis